Authority: IC 22-13-2-2
Affected: IC 22-12-7; IC 22-13; IC 22-14; IC 36-8-17
Sec. 16.
Chapter 23 is amended as follows:
TABLE 2306.2.3
Tank Type | Class of Liquid | Individual Capacity | Aggregate Capacity in Same Dike of Cluster | Minimum Distance to Nearest Building on Same Property | Minimum Distance from Nearest Fuel Dispenser for Fleet Fueling | Minimum Distance from Nearest Fuel Dispenser for Public Operations | Minimum Distance from Lot Line that is or can be Built Upon, Including Opposite Side of Public Way | Minimum Distance Nearest Side of any Public Way | Minimum Distance Between Tanks |
UL2085 | Class I Liquids | 6,000 Gallons or Less | 48,000 Gallons | 5 | 0 | 25 | 15 | 5 | 3 |
UL2085 | Class I Liquids | Greater Than 6,000 Gallons | 48,000 Gallons | 15 | 0 | 25 | 25 | 15 | 3 |
UL2085 | Class II & III Liquids | Same as Class I Liquids | Same as Class I Liquids | Same as Class I Liquids | Same as Class I Liquids | Same as Class I Liquidsc | Same as Class I Liquids | Same as Class I Liquids | 3 |
Tanks in Vaults | Class I, II & III Liquidsb | 20,000 Gallons or Less | N/A | 0 | 0 | 0 | 0 | 0 | Separate Compart ments for Each Tank |
Other Tanks | Other Tanks | All | N/A | 50 | 50 | N/Ad | 100 | 50 | 3 |
UL142 | Class II & III Liquids | 6,000 Gallons or Less | 18,000 Gallons | 10 | 0a | N/Ad | 30 | 10 | 3 |
UL142 | Class II & III Liquids | 6,001 to 12,000 Gallons | 18,000 Gallons | 30 | 0a | N/Ad | 50 | 30 | 3 |
UL142 | Class I, II & III Liquids | 1,100 Gallons | Single Tank Install Only | 30 | 0a | N/Ad | 50 | 30 | 3 |
For SI: 1 foot = 304.8 mm, 1 gallon = 3.785 Liter
N/A = not applicable
Tanks shall be installed in accordance with Chapter 57 and shall be installed in special enclosures constructed in accordance with Section 2306.2.4 or is listed and approved tank enclosures or materials providing fire protection of not less than two (2) hours. The following additional criteria shall apply:
EXCEPTIONS:
Plans submitted under 675 IAC 12-6, Design Releases, shall include the method of storage and dispensing, quantities and types of liquids to be stored, distances from tanks and dispensers to property lines and buildings, vehicle access, fire appliances, collision barriers, design and construction of tanks and tank supports, secondary containment tank venting, vapor recovery provisions, and emergency controls.
Tanks, special enclosures, and dispensing systems shall be maintained in proper condition. Damage shall be repaired immediately using materials having equal or greater strength and fire resistance.
675 IAC 22-2.5-16