Current through Register Vol. 56, No. 21, November 4, 2024
Section 5:14A-13.10 - Electrical equipment, wiring and generators(a) Blowers shall be specific to the inflatable ride to avoid over inflation and possible rupture or under inflation, and shall be suitably guarded at the inlet and outlet. Blowers shall not be sited internally unless they are in a part of the structure not used by riders and out of possible contact with riders.(b) Extension cords shall be of minimum length, proper gauge, and connected to a GFCI (ground fault circuit interrupter) receptacle.(c) Extension cords shall not be connected.(d) Extension cords shall be protected and secured so as not to present a tripping hazard.(e) When an electrical generator is used, the generator shall:1. Be in good operating condition;3. Have a proper spark arresting muffler arranged such that the exhaust fumes are directed away from the blower intake;4. Have circuit protection with ground fault interrupt outlets; and5. Be located at a safe distance from the inflatable ride and the public.(f) All riders shall be removed from the inflatable ride during refueling of the generator.N.J. Admin. Code § 5:14A-13.10