GEORGIA STATE MINIMUM STANDARD PLUMBING CODE
(INTERNATIONAL PLUMBING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL PLUMBING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL PLUMBING CODE, 2018 EDITION, shall constitute the official Georgia State Minimum Standard Plumbing Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
CHAPTER 4
FIXTURES, FAUCETS AND FIXTURE FITTINGS
*Revise Table 403.1 'Minimum Number of Required Plumbing Fixturesa' by adding the following requirement under the column labeled 'Other' for line number '7' 'One- and two-family dwellings' and 'Apartment house' descriptions:
Table 403.1 Minimum Number of Required Plumbing Fixturesa
Detached single-family, duplex and multi-family dwelling structures three stories or less in height shall have not less than two exterior hose bibs, sill cocks or outside hydrants with one being located on the side or rear of the structure.
(Effective January 1, 2024)
GEORGIA STATE MINIMUM STANDARD PLUMBING CODE
(INTERNATIONAL PLUMBING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL PLUMBING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL PLUMBING CODE, 2018 EDITION, shall constitute the official Georgia State Minimum Standard Plumbing Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
CHAPTER 4
FIXTURES, FAUCETS AND FIXTURE FITTINGS
* Delete Table 403.1 'Minimum Number of Required Plumbing Fixtures' from the International Plumbing Code 2020 Amendments.
(Effective January 1, 2023)
GEORGIA STATE MINIMUM STANDARD PLUMBING CODE
(INTERNATIONAL PLUMBING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL PLUMBING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL PLUMBING CODE, 2018 Edition, shall constitute the official Georgia State Minimum Standard Plumbing Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
GEORGIA STATE MINIMUM
REQUIREMENTS FOR BOILERS/WATER HEATERS AND PRESSURE VESSELS
The State's minimum requirements for boilers/water heaters and pressure vessels over 200,000 BTU/h (58.61 kW), 210 degrees Fahrenheit or 120 gallons capacity shall be established by O.C.G.A. Title 25, Chapter 15 and the Rules and Regulations of the Office of Insurance and Safety Fire Commissioner.
*Revise the International Plumbing Code, 2018 Edition, to read as follows:
CHAPTER 5
WATER HEATERS
SECTION 506
MINIMUM CAPACITIES FOR RESIDENTIAL WATER HEATERS
*Name Change Table 506 'Minimum Capacities for Residential Water Heaters' to 'Minimum First Hour Rating for Residential Water Heaters' and Revise to read as follows:
TABLE 506 MINIMUM FIRST HOUR RATING FOR RESIDENTIAL WATER HEATERS 1, 2, 3
Number of Bathrooms | 1 to 1.5 | 2 to 2.5 | 3 to 3.5 | ||||||||
Number of Bedrooms | 1 | 2 | 3 | 2 | 3 | 4 | 5 | 3 | 4 | 5 | 6 |
First Hour Rating, in Gallons | 38 | 49 | 49 | 49 | 62 | 62 | 74 | 62 | 74 | 74 | 74 |
FHR= First Hour Rating, 1 gal=3.7854 L, 1 gph=1.5 mL/s
(Effective January 1, 2022)
GEORGIA STATE MINIMUM STANDARD PLUMBING CODE
(INTERNATIONAL PLUMBING CODE WITH GEORGIA STATE AMENDMENTS)
The INTERNATIONAL PLUMBING CODE, 2018 Edition, published by the International Code Council, when used in conjunction with these and any other Georgia State Amendments to the INTERNATIONAL PLUMBING CODE, 2018 EDITION, shall constitute the official Georgia State Minimum Standard Plumbing Code.
GEORGIA STATE AMENDMENTS
CODE REFERENCE:
APPENDICES:
Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.
GEORGIA STATE MINIMUM
REQUIREMENTS FOR BOILERS/WATER HEATERS AND PRESSURE VESSELS
The State's minimum requirements for boilers/water heaters and pressure vessels over 200,000 BTU/h (58.61 kW), 210 degrees Fahrenheit or 120 gallons capacity shall be established by O.C.G.A. Title 25, Chapter 15 and the Rules and Regulations of the Office of Insurance and Safety Fire Commissioner.
*Revise the International Plumbing Code, 2018 Edition, to read as follows:
CHAPTER 1
SCOPE AND ADMINISTRATION
*Delete Chapter 1 'Scope and Administration' entirely without substitution. Chapter 1 to remain in the Code as a reference guide for local governments to use in development of their own Administrative Procedures.
(Effective January 1, 2020)
CHAPTER 2
DEFINITIONS
SECTION 202
GENERAL DEFINITIONS
*Add new definition of 'High Efficiency Plumbing Fixtures and Fittings' to read as follows:
HIGH EFFICIENCY PLUMBING FIXTURES AND FITTINGS.
Dual flush water closet. A dual flush water closet or toilet that the average flush volume of two reduced flushes and one full flush does not exceed 1.28 gallons and is listed to the WaterSense Tank-Type High Efficiency Toilet Specification.
Kitchen faucet or kitchen faucet replacement aerator. A kitchen faucet or kitchen faucet replacement aerator that allows a flow of no more than 2.0 gallons of water per minute.
Lavatory faucet or lavatory faucet replacement aerator. A lavatory faucet or lavatory faucet replacement aerator that allows a flow of no more than 1.5 gallons per minute at a pressure of 60 pounds per square inch and is listed to the WaterSense High Efficiency Lavatory Faucet Specification.
Nonwater urinal. A urinal that is designed to receive and convey only liquid waste through a trap seal into the gravity drainage system without the use of water for such function.
Single flush water closet. A single flush water closet or toilet, including gravity, pressure assisted and electro-hydraulic tank types, that the average flush volume does not exceed 1.28 gallons and is listed to the WaterSense Tank-Type High Efficiency Toilet Specification.
Shower head. A shower head that allows a flow of no more than the average of 2.5 gallons of water per minute at 60 pounds per square inch of pressure.
Urinal. A urinal and associated flush valve that uses no more than 0.5 gallons of water per flush and is listed to the WaterSense Specification for Flushing Urinals.
(Effective January 1, 2020)
*Add new definition of 'Lavatory Faucet' to read as follows:
LAVATORY FAUCET. A faucet that discharges into a lavatory basin in a domestic or commercial installation.
(Effective January 1, 2020)
*Revise the definition of 'Plumbing Fixture' to read as follows:
PLUMBING FIXTURE. A receptacle or device that receives water, waste or both and discharges water, waste, or both into a drainage system, and that is either permanently or temporarily connected to the water distribution system of the premises and demands a supply of water therefrom; discharges wastewater, liquid-borne waste materials or sewage either directly or indirectly to the drainage system of the premises; or requires both a water supply connection and a discharge to the drainage system of the premises. The term includes a kitchen sink, utility sink, lavatory, bidet, bathtub, shower, urinal, toilet, water closet or drinking water fountain.
(Effective January 1, 2020)
*Rename and revise the definition of 'Fixture Fitting' to read as follows:
PLUMBING FIXTURE FITTING. A device that controls and directs the flow of water or conveys sanitary waste. The term includes a sink faucet, lavatory faucet, showerhead, or bath filler.
Supply fitting. A fitting that controls the volume, direction of flow or both of water and is either attached to or accessed from a fixture or is used with an open or atmospheric discharge.
Waste fitting. A combination of components that conveys the sanitary waste from the outlet of a fixture to the connection to the sanitary drainage system.
(Effective January 1, 2020)
*Add new definition of 'Pressurized Flushing Device' to read as follows:
PRESSURIZED FLUSHING DEVICE. A device that contains a valve that:
(Effective January 1, 2020)
*Under definition of 'Sewer' revise 'Public Sewer' to read as follows:
SEWER
Public sewer. That part of the drainage system of pipes installed or maintained by a city, township, county, public utility company or other public entity, on public property, in the street or in an approved dedicated easement of public or community use.
(Effective January 1, 2020)
*Add new definition of 'Toilet' to read as follows:
TOILET. A water closet.
(Effective January 1, 2020)
*Add new definition of 'Water Closet' to read as follows:
WATER CLOSET. A fixture with a water-containing receptor that receives liquid and solid body waste and on actuation conveys the waste through an exposed integral trap into a drainage system and which is also referred to as a toilet.
(Effective January 1, 2020)
*Add new definition of 'WaterSense' to read as follows:
WATERSENSE. A voluntary program of the United States Environmental Protection Agency designed to identify and promote water efficient products and practices.
(Effective January 1, 2020)
*Add new definition of 'WaterSense Listed Plumbing Fixture or Plumbing Fixture Fitting' to read as follows:
WATERSENSE LISTED PLUMBING FIXTURE OR PLUMBING FIXTURE FITTING.
A plumbing fixture or plumbing fixture fitting that has been tested by an accredited third-party certifying body or laboratory in accordance with the WaterSense Program of the United States Environmental Protection Agency and has been listed (certified) by such body or laboratory as meeting the performance and efficiency requirements of the program and has been authorized by the program to use its label.
(Effective January 1, 2020)
CHAPTER 3
GENERAL REGULATIONS
*Add new Section 300 'General Applicability Standards' to read as follows:
SECTION 300
GENERAL APPLICABILITY STANDARDS
The owner or the owner's designated agent shall be responsible for maintenance of plumbing systems. To determine compliance with this provision, the code official shall have the authority to require any plumbing system to be reinspected.
(Effective January 1, 2020)
SECTION 301
GENERAL
*Add new Section 301.1.1 'Requirements for high efficiency plumbing fixtures' to read as follows:
(Effective January 1, 2020)
*Add new Section 301.1.2 'Waiver for requirements of high efficiency plumbing fixtures' to read as follows:
(Effective January 1, 2020)
SECTION 305
PROTECTION OF PIPES AND
PLUMBING SYSTEM COMPONENTS
*Revise Section 305.4.1 'Sewer depth' to read as follows:
SECTION 306
TRENCHING, EXCAVATION AND BACKFILL
*Revise Section 306.3 'Backfilling' to read as follows:
(Effective January 1, 2020)
*Add new Section 306.5 'Open trenches' to read as follows:
SECTION 311
TOILET FACILITIES FOR WORKERS
*Delete Section 311 'Toilet Facilities for Workers' entirely without substitution. (Effective January 1, 2020)
SECTION 314
CONDENSATE DISPOSAL
*Delete Section 314 'Condensate Disposal' entirely without substitution.
(Effective January 1, 2020)
CHAPTER 4
FIXTURES, FAUCETS AND FIXTURE FITTINGS
SECTION 401
GENERAL
*Add new Section 401.4 'Prohibited locations' to read as follows:
Exception: Deep-seal trap floor drains consisting of a minimum 4-inch (102 mm) seal and supplied with a trap primer connected to a water distribution pipe shall be permitted.
(Effective January 1, 2020)
SECTION 403
MINIMUM PLUMBING FIXTURES
*Revise Table 403.1 'Minimum Number of Required Plumbing Fixturesa' to delete the requirements for 'service sink' entirely without substitution.
(Effective January 1, 2020)
*Revise Table 403.1 'Minimum Number of Required Plumbing Fixturesa' by adding the following requirement under the column labeled 'Other' for line number '7' descriptions:
TABLE 403.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES
NO. | CLASSIFICATION | DESCRIPTION | WATER CLOSETS (URINALS: SEE SECTION 424.2) | LAVATORIES | BATHTUBS/ SHOWERS | DRINKING FOUNTAIN (SEE SECTION 410) | OTHER | ||
Male | Female | Male | Female | ||||||
7 | Residential | Apartment house | 1 per dwelling unit | 1 per dwelling unit | ---- | --- | 1 kitchen sink per dwelling unit; 1 automatic clothes washer connection per 20 dwelling units. Detached single-family, duplex and multi-family dwelling structures three stories or less in height shall have not less than two exterior hose bibs, sill cocks or outside hydrants with one being located on the side or rear of the structure. | ||
One-and two-family dwellings and lodging houses with five or fewer guestrooms | 1 per dwelling unit | 1 per dwelling unit | 1 per dwelling unit | ---- | 1 kitchen sink per dwelling unit, 1 automatic clothes washer connection per dwelling unit. Detached singlefamily, duplex and multi-family dwelling structures three stories or less in height shall have not less than two exterior hose bibs, sill cocks or outside hydrants with one being located on the side or rear of the structure |
Remainder of table remains unchanged.
(Effective January 1, 2020)
*Revise exception of Section 403.3.3 'Location of toilet facilities in occupancies other than malls' to read as follows:
Exception: The location and maximum travel distances to required employee toilet facilities in factory, storage and industrial occupancies are permitted to exceed that required by this section, provided that the location and maximum travel distance are approved.
(Effective January 1, 2020)
SECTION 406
AUTOMATIC CLOTHES WASHERS
*Revise Section 406.2 'Waste connection' to read as follows:
(Effective January 1, 2020)
SECTION 410
DRINKING FOUNTAINS
*Revise Section 410.2 'Small occupancies' to read as follows:
(Effective January 1, 2020)
SECTION 412
FAUCETS AND OTHER FIXTURE FITTINGS
*Revise Section 412.1 'Approval' to add a new paragraph at the end of the section:
High efficiency lavatory faucets or lavatory faucet replacement aerators in private use, such as, in residences and apartments, and private (nonpublic) restrooms in hotels and hospitals shall be listed to the WaterSense High Efficiency Lavatory Faucet Specification.
(Effective January 1, 2020)
SECTION 419
LAVATORIES
*Revise Section 419.5 'Tempered water for public hand-washing facilities' to read as follows:
(Effective January 1, 2020)
SECTION 424
URINALS
*Revise Section 424.1 'Approval' to read as follows:
(Effective January 1, 2020)
SECTION 425
WATER CLOSETS
*Revise Section 425.1 'Approval' to read as follows:
(Effective January 1, 2020)
CHAPTER 5
WATER HEATERS
SECTION 501
GENERAL
*Add new Section 501.9 'Water heaters over 200,000 BTU/h' to read as follows:
(Effective January 1, 2020)
SECTION 504
SAFETY DEVICES
*Revise Section 504.6 'Requirements for discharge piping' to read as follows:
(Effective January 1, 2020)
*Add new Section 506 'Minimum Capacities for Residential Water Heaters' to read as follows:
SECTION 506
MINIMUM CAPACITIES FOR RESIDENTIAL WATER HEATERS
(Effective January 1, 2020)
*Add new Table 506 'Minimum Capacities for Residential Water Heaters' to read as follows:
TABLE 506
MINIMUM CAPACITIES FOR RESIDENTIAL WATER HEATERS1, 2, 3
Fuel | Gas | Elec | Gas | Elec | Gas | Elec | Gas | Elec | |
# of Bedrooms | 1 | 2 | 3 | .... | |||||
1 to 1 1/2 Baths | FHR (gal) | 40 | 40 | 45 | 45 | 48 | 48 | .... | .... |
# of Bedrooms | 2 | 3 | 4 | 5 | |||||
2 to 2 1/2 Baths | FHR (gal) | 47 | 47 | 60 | 60 | 62 | 62 | 70 | 70 |
# of Bedrooms | 3 | 4 | 5 | 6 | |||||
3 to 3 1/2 Baths | FHR (gal) | 60 | 60 | 67 | 67 | 70 | 70 | 72 | 72 |
FHR= First Hour Rating, 1 ga1=3.7854 L, 1 gph=1.05 mL/s
(Effective January 1, 2020)
CHAPTER 6
WATER SUPPLY AND DISTRIBUTION
SECTION 604
DESIGN OF BUILDING
WATER DISTRIBUTION SYSTEM
*Revise Table 604.4 'Maximum Flow Rates and Consumption for Plumbing Fixtures and Fixture Fittings' to read as follows:
TABLE 604.4
MAXIMUM FLOW RATES AND CONSUMPTION FOR
PLUMBING FIXTURES AND FIXTURE FITTINGS
PLUMBING FIXTURE OR FIXTURE FITTING | MAXIMUM FLOW RATE OR QUANTITYb |
Lavatory, private | 1.5f gpm at 60 psi |
Lavatory, public (metering) | 0.25 gallon per metering cycle |
Lavatory, public (other than metering) | 0.5 gpm at 60 psi |
Shower heada | 2.5 gpm at 60f psi |
Sink faucet | 2.0f gpm at 60 psi |
Urinal | 0.5f gallons per flushing cycle |
Water closet | 1.28c, d, e, f gallons per flushing cycle |
For SI: 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m, 1 pound per square inch = 6.895 kPa.
(Effective January 1, 2020)
SECTION 605
MATERIALS, JOINTS AND CONNECTIONS
*Revise Section 605.9 'Prohibited joints and connections' to add a new exception to Item 4. 'Saddle-type fittings' to read as follows:
Exception: Saddle-type fittings can be used to connect refrigerator ice makers and humidifiers to an existing residential unit water distribution system provided that the manufacturer's installation instructions for the distribution piping do not prohibit the use of saddle fittings.
(Effective January 1, 2020)
*Revise Section 605.12.3 'Soldered joints' to read as follows:
(Effective January 1, 2020)
*Revise Section 605.13.6 'Soldered joints' to read as follows:
(Effective January 1, 2020)
SECTION 606
INSTALLATION OF THE BUILDING WATER DISTRIBUTION SYSTEM
*Revise Section 606.2 'Location of shutoff valves' to add new Location #4 to read as follows:
(Effective January 1, 2020)
SECTION 607
HOT WATER SUPPLY SYSTEM
*Revise Section 607.1 'Where required' to read as follows:
(Effective January 1, 2020)
SECTION 608
PROTECTION OF POTABLE WATER SUPPLY
*Revise Section 608.17.5 'Connections to lawn irrigation systems' to read as follows:
(Effective January 1, 2020)
SECTION 610
DISINFECTION OF POTABLE WATER SYSTEM
*Revise Section 610.1 'General' to read as follows:
(Effective January 1, 2020)
CHAPTER 7
SANITARY DRAINAGE
SECTION 705
JOINTS
*Revise Section 705.10.2 'Solvent cementing' to read as follows:
(Effective January 1, 2020)
SECTION 706
CONNECTIONS BETWEEN DRAINAGE PIPING AND FITTINGS
*Revise Section 706.3 'Installation of fittings' to read as follows and delete the exception:
(Effective January 1, 2020)
*Delete Section 706.4 'Heel- or side-inlet quarter bends' entirely without substitution.
(Effective January 1, 2020)
SECTION 708
CLEANOUTS
*Revise Section 708.1.2 'Building sewers' to read as follows:
(Effective January 1, 2020)
*Revise Section 708.1.3 'Building drain and building sewer junction' to read as follows:
(Effective January 1, 2020)
*Revise Section 708.1.5 'Cleanout size' to read as follows:
Exceptions:
(Effective January 1, 2020)
CHAPTER 9
VENTS
SECTION 903
VENT TERMINALS
*Revise Section 903.1 'Roof extension' to read as follows:
(Effective January 1, 2020)
*Delete exception to Section 909.1 'Distance of trap from vent' entirely without substitution.
(Effective January 1, 2020)
SECTION 913
WASTE STACK VENT
*Revise Section 913.2 'Stack installation' to read as follows:
(Effective January 1, 2020)
SECTION 914
CIRCUIT VENTING
*Revise Section 914.2 'Vent connection' to read as follows:
(Effective January 1, 2020)
CHAPTER 10
TRAPS, INTERCEPTORS AND SEPARATORS
SECTION 1002
TRAP REQUIREMENTS
*Revise first paragraph of Section 1002.1 'Fixture traps' to read as follows:
(Effective January 1, 2020)
CHAPTER 13
NONPOTABLE WATER SYSTEMS
SECTION 1304
RECLAIMED WATER SYSTEMS
*Add new Section 1304.3.2 'Connections to water supply' to read as follows:
(Effective January 1, 2020)
CHAPTER 14
SUBSURFACE LANDSCAPE IRRIGATIONS SYSTEMS
SECTION 1401
GENERAL
*Add new Section 1401.7 'Gray water' to read as follows:
(Effective January 1, 2020)
CHAPTER 15
REFERENCED STANDARDS
*Revise Chapter 15 'Referenced standards' to add the following new reference standards for WaterSense:
WATERSENSE | WaterSense U.S. Environmental Protection Agency 1200 Pennsylvania Avenue, N.W. Washington, D.C. 20460 |
WaterSense: Tank-Type High Efficiency Toilet Specification | |
202, 420.1 | |
WaterSense: Specification for Flushing Urinals | |
202, 419.1 | |
WaterSense: High-Efficiency Lavatory Faucet Specification | |
202 |
End of Amendments.
Ga. Comp. R. & Regs. R. 110-11-1-.26
O.C.G.A. § 8-2-20 et seq.