Section I-9929 - Other Environmental Conditions
A. A hard surfaced off-the-road parking area to provide parking for one car per five licensed beds shall be provided. This is a minimum requirement and may be exceeded by local ordinances. Where this requirement would impose an unreasonable hardship, a written request for a lesser amount may be submitted to the department for waiver consideration.
B. The nursing facility shall make arrangements for an adequate supply of safe potable water even when there is a loss of normal water supply. Service from a public water supply shall be used, if available. Private water supplies, if used, shall meet the requirements of the LAC Title 51, Public Health-Sanitary Code.
C. An adequate supply of hot water shall be provided which shall be adequate for general cleaning, washing, and sterilizing of cooking and food service dishes and other utensils, and for bathing and laundry use. Hot water supply to the hand washing and bathing faucets in the resident areas shall have automatic control to assure a temperature of not less than 100 degrees Fahrenheit, nor more than 120 degrees Fahrenheit, at the faucet outlet. Supply system design shall comply with the Louisiana state Plumbing Code and shall be based on accepted engineering procedures using actual number and types of fixtures to be installed.
D. The nursing facility shall be connected to the public sewerage system, if such a system is available. Where a public sewerage is not available, the sewerage disposal system shall conform to the requirements of the LAC Title 51, Public Health-Sanitary Code.
E. The nursing facility shall maintain a comfortable sound level conducive to meeting the need of the residents.
F. All plumbing shall be properly maintained and conform to the requirements of the LAC Title 51, Public Health-Sanitary Code.
G. All openings to the outside atmosphere shall be effectively screened. Exterior doors equipped with closers in air conditioned buildings need not have screens.
H. Each room used by residents shall be capable of being heated to not less than 71 degrees Fahrenheit in the coldest weather and capable of being cooled to not more than 81 degrees Fahrenheit in the warmest weather.
I. Lighting levels in all areas shall be adequate to support task performance by staff personnel and independent functioning of residents. A minimum of 6 foot to 10 foot candelas over the entire stairway, corridors, and resident rooms measured at an elevation of 30 inches above the floor and a minimum of 20 foot to 30 foot candelas over areas used for reading or close work shall be available.
J. Corridors used by residents shall be equipped on each side with firmly secured handrails, affixed to the wall. Handrails shall comply with the requirements of the state adopted accessibility guidelines.
K. There shall be an effective pest control program so that the nursing facility is free of pest and rodent infestation.

La. Admin. Code tit. 48, § I-9929

Promulgated by the Department of Health and Hospitals, Office of the Secretary, Bureau of Health Services Financing, LR 24:65 (January 1998), Promulgated by the Department of Health, Bureau of Health Services Financing, LR 421929 11/1/2016).
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:2009.1-2116.