Part 1311.1006 - SECTION 1006, STRUCTURAL

Exception: Structural elements whose demand-capacity ratio considering the change of occupancy is not more than 105 percent of the demand-capacity ratio based on previously approved live loads. The evaluation of demand-capacity ratios and calculation of design gravity loads, forces, and capacities shall account for the cumulative effects of additions and alterations since original construction.