Section XI-4337 - Sensing Devices (Formerly section 1337)A. Each operator shall determine the appropriate location for and install sensing devices necessary to monitor the operation of components to detect malfunction which could cause a hazardous condition if permitted to continue; andB. Buildings in which potentially hazardous quantities of carbon dioxide may exist must be continuously monitored by carbon dioxide sensing devices set to activate audible and visual alarms in the building and at the control center.La. Admin. Code tit. 43, § XI-4337
Promulgated by the Department of Natural Resources, Office of Conservation, LR 12:115 (February 1986), repromulgated LR 49312 (2/1/2023).AUTHORITY NOTE: Promulgated in accordance with R.S. 30:4(C)(17) and R.S. 30:1104(A).