Current through Register Vol. 51, No. 26, December 27, 2024
Section 09.17.02.04 - Monitors and IndicatorsA. For a boiler, a computerized monitoring system shall qualify as a "24-hour computerized monitoring system and automatic controls," in accordance with Business Occupations and Professions Article, Title 6.5, Annotated Code of Maryland, if it meets the requirements of this regulation.B. For a boiler operating at 30 to 299 horsepower, the system shall monitor and indicate: (1) Stack flue gas temperature;(2) Burner status, including "on" and "off" indicators;(3) Flame safety control status, including "normal" and "flame failure" indicators; and(4) One of the following, as applicable:(b) For hot water boilers, temperature.C. For a boiler operating at 300 horsepower or more, the system shall monitor, indicate, and record: (1) Stack flue gas temperature;(2) Burner status, including "on" and "off" indicators;(3) Flame safety control status, including "normal" and "flame failure" indicators; and(4) One of the following, as applicable:(b) For hot water boilers: Md. Code Regs. 09.17.02.04