a) Finished water storage structures must be vented as follows: 1) the overflow pipe must not be considered a vent; and2) open construction between the sidewall and roof is not permissible.b) Vents must: 1) prevent the entrance of surface water and rainwater;2) exclude birds and animals;3) exclude insects and dust to the extent practicable;4) on ground level structures, open downward with the opening at least 24 inches above the roof or sod and be covered with 24 mesh non-corrodible screen; and5) on elevated tanks and standpipes: B) be fitted with either four mesh non-corrodible screen, or with finer mesh non-corrodible screen in combination with an automatically resetting pressure-vacuum relief mechanism, as required by the Agency.Ill. Admin. Code tit. 35, § 604.1315
Adopted in R18-17 at 43 Ill. Reg. 8064, effective 7/26/2019.