Pressure relief valves for excessive heat or fire protection used on containers covered by parts 1513.0300 to 1513.0380 and 1513.1000 to 1513.1070 must be constructed to discharge at not less than the rates required in this part before the pressure is in excess of 121 percent of the maximum allowable working pressure of the container. Relief protection for any other reason, except refrigerated storage, must use ASME UG-125 through UG-136.
Surface Area, Sq.Ft. | Flow Rate, CFM Air | Surface Area, Sq.Ft. | Flow Rate, CFM Air | Surface Area, Sq.Ft. | Flow Rate, CFM Air |
20 | 258 | 185 | 1,600 | 900 | 5,850 |
25 | 310 | 190 | 1,640 | 950 | 6,120 |
30 | 360 | 195 | 1,670 | 1,000 | 6,380 |
35 | 408 | 200 | 1,710 | 1,050 | 6,640 |
40 | 455 | 210 | 1,780 | 1,100 | 6,900 |
45 | 501 | 220 | 1,850 | 1,150 | 7,160 |
50 | 547 | 230 | 1,920 | 1,200 | 7,410 |
55 | 591 | 240 | 1,980 | 1,250 | 7,660 |
60 | 635 | 250 | 2,050 | 1,300 | 7,910 |
65 | 678 | 260 | 2,120 | 1,350 | 8,160 |
70 | 720 | 270 | 2,180 | 1,400 | 8,410 |
75 | 762 | 280 | 2,250 | 1,450 | 8,650 |
80 | 804 | 290 | 2,320 | 1,500 | 8,900 |
85 | 845 | 300 | 2,380 | 1,550 | 9,140 |
90 | 885 | 310 | 2,450 | 1,600 | 9,380 |
95 | 925 | 320 | 2,510 | 1,650 | 9,620 |
100 | 965 | 330 | 2,570 | 1,700 | 9,860 |
105 | 1,010 | 340 | 2,640 | 1,750 | 10,090 |
110 | 1,050 | 350 | 2,700 | 1,800 | 10,330 |
115 | 1,090 | 360 | 2,760 | 1,850 | 10,560 |
120 | 1,120 | 370 | 2,830 | 1,900 | 10,800 |
125 | 1,160 | 380 | 2,890 | 1,950 | 11,030 |
130 | 1,200 | 390 | 2,950 | 2,000 | 11,260 |
135 | 1,240 | 400 | 3,010 | 2,050 | 11,490 |
140 | 1,280 | 450 | 3,320 | 2,100 | 11,720 |
145 | 1,310 | 500 | 3,620 | 2,150 | 11,950 |
150 | 1,350 | 550 | 3,910 | 2,200 | 12,180 |
155 | 1,390 | 600 | 4,200 | 2,250 | 12,400 |
160 | 1,420 | 650 | 4,480 | 2,300 | 12,630 |
165 | 1,460 | 700 | 4,760 | 2,350 | 12,850 |
170 | 1,500 | 750 | 5,040 | 2,400 | 13,080 |
175 | 1,530 | 800 | 5,300 | 2,450 | 13,300 |
180 | 1,570 | 850 | 5,590 | 2,500 | 13,520 |
Surface Area = Total Outside Surface Area of Container in Square Feet. If the surface area is not stamped on the nameplate or when the marking is not legible, the area can be calculated by using one of the following formulas:
(1) | Cylindrical container with hemispherical heads Area = overall length in feet times outside diameter in feet times 3.1416. |
(2) | Cylindrical container with other than hemispherical heads Area = (overall length in feet plus 0.3 outside diameter in feet) times outside diameter in feet times 3.1416. |
(3) | Spherical container Area = outside diameter in feet squared times 3.1416. |
Flow Rate--CFM Air = cubic feet per minute of air required at standard conditions, 60 degrees Fahrenheit and atmospheric pressure (14.7 psia).
The rate of discharge may be interpolated for intermediate values of surface area. For containers with total outside surface area greater than 2,500 square feet, the required flow rate can be calculated using the formula, Flow Rate CFM Air = 22.11 A0.82 where A = outside surface of the container in square feet.
CONVERSION FACTORS: | ||
ft2 | x 0.092 903 = m2 | |
CFM | x 0.028 317 = m3/min | |
ft | x 0.304 8 = m |
Minn. R. agency 105, ch. 1513, MINIMUM REQUIRED FLOW RATE OF PRESSURE RELIEF DEVICES FOR PROTECTION, pt. 1513.1100
Statutory Authority: MS s 18C.121