Minn. R. agency 167, ch. 7080, pt. 7080.1940

Current through Register Vol. 49, No. 20, November 12, 2024
Part 7080.1940 - MULTIPLE SEPTIC TANKS
A. If more than one septic tank is used to obtain the required liquid capacity as determined in part 7080.1930, septic tanks must be connected in series or employ multiple collection systems.
B. When tanks are connected in series, each tank or compartment must contain at least 25 percent of the required total liquid capacity.

Minn. R. agency 167, ch. 7080, pt. 7080.1940

32 SR 1347; 35 SR 1353

Statutory Authority: MS s 115.03; 115.55