Current through Register Vol. 50, No. 12, December 20, 2024
Section XIII-7705 - Cooldown [49 CFR 193.2505]A. The cooldown of each system of components that is subjected to cryogenic temperatures must be limited to a rate and distribution pattern that keeps thermal stresses within design limits during the cooldown period, paying particular attention to the performance of expansion and contraction devices. [ 49 CFR 193.2505(a) ]B. After cooldown stabilization is reached, cryogenic piping systems must be checked for leaks in areas of flanges, valves, and seals. [ 49 CFR 193.2505(b) ]La. Admin. Code tit. 43, § XIII-7705