Table 1
Criteria for Determining Leak Classification | Leak Grade Classification | Required Action |
i. Escaping gas resulting in unintentional ignition. | ||
ii. Any leak that can be seen, heard, or felt and is in a location that may endanger the general public or property. | ||
iii. Any leak within 10 feet of an exterior wall of a building or where gas would likely migrate to an exterior wall of a building. | ||
iv. Any reading of gas, which has migrated into or under a building, or into a tunnel. | Grade 1--Most | N.J.A.C. 14:7- |
v. Any leak on a pipeline operating at or above 125 psig. | Severe | 1.19(a)1 |
vi. Any leak with a 20 percent or greater LEL reading in any enclosed space. | ||
vii. Any leak that in the judgment of operator personnel at the scene, is considered an immediate hazard. | ||
viii. Any above ground leak that is not able to be permanently fixed immediately upon discovery by lubrication, adjustment, or tightening. | ||
i. Any leak with a reading below 20 percent of the LEL in any enclosed space. | ||
ii. Any leak detected in a continuously paved area from the inside curb to the exterior wall of a building with a 10 percent or greater LEL reading taken at a distance greater than 10 feet but no greater than 20 feet from the wall. | ||
iii. Any leak detected in a continuously paved area from the inside curb to the exterior wall of a building with a 30 percent or greater LEL reading taken at a distance greater than 20 feet but no greater than 40 feet from the wall. | Grade 2 | N.J.A.C. 14:7-1.19(a)2 |
iv. Any leak detected in an unpaved area from the inside curb to the exterior wall of a building with a 20 percent or greater LEL reading taken at a distance greater than 10 feet but no greater than 20 feet from the wall. | ||
v. Any leak detected in an unpaved area from the inside curb to the exterior wall of a building with a 40 percent or greater LEL reading taken at a distance greater than 20 feet but no greater than 40 feet from the wall. | ||
Any leak that is not classified as a Grade 1 or Grade 2. | Grade 3--Least Severe | N.J.A.C. 14:7-1.19(a)3 |
N.J. Admin. Code § 14:7-1.19
See: 29 N.J.R. 5184(a), 30 N.J.R. 1050(a).
Deleted a former (c).
Recodified from N.J.A.C. 14:7-1.33 and amended by R.2009 d.69, effective 3/2/2009.
See: 40 N.J.R. 4915(a), 41 N.J.R. 1083(a).
Section was "Compliance; supplementary data on tests". Rewrote the section. Former N.J.A.C. 14:7-1.19, Compressor stations: piping, repealed.
Repealed by R.2009 d.291, effective 10/5/2009.
See: 41 N.J.R. 997(a), 41 N.J.R. 3844(b).
Section was "Testing prior to transmission pipeline operation".