IRC Section N1103 is deleted in its entirety and replaced with the following:
Exception: Ducts for which heat gain or loss, without insulation, will not increase the energy requirements of the building.
MINIMUM REQUIRED INSULATION | |
(see notes for explanations) | |
Duct Location | Requirements |
Attics, garages, and ventilated crawl spaces | R-8 and V |
Exterior of building | R-8, V and W |
Inside of building and in unconditioned spaces less than or equal to 15 degrees Fahrenheit | None required |
TD greater than 15 degrees Fahrenheit and less than or equal to 40 degrees Fahrenheit | R-3.3 and V |
TD greater than 40 degrees Fahrenheit | R-5 and V |
Within conditioned spaces, in basements with insulated walls, and in plenums within conditioned spaces | None required |
Intake and exhaust ducts within conditioned spaces* | R-3.3 and V |
Within cement slab or within ground (also see IMC Section 603.7) | R-3.5 |
Notes:
* Insulation required for a distance of 3 feet (914 mm) from the exterior.
TD = Design temperature differential between the air in the duct and the ambient temperature outside of the duct.
V = Vapor retarder required in accordance with the IMC Section 604.11. When a vapor retarder is required, duct insulation required by this section shall be installed without respect to other building envelope insulation.
W = Approved weatherproof barrier.
Location | Design Static Pressure | Minimum Required Sealing |
All locations | Greater than 3.0 inches (750Pa) water gauge | All transverse joints, longitudinal seams, and duct wall penetrations shall be sealed. Ductwork shall be equal to or less than Leakage Class 6 as defined in Section 4 of the SMACNA HVAC Duct Leakage Test Manual* |
Portions of return air ducts completely inside the vapor retarder/ air barrier enclosing conditioned space | 3.0 inches (750Pa) water gauge and less | All transverse joints, longitudinal seams, and duct wall penetrations shall be sealed |
Portions of return air air ducts in the same space as an atmospher- ically vented or fan- assisted appliance | 3.0 inches (750Pa) water gauge and less | All transverse joints, longitudinal seams, and duct wall penetrations shall be sealed |
All locations | Greater than 0.50 to 3.0 inches (125 to 750Pa) water gauge | All transverse joints and duct wall penetrations shall be sealed |
All locations | 0.50 inches (125Pa) water gauge and less | All transverse joints, longitudinal seams, and duct wall penetrations shall have no visible gaps and shall be sufficiently airtight according to Section 1.7 of the SMACNA HVAC Duct Construction Standards - Metal and Flexible |
Exception: All piping located within 6 inches of any heating pipes shall have a minimum of 1 inch insulation with an appropriate vapor jacket.
Exceptions:
Exceptions:
Table N1103.2.4 | ||||||
Insulation Thickness for Nominal Pipe Diameters | ||||||
Fluid Temperature Range Degrees Fahrenheit | Runouts (see item C) | 1 inch (25.4 mm and less) | 1.25 to 2 inches (31.7 to 50.8 mm) | 2.5 to 4 inches (63.5 to 101.6 mm) | 5 to 6 inches (127 to 152 mm) | 8 inches (203 mm) and larger |
Piping System Type - Heating | ||||||
Above 350 | 1.5 | 2.5 | 2.5 | 3.0 | 3.5 | 3.5 |
251-350 | 1.5 | 2.0 | 2.5 | 2.5 | 3.5 | 3.5 |
201-250 | 1.0 | 1.5 | 1.5 | 2.0 | 2.0 | 3.5 |
141-200 | 0.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 |
105-140 | 0.5 | 1.0 | 1.0 | 1.0 | 1.5 | 1.5 |
Piping System Type - Cooling | ||||||
40.55 | 0.5 | 0.5 | 0.75 | 1 | 1 | 1 |
Below 40 (see Item D) | 1 | 1 | 1.5 | 1.5 | 1.5 | 1.5 |
Minn. R. agency 151, ch. 1322, pt. 1322.1103
Statutory Authority: MS s 326B.02; 326B.101; 326B.106; 326B.13