Authority: IC 13-13-5-1; IC 13-14-8-2; IC 13-14-8-7; IC 13-18-3-2
Affected: IC 13-12-3-1; IC 13-13-5-2; IC 13-14-9; IC 13-18-11
Sec. 9.
Systems shall comply with monitoring requirements in section 6(d) of this rule.
Step 1 Required Removal of TOC by Enhanced Coagulation and Enhanced Softening for Subpart H Systems Using Conventional Treatment1,2
Source-Water Alkalinity, mg/L as CaCO3 | |||
Source-Water TOC, mg/L | 0-60 | >60-120 | >1203 |
>2.0-4.0 | 35.0% | 25.0% | 15.0% |
>4.0-8.0 | 45.0% | 35.0% | 25.0% |
>8.0 | 50.0% | 40.0% | 30.0% |
Failure to achieve alternate minimum TOC removal levels is a violation of this subsection.
Enhanced Coagulation Step 2 Target pH | |
Alkalinity (mg/L as CaCO3) | Target pH |
0-60 | 5.5 |
>60-120 | 6.3 |
>120-240 | 7.0 |
>240 | 7.5 |
STEP 1: Calculate actual monthly TOC percent removal, which is equal to: (1 - (treated water TOC/source water TOC)) one hundred (100).
STEP 2: Calculate the required monthly TOC percent removal (from either the table in subsection (b)(2) or from subsection (b)(3)).
STEP 3: Divide the value determined under STEP 1 by the value determined under STEP 2.
STEP 4: Add together the quotients determined under STEP 3 for the last twelve (12) months and divide by twelve (12).
STEP 5: If the quotient calculated in STEP 4 is less than one and zero-hundredths (1.00), the system is not in compliance with the TOC percent removal requirements.
327 IAC 8-2.5-9