Section 13.4.8 is amended to add sections 13.4.8.1 and 13.4.8.2 as follows: 13.4.8.1 Inspection, Testing, and Maintenance Label. Satisfactory inspection, testing, and maintenance system's tests shall have an approved inspection label affixed to the fire pump controller. The label shall follow the guidelines found in the water-based fire extinguishing systems inspection labels, tags, and collars.
13.4.8.2 Inspection, Testing, and Maintenance report. An inspection, testing, and maintenance report entitled "Fire Pumps" available on the State Fire Council's website and at each county fire department's fire prevention bureau, or a similar report approved by the AHJ shall be provided to the property owner or agent within fourteen days after the test.
Haw. Code R. tit. 3, Building Code Council, State Fire Code, 58