IMC Section 501.2 is amended to read as follows:
Exception:
IMC section 501.4 is amended and subsections added to read as follows:
Exception: Combination makeup air and combustion air systems may be approved by the building official where they are reasonably equivalent in terms of health, safety, and durability.
Exception: If powered makeup air is electrically interlocked and matched to the airflow of the exhaust system, additional makeup air is not required.
Exception: If powered makeup air is electrically interlocked and matched to the airflow of the exhaust system, additional makeup air is not required.
Exception. If a closed combustion solid fuel burning appliance is installed with combustion air in accordance with the manufacturers installation instructions, additional makeup air is not required.
Exception: If powered makeup air is electrically interlocked and matched to the airflow of the exhaust system, additional makeup air is not required.
Exception: If powered makeup air is electrically interlocked and matched to the airflow of the exhaust system, additional makeup air is not required.
Exception: If a closed combustion solid fuel burning appliance is installed with combustion air in accordance with the manufacturers installation instructions, additional makeup air is not required.
Exception: Makeup air is not required in items 1 to 6 when any of the following are demonstrated:
Table 501.4.1
Procedure to Determine Makeup Air Quantity for Exhaust Appliances in Dwellings
One or multiple power vent or direct vent appliances or no combustion appliancesA | One or multiple fan-assisted appliances and power vent or direct vent appliancesB | One atmospherically vented gas or oil appliance or one solid fuel applianceC | Multiple appliances that are atmospherically vented gas or oil appliances or solid fuel appliancesD | |
1. Use the Appropriate Column to Estimate House Infiltration | ||||
a) pressure factor (cfm/sf) | 0.15 | 0.09 | 0.06 | 0.03 |
b) conditioned floor area (sf) | ____ | ____ | ____ | ____ |
(including unfinished basements) | ||||
Estimated House Infiltration (cfm): [1a x 1b] | ____ | ____ | ____ | ____ |
2. Exhaust Capacity | ||||
a) clothes dryer | 135 | 135 | 135 | 135 |
b) 80% of largest exhaust rating (cfm): | ____ | ____ | ____ | ____ |
(not applicable if recirculating system or if powered makeup air is electrically interlocked and matched to exhaust) | ||||
c) 80% of next largest exhaust rating (cfm): | not applicable | ____ | ____ | ____ |
(not applicable if recirculating system or if powered makeup air is electrically interlocked and matched to exhaust) | ||||
Total Exhaust Capacity (cfm): [2a+2b+2c] | ____ | ____ | ____ | ____ |
3. Makeup Air Requirement | ||||
a) Total Exhaust Capacity (from above) | ____ | ____ | ____ | ____ |
b) Estimated House Infiltration (from above) | ____ | ____ | ____ | ____ |
Makeup Air Quantity (cfm): [3a - 3b] | ____ | ____ | ____ | ____ |
(if value is negative, no makeup air is needed) |
AUse this column if there are other than fan-assisted or atmospherically vented gas or oil appliances or if there are no combustion appliances.
BUse this column if there is one fan-assisted appliance per venting system. Other than atmospherically vented appliances may also be included.
CUse this column if there is one atmospherically vented (other than fan-assisted) gas or oil appliance per venting system or one solid fuel appliance.
DUse this column if there are multiple atmospherically vented gas or oil appliances using a common vent or if there are atmospherically vented gas or oil appliances and solid fuel appliances.
Table 501.4.2
Makeup Air Opening Sizing Table for New and Existing Dwellings
One or multiple power vent or direct vent appliances or no combustion appliancesA | One or multiple fan-assisted appliances and power vent or direct vent appliancesB | One atmospherically vented gas or oil appliance or one solid fuel applianceC | Multiple appliances that are atmospherically vented gas or oil appliances or solid fuel appliancesD | Passive makeup air opening duct diameterE,F,G | |
Type of opening or system | (cfm) | (cfm) | (cfm) | (cfm) | (inches) |
Passive Opening | 1-36 | 1-22 | 1-15 | 1-9 | 3 |
Passive Opening | 37-66 | 23-41 | 16-28 | 10-17 | 4 |
Passive Opening | 67-109 | 42-66 | 29-46 | 18-28 | 5 |
Passive Opening | 110-163 | 67-100 | 47-69 | 29-42 | 6 |
Passive Opening | 164-232 | 101-143 | 70-99 | 43-61 | 7 |
Passive Opening | 233-317 | 144-195 | 100-135 | 62-83 | 8 |
Passive Opening with Motorized Damper | 318-419 | 196-258 | 136-179 | 84-110 | 9 |
Passive Opening with Motorized Damper | 420-539 | 259-332 | 180-230 | 111-142 | 10 |
Passive Opening with Motorized Damper | 540-679 | 333-419 | 231-290 | 143-179 | 11 |
Powered Makeup AirH | >679 | >419 | >290 | >179 | Not Applicable |
AUse this column if there are other than fan-assisted or atmospherically vented gas or oil appliances or if there are no combustion appliances.
BUse this column if there is one fan-assisted appliance per venting system. Other than atmospherically vented appliances may also be included.
CUse this column if there is one atmospherically vented (other than fan-assisted) gas or oil appliance per venting system or one solid fuel appliance.
DUse this column if there are multiple atmospherically vented gas or oil appliances using a common vent or if there are atmospherically vented gas or oil appliances and solid fuel appliance(s).
EAn equivalent length of 100 feet of round smooth metal duct is assumed. Subtract 40 feet for the exterior hood and ten feet for each 90-degree elbow to determine the remaining length of straight duct allowable.
FIf flexible duct is used, increase the duct diameter by one inch. Flexible duct shall be stretched with minimal sags.
GBarometric dampers are prohibited in passive makeup air openings when any atmospherically vented appliance is installed.
HPowered makeup air shall be electrically interlocked with the largest exhaust system.
Table 501.4.3(1)
Procedure to Determine Makeup Air Quantity for Exhaust Appliances in Existing Dwellings
(Refer to item 4 in section 501.4.3 to determine applicability of this table)
One or multiple power vent or direct vent appliances or no combustion appliancesA | One or multiple fan-assisted appliances and power vent or direct vent appliancesB | One atmospherically vented gas or oil appliance or one solid fuel applianceC | Multiple appliances that are atmospherically vented gas or oil appliances or solid fuel appliancesD | |
1. Use the Appropriate Column to Estimate House Infiltration | ||||
a) pressure factor (cfm/sf) | 0.15 | 0.09 | 0.06 | 0.03 |
b) conditioned floor area (sf) | ___ | ___ | ___ | ___ |
Estimated House Infiltration (cfm): [1a x 1b] | ___ | ___ | ___ | ___ |
2. Exhaust Capacity | ||||
80% of exhaust rating = Exhaust Capacity (cfm): | ___ | ___ | ___ | ___ |
(not applicable if recirculating system or if powered makeup air is electrically interlocked and matched to exhaust) | ||||
3. Makeup Air Requirement | ||||
a) Exhaust Capacity (from above) | ___ | ___ | ___ | ___ |
b) Estimated House Infiltration (from above) | ___ | ___ | ___ | ___ |
Makeup Air Quantity (cfm): [3a - 3b] | ___ | ___ | ___ | ___ |
(if value is negative, no makeup air is needed) |
AUse this column if there are other than fan-assisted or atmospherically vented gas or oil appliances or if there are no combustion appliances.
BUse this column if there is one fan-assisted appliance per venting system. Other than atmospherically vented appliances may also be included.
CUse this column if there is one atmospherically vented (other than fan-assisted) gas or oil appliance per venting system or one solid fuel appliance.
DUse this column if there are multiple atmospherically vented gas or oil appliances using a common vent or if there are atmospherically vented gas or oil appliances and solid fuel appliances.
Table 501.4.3(2)
Procedure to Determine Makeup Air Quantity for Exhaust Appliances in Existing Dwellings
(Refer to item 5 in section 501.4.3 to determine applicability of this table)
One or multiple power vent or direct vent appliances or no combustion appliancesA | One or multiple fan-assisted appliances and power vent or direct vent appliancesB | One atmospherically vented gas or oil appliance or one solid fuel applianceC | Multiple appliances that are atmospherically vented gas or oil appliances or solid fuel appliancesD | |
1. Use the Appropriate Column to Estimate House Infiltration | ||||
a) pressure factor (cfm/sf) | 0.25 | 0.15 | 0.10 | 0.05 |
b) conditioned floor area (sf) | ___ | ___ | ___ | ___ |
(including unfinished basements) | ||||
Estimated House Infiltration (cfm): [1a x 1b] or Alternative Calculation (by using blower door test)E | ___ | ___ | ___ | ___ |
c) conversion factor | 0.75 | 0.45 | 0.30 | 0.15 |
d) CFM50 value (from blower door test) | ___ | ___ | ___ | ___ |
Estimated House Infiltration (cfm): [1c x 1d] | ___ | ___ | ___ | ___ |
2. Exhaust Capacity | ||||
80% of exhaust rating = Exhaust Capacity (cfm): | ___ | ___ | ___ | ___ |
(not applicable if recirculating system or if powered makeup air is electrically interlocked with exhaust) | ||||
3. Makeup Air Requirement | ||||
a) Exhaust Capacity (from above) | ___ | ___ | ___ | ___ |
b) Estimated House Infiltration (from above) | ___ | ___ | ___ | ___ |
Makeup Air Quantity (cfm): [3a - 3b] | ___ | ___ | ___ | ___ |
(if value is negative, no makeup air is needed) |
AUse this column if there are other than fan-assisted or atmospherically vented gas or oil appliances or if there are no combustion appliances.
BUse this column if there is one fan-assisted appliance per venting system. Other than atmospherically vented appliances may also be included.
CUse this column if there is one atmospherically vented (other than fan-assisted) gas or oil appliance per venting system or one solid fuel appliance.
DUse this column if there are multiple atmospherically vented gas or oil appliances using a common vent or if there are atmospherically vented gas or oil appliances and solid fuel appliances.
EAs an alternative, the Estimated House Infiltration may be calculated by performing a blower door test and multiplying the conversion factor by the CFM50 value.
Table 501.4.3(3)
Procedure to Determine Makeup Air Quantity for Exhaust Appliances in Existing Dwellings
(Refer to item 6 in section 501.4.3 to determine applicability of this table)
One or multiple power vent or direct vent appliances or no combustion appliancesA | One or multiple fan-assisted appliances and power vent or direct vent appliancesB | One atmospherically vented gas or oil appliance or one solid fuel applianceC | Multiple appliances that are atmospherically vented gas or oil appliances or solid fuel appliances | |
1. Use the Appropriate Column to Estimate House Infiltration | ||||
a) pressure factor (cfm/sf) | 0.25 | 0.15 | 0.10 | 0.05 |
b) conditioned floor area (sf) | ___ | ___ | ___ | ___ |
(including unfinished basements) | ||||
Estimated House Infiltration (cfm): [1a x 1b] or Alternative Calculation (by using blower door test)E | ___ | ___ | ___ | ___ |
c) conversion factor | 0.75 | 0.45 | 0.30 | 0.15 |
d) CFM50 value (from blower door test) | ___ | ___ | ___ | ___ |
Estimated House Infiltration (cfm): [1c x 1d] | ___ | ___ | ___ | ___ |
2. Exhaust Capacity | ||||
a) clothes dryer (cfm) | 135 | 135 | 135 | 135 |
b) 80% of largest exhaust rating (cfm): | ___ | ___ | ___ | ___ |
(not applicable if recirculating system or if powered makeup air is electrically interlocked and with exhaust) | ||||
c) 80% of next largest exhaust rating (cfm) | Not applicable | ___ | ___ | ___ |
(not applicable if recirculating system or if powered makeup air is electrically interlocked with exhaust) | ||||
Total Exhaust Capacity (cfm): [2a+2b+2c] | ___ | ___ | ___ | ___ |
3. Makeup Air Requirement | ||||
a) Total Exhaust Capacity (from above) | ___ | ___ | ___ | ___ |
b) Estimated House Infiltration (from above) | ___ | ___ | ___ | ___ |
Makeup Air Quantity (cfm): [3a - 3b] | ___ | ___ | ___ | ___ |
(if value is negative, no makeup air is needed) |
AUse this column if there are other than fan-assisted or atmospherically vented gas or oil appliances or if there are no combustion appliances.
BUse this column if there is one fan-assisted appliance per venting system. Other than atmospherically vented appliances may also be included.
CUse this column if there is one atmospherically vented (other than fan-assisted) gas or oil appliance per venting system or one solid fuel appliance.
DUse this column if there are multiple atmospherically vented gas or oil appliances using a common vent or if there are atmospherically vented gas or oil appliances and solid fuel appliances.
EAs an alternative, the Estimated House Infiltration may be calculated by performing a blower door test and multiplying the conversion factor by the CFM50 value.
Minn. R. agency 151, ch. 1346, MINNESOTA MECHANICAL CODE, pt. 1346.0501
Statutory Authority: MS s 16B.59; 16B.61; 16B.64; 326B.101; 326B.106; 326B.13