Mich. Admin. Code R. 325.52007

Current through Vol. 24-21, December 1, 2024
Section R. 325.52007 - Exhaust ventilation systems

Rule 7. The minimum rate of exhaust ventilation for places of manufacturing, processing, assembling, maintenance and repair, or storage of material shall be 1 cubic foot of air per minute per square foot of floor area. This amount of exhaust ventilation may be provided by local exhaust, general exhaust, or both. The director may permit a variance if contaminant control is accomplished at a lesser rate of ventilation.

Mich. Admin. Code R. 325.52007

2005 AACS