Maximum Leak Detection Rate Per Test Section Volume
Test Section Volume (gallons) | Semiannual Test leak detection rate not to exceed (gallons/hour) | Annual Test leak detection rate not to exceed (gallons/hour) |
[LESS THAN]50,000 | 1.0 | 0.5 |
[GREATER THAN OR EQUAL TO]50,000 to [LESS THAN]75,000 | 1.5 | 0.75 |
[GREATER THAN OR EQUAL TO]75,000 to [LESS THAN]100,000 | 2.0 | 1.0 |
[GREATER THAN OR EQUAL TO]100,000 | 3.0 | 1.5 |
Phase In For Piping Segments [GREATER THAN OR EQUAL TO]100,000 Gallons In Volume
First Test | Not later than October 13, 2018 (may use up to 6.0 gph leak rate) |
Second Test | Between October 13, 2018 and October 13, 2021 (may use up to 6.0 gph leak rate) |
Third Test | Between October 13, 2021 and October 13, 2022 (must use 3.0 gph for leak rate) |
Subsequent Tests | After October 13, 2022, begin using semiannual or annual line testing according to the Maximum Leak Detection Rate Per Test Section Volume table in subsection (d)(2)(A)(i) |
Ill. Admin. Code tit. 41, § 175.910