Table 1006.2.1 is amended to read as follows:
TABLE 1006.2.1
SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY
Maximum Common Path of Egress Travel Distance (feet) Without Sprinkler System (feet) | ||||
Maximum Occupant Load of Space | Occupant Load | With Sprinkler System (feet) | ||
Occupancy | OL <= 30 | OL > 30 | ||
Ac, E, M | 49 | 75 | 75 | 75a |
B | 49 | 100 | 75 | 100a |
F | 49 | 75 | 75 | 100a |
H-1, H-2, H-3 | 3 | NP | NP | 25b |
H-4, H-5 | 10 | NP | NP | 75b |
I-1, I-2d | 10 | NP | NP | 75a |
I-3 | 10 | NP | NP | 100a |
I-4 | 10 | 75 | 75 | 75a |
R-1 | 10 | 75 | 75 | 75a |
R-2 | 20 | 75 | 75 | 125a |
R-3 | 20 | 75 | 75 | 125a,f |
R-4 | 20 | 75 | 75 | 125a,f |
Se | 29 | 100 | 75 | 100a |
U | 49 | 100 | 75 | 75a |
NP = Not Permitted
a Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2. See Section 903 for occupancies where automatic sprinkler systems are permitted in accordance with Section 903.3.1.2.
b Group H occupancies equipped throughout with an automatic sprinkler system in accordance with Section 903.2.5.
c For a room or space used for assembly purposes having fixed seating, see Section 1029.8.
d For the travel distance limitations in Group I-2, see Section 407.4 of the Building Code.
e The common path of egress travel distance in a Group S-2 open parking garage shall not be more than 100 feet.
f For the travel distance limitations in Groups R-3 and R-4 equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.3, see Section 1006.2.2.6.
IFC section 1006.2.2.1 is amended to read as follows:
IFC section 1006.2.2.4 is amended to read as follows:
IFC section 1006.2.2 is amended by adding a subsection to read as follows:
IFC section 1006.3.3 is amended to read as follows:
(Subsection 1006.3.3.1 remains unchanged.)
Minn. R. agency 151, ch. 7511, pt. 7511.1006