Haw. Code R. § 11-280.1-25

Current through September, 2024
Section 11-280.1-25 - Under-dispenser containment
(a) Dispenser systems installed on or after August 9, 2013, other than for airport hydrant fuel distribution systems and UST systems with field-constructed tanks, must have under-dispenser containment that meets the requirements in subsection (c).
(b) Dispenser systems installed on or after the effective date of these rules must have under-dispenser containment that meets the requirements in subsection (c).
(c) Under-dispenser containment required by subsection (a) or (b) must:
(1) Be liquid-tight on its sides, bottom, and at any penetrations;
(2) Be compatible with the substance conveyed by the piping;
(3) Allow for visual inspection and access to the components in the containment system; and
(4) Be monitored for leaks from the dispenser system with a sensing device that signals the operator of the presence of regulated substances.

Haw. Code R. § 11-280.1-25

[Eff 7/15/2018] (Auth: HRS §§ 342L-3, 342L-32) (Imp: HRS §§ 342L-3, 342L-32)
Comp 1/17/2020