Mich. Admin. Code R. 408.41868

Current through Vol. 24-21, December 1, 2024
Section R. 408.41868 - Handling at point of use

Rule 1868.

(1) Not more than 1 day's supply, but not to exceed 25 gallons of flammable liquid, shall be permitted to stand outside a cabinet at a place of usage.
(2) A category 1, 2, or 3 flammable liquid shall not be used where there is an open flame or source of ignition within 50 feet of the liquid, unless conditions warrant greater clearance.
(3) Leakage or spillage of a flammable liquid shall be disposed of without creating another hazard.
(4) Natural or mechanical ventilation capable of maintaining the vapor below 10% of the lower explosive limit shall be provided and used when a flammable liquid is used or handled.
(5) Category 1, 2, or 3 flammable liquids shall be kept in closed containers when not in use.

Mich. Admin. Code R. 408.41868

1979 AC; 1983 AACS; 2002 AACS; 2015 MR 7, Eff. April 14, 2015