Section 10063 of the 2018 IEBC is amended to read as follows:
"10063 Seismic loads. Where a change of occupancy results in a building being assigned to a higher risk category, or where the change is from a Group S or Group U occupancy to any occupancy other than Group S or Group U, the building shall satisfy the requirements of Section 1613 of the International Building Code for the new risk category using full seismic forces.
Exceptions:
1. Where a change of use results in a building being reclassified from Risk Category I or II to Risk Category III and the seismic coefficient, SDS, is less than 0.33, compliance with this section is not required.2. Where the area of the new occupancy is less than 10 percent of the building area and the new occupancy is not assigned to Risk Category IV. The cumulative effect of occupancy changes over time shall be considered.3. Unreinforced masonry bearing wall buildings assigned to Risk Category III and to Seismic Design Category A or B shall be permitted to use Appendix Chapter A1 of this code.4. Where the change is from a Group S or Group U occupancy, use of reduced seismic forces shall be permitted". Haw. Code R. tit. 3, Building Code Council, State Building Code, AMENDMENTS TO THE 2018 ICC INTERNATIONAL EXISTING BUILDING CODE (IEBC), 10