Section R. 408.30758b - Water supplyRule 758b Section 411.3 is added to the code to read as follows:
411.3. Water supply. Where hot and cold water are supplied to an emergency shower or eyewash station, the temperature of the water supply shall only be controlled by temperature-actuated mixing value complying with ASSE 1071. Where water is supplied directly to an emergency shower or eyewash station from a water heater, the water heater shall comply with ASSE 1085, See section 607.1.2.Mich. Admin. Code R. 408.30758b