Section 39-4-I-2-103 - "Certified Interconnection Equipment" or "Certified Equipment" or "Certified"

"Certified Interconnection Equipment" or "Certified Equipment" or "Certified" means a designation that the Interconnection Equipment meets the following requirements:

1. The Interconnection Equipment has been tested by a Nationally Recognized Testing Laboratory (NRTL) recognized by the United States Occupational Safety and Health Administration (OSHA) in accordance with the following relevant codes and standards:
a. IEEE 1547.1 Standard for Conformance Tests Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems; and
b. Underwriters Laboratories ("UL"), UL 1741 Inverters, Converters, and Controllers for Use in Independent Power Systems;
2. The Interconnection Equipment shall meet the requirements of the most current approved version of each code and standard listed above, as amended and supplemented at the time the Interconnection Request is submitted to be deemed Certified;
3. The Interconnection Equipment has been labeled and is publicly listed by such NRTL at the time of the interconnection application;
4. The Interconnection Customer verifies that the intended use of the Interconnection Equipment falls within the use or uses for which the Interconnection Equipment is labeled and is listed by the NRTL;
5. If the Interconnection Equipment is an integrated equipment package such as an inverter, then the Interconnection Customer shall show that the generator or other electric source being utilized is compatible with the Interconnection Equipment and is consistent with the testing and listing specified for this type of Interconnection Equipment;
6. If the Interconnection Equipment includes only interface components (switchgear, multi-function relays, or other interface devices), an Interconnection Customer shall demonstrate that the generator or other electric source being utilized is compatible with the Interconnection Equipment and is consistent with the testing and listing specified for this type of Interconnection Equipment; and
7. Certified Interconnection Equipment shall not require further design testing or Production Testing, as specified by IEEE Standard 1547 Sections 5.1 and 5.2, or additional Interconnection Equipment modification to meet the requirements. However, nothing herein shall preclude the need for an on-site Witness Test or operational test by the Interconnection Customer.

39 Miss. Code. R. 4-I-2-103

Adopted 1/3/2016
Amended 8/12/2022
Amended 11/6/2022