Ga. Comp. R. & Regs. 110-11-1-.14

Current through Rules and Regulations filed through October 29, 2024
Rule 110-11-1-.14 - Adoption of the 2003 International Fire Code with Georgia Amendments, Georgia Amendments to the 2000 CABO One and Two Family Dwelling Code, 2000 Standard Building Code, 2000 Standard Plumbing Code, 2000 Standard Mechanical Code, 2000 Standard Gas Code, and the 2000 International Energy Conservation Code, effective January 1, 2005

The Board of Community Affairs hereby adopts the following code editions and amendments as the Georgia State Minimum Standard Codes for Construction:

Click here to view image

INTERNATIONAL FIRE CODE:

A GEORGIA STATE MINIMUM

STANDARD CODE

The INTERNATIONAL FIRE CODE, 2003 Edition, published by the International Code Council, when used in conjunction with these Georgia Amendments, shall constitute this official Georgia State Minimum Standard Code.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Replace all references to the ICC Electrical Code with references to the Georgia State Minimum Standard Electrical Code (National Electrical Code).

(b) Replace all references to the International Energy Conservation Code (IECC) with references to the Georgia State Energy Code for Buildings. The Georgia State Energy Code for Buildings shall be used for efficiency and coefficient of performance ratings of equipment.

SCOPE:

This Georgia State Minimum Standard Code (the International Fire Code) establishes regulations affecting or relating to structures, processes and premises and safeguards from the hazards of fire and explosion arising from the storage, handling or use of structures, materials or devices; from conditions hazardous to life, property or public welfare in the occupancy of structures or premises; and from fire hazards in the structure or on the premise from occupancy or operation. It also applies to the construction, extension, repair, alteration or removal of fire suppression and alarm systems.

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

CHAPTER 1

ADMINISTRATION

SECTION 102

APPLICABILITY

*Delete paragraph 102.5 in its entirety and insert in its place the following:

102.5 Existing and special historic buildings. Refer to 102.1 regarding the application of this Code to existing buildings. Except to the extent required by applicable laws of Georgia, the provisions of this Code are not mandatory for buildings or structures identified by the state, or as appropriate, a local jurisdiction, as historic buildings when such buildings or structures are judged by the fire official to be safe and in the public interest of health, safety and welfare. When evaluating the safety of existing and historic buildings the fire official should consult O.C.G.A. Section 8-2-3, 'Uniform Act for the Application of Building and Fire Related Codes to Existing Buildings,' and the provisions of O.C.G.A. Sections 25-2-13(b)(3) & 25-2-13(b)(4).

(Effective January 1, 2005)

*Delete paragraph 102.6 in its entirety and substitute in its place the following:

102.6 Referenced codes and standards. Where the provisions of this Code or the standards referenced thereby and in Chapter 45 of this Code do not apply to the specific subjects, situations or conditions encountered that involve risks to life and property from the hazards of fire, panic from fear of fire or smoke, or related hazards, compliance with the applicable chapters of the Rules and Regulations of the Safety Fire Commissioner shall be evidence of compliance with this Code.

102.6.1 Basic minimum standard. Except where otherwise stated in this Code, where this Code or the standards referenced thereby and in Chapter 45 of this Code and the provisions of other chapters of the Rules and Regulations of the Safety Fire Commissioner deal with the same subject, situation or condition, the more protective or stringent provision shall be the basic minimum standard to the degree specified in Section 103.

102.6.2 Recognized standards and publications. In Chapter 45 of this Code, under the heading 'NFPA,' the year edition of the National Fire Protection Association codes and standards referenced for purposes of this Code are the specific editions and any modifications thereto adopted by the various chapters of the Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

*Add a new paragraph 102.10 to read as follows:

102.10 General provisions.

102.10.1 The administration, enforcement and penalty provisions of O.C.G.A. Title 25, Chapter 2, and the administrative provisions of the various chapters of the Rules and Regulations of the Safety Fire Commissioner shall apply to and regulate the application and enforcement of this Code. For conditions existing prior to the adoption of this Code, the provisions and modifications adopted in Chapter 120-3-3, under Rule 120-3-3-.04 for Section 4.6 of NFPA 101, the Life Safety Code (LSC), shall apply to the application of this Code. NOTE: Nothing herein shall be construed as prohibiting any local jurisdiction from adopting the deleted portions of Chapter 1 of this Code for local purposes, provided, however, local amendments shall not be less restrictive than the code as adopted in these regulations.

102.10.2 The provisions of O.C.G.A. Title 25, Chapter 2, and other applicable state laws, and the applicable provisions of various chapters of the Rules and Regulations of the Safety Fire Commissioner regarding the requirements for certificates, licenses, permits, plan reviews, inspections, approvals, fees, etc. shall apply. Local authorities having jurisdiction need to be consulted to determine if rules and regulations of the local jurisdiction regarding the requirements for local certificates, licenses, permits, plan reviews, inspections, approvals, fees, etc. also apply.

(Effective January 1, 2005)

SECTION 103

PURPOSE AND INTENT

*Delete Section 103 in its entirety and substitute in its place the following:

103.1 General. The primary purpose of the Code as adopted is to provide, along with other adopted codes and standards, for the reasonable protection of life and property from the hazards created by fire, smoke, explosion, or panic created from a fear of fire or smoke. It is intended that the purpose of this Code be accomplished by:

(1) Coordinating application and enforcement of its provisions with those of other applicable codes, standards and regulations; and

(2) By coordinating the application of its provisions where possible with educational programs or efforts designed to bring about changes in high risk attitudes and behaviors that are the root causes of most fire related problems in Georgia; and

(3) By encouraging or requiring informational and awareness programs designed to make the citizens of Georgia aware of their responsibilities for compliance with this Code as well as the other Rules and Regulations of the Safety Fire Commissioner.

103.2 Coordination of provisions. This Code shall apply to all buildings, structures and facilities as provided in subsection 102.1, except as herein provided and shall be utilized in conjunction with the Life Safety Code (LSC), the International Building Code (IBC), the International Fire Code (IFC), the International Mechanical Code (IMC), and the International Fuel Gas Code (IFGC), to the degree provided in 103.1. Where specific occupancy types and structures have been addressed by additional NFPA standards in addition to the LSC, the specific NFPA standard related to the occupancy type and/or structure shall take precedence over any of the requirements of the International Codes referenced in subsection 1.4.3 of the LSC, except for areas where the International Codes provide for additional requirements related to minimum construction requirements and standpipes.

Exception: This Code does not apply to one- and two-family dwellings or one- and two-family row houses (townhouses) separated by a 2-hour fire wall.

103.3 Resolution of conflicts. Where any technical requirements which are addressed by this Code and the IBC, the IMC, and the IFGC, and other referenced NFPA Codes and/or Standards; and where two or more of the aforementioned codes and/or standards establish differing requirements, whether conflicting or more restrictive, the code conflict resolution principles specified in O.C.G.A. Section 25-2-13(g) shall be applied by the authority having jurisdiction.

"Exception: Where this Code provides for additional requirements related to standpipes."

(Effective January 1, 2005)

SECTION 105

PERMITS

The provisions of Section 105, PERMITS, are not adopted for purposes of the Rules and Regulations of the Safety Fire Commissioner. Local governing authorities may adopt the provisions for local purposes. Refer to 102.10.2 with regard to permits required by the Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

SECTION 107

MAINTENANCE

*Delete Section 107.6 in its entirety and substitute in its place the following:

107.6 Overcrowding. Overcrowding or admittance of any person beyond the approved capacity of a building or a portion thereof shall not be allowed. The Fire Code Official, upon finding any overcrowded conditions or obstructions in aisles, passageways or other means of egress, or upon finding any condition which constitutes a life safety hazard, shall be authorized to cause the event to be stopped until such condition or obstruction is corrected, or to take other actions deemed appropriate to have the condition or obstruction corrected.

(Effective January 1, 2005)

SECTION 108

BOARD OF APPEALS

The provisions of Section 108, BOARD OF APPEALS, are not adopted for purposes of the Rules and Regulations of the Safety Fire Commissioner. Local governing authorities may adopt the provisions for local purposes.

(Effective January 1, 2005)

SECTION 109

VIOLATIONS

The provisions of Section 109, VIOLATIONS, are not adopted for purposes of the Rules of the Safety Fire Commissioner. Local governing authorities may adopt the provisions for local purposes.

(Effective January 1, 2005)

SECTION 110

UNSAFE BUILDINGS

The provisions of Section 110, UNSAFE BUILDINGS, are not adopted for purposes of the Rules and Regulations of the Safety Fire Commissioner. Local governing authorities may adopt the provisions for local purposes.

(Effective January 1, 2005)

SECTION 111

STOP WORK ORDER

The provisions of Section 111, STOP WORK ORDER, are not adopted for purposes of the Rules and Regulations of the Safety Fire Commissioner. Local governing authorities may adopt the provisions for local purposes.

(Effective January 1, 2005)

CHAPTER 3

GENERAL PRECAUTIONS AGAINST FIRE

SECTION 303

ASPHALT KETTLES

*Delete paragraph 303.5 in its entirety and substitute in its place the following:

303.5 Fire extinguishers. There shall be at least one portable fire extinguisher complying with Section 906 and with a minimum 2-A:40-B:C rating within 25 feet (7620 mm) of each asphalt (tar) kettle during the period such kettle is being utilized, and a minimum of one additional portable fire extinguisher with a minimum 2-A:40-B:C rating on the roof being covered.

(Effective January 1, 2005)

CHAPTER 5

FIRE SERVICE FEATURES

SECTION 503

FIRE APPARATUS ACCESS ROADS

*Delete paragraph 503.1.1 in its entirety and substitute in its place the following:

503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction as determined by the local responding fire department or agency. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45.7 m) of all portions of the facility or any portion of the exterior wall of the first story of the building as measured by an approved route around the exterior of the building or facility.

Exception: The local responding fire department or agency is authorized to increase the dimension of 150 feet (45.7 m) where:

1. The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3.

2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided.

3. There are not more than two Group R-3 or Group U occupancies.

(Effective January 1, 2005)

SECTION 504

ACCESS TO BUILDING OPENINGS AND ROOFS

*Add a new paragraph 504.1.1 to read as follows:

504.1.1 Access doors. For fire fighting purposes, there shall be at least one access door in each 100 linear feet (30.5 m) or major fraction thereof of the exterior walls which face the access roadways required by Section 503, unless otherwise required in this code section. In exterior walls designed with continuous rolling dock doors, which face access roadways, there shall be at least one access door in each 200 linear feet (61 m) or fraction thereof. Required access doors shall be a minimum of 3 feet (0.9 m) wide and 6 feet 8 inches (2 m) high and shall be accessible without use of a ladder. Rolling doors are acceptable for such purposes in buildings protected throughout by an approved automatic sprinkler system(s) unless otherwise approved for unsprinklered buildings by the Fire Code Official.

(Effective January 1, 2005)

SECTION 508

FIRE PROTECTION WATER SUPPLIES

*Delete paragraph 508.5.1 in its entirety and substitute in its place the following:

508.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 500 feet (152 m) from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrant mains shall be provided where required by the local responding fire department or agency.

Exceptions:

1. For group R-3 and Group U occupancies, the distance requirement shall be 600 feet (183 m).

2. For buildings equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2, the distance requirement shall be 600 feet (183 m).

(Effective January 1, 2005)

CHAPTER 6

BUILDING SERVICES AND SYSTEMS

SECTION 601

GENERAL

*Add a new paragraph 601.3 to read as follows:

601.3 Where reference is made in this Code to the International Electrical Code, it shall be construed as referencing NFPA 70, National Electrical Code (NEC) as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

SECTION 603

FUEL-FIRED APPLIANCES

*Delete paragraph 603.1.4 in its entirety and substitute in its place the following:

603.1.4 Fuel oil. The grade of fuel oil used in a burner shall be that for which the burner is approved and as stipulated by the manufacturer. The use of crankcase oil or any other oil containing gasoline shall not be used except as permitted in NFPA 31, Standard for the Installation of Oil-Burning Equipment, as adopted by Chapter 120-3-11, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

CHAPTER 7

FIRE-RESISTANCE-RATED CONSTRUCTION

SECTION 703

FIRE-RESISTANCE-RATED CONSTRUCTION

*Add a new paragraph 703.5 to read as follows:

703.5 Barrier identification. All fire and/or smoke barriers or walls shall be effectively and permanently identified with signs or stenciling above a decorative ceiling and/or in concealed spaces with letters a minimum of 2 inches (51 mm) high on a contrasting background spaced a maximum of 12 feet (3.7 m) on center with a minimum of one per wall or barrier. The hourly rating shall be included on all rated barriers or walls. Suggested wording '(__) Hour Fire and Smoke Barrier-Protect All Openings.'

Exception: Existing stenciling acceptable to the authority having jurisdiction.

(Effective January 1, 2005)

CHAPTER 8

INTERIOR FINISH, DECORATIVE MATERIALS AND

FURNISHINGS

SECTION 801

GENERAL

*Delete paragraph 801.1 in its entirety and substitute in its place the following:

801.1 General. The State's minimum requirements for furniture, furnishings, interior finishes, interior trim, decorative materials, and decorative vegetation shall be as required by the LSC, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

CHAPTER 9

FIRE PROTECTION SYSTEMS

SECTION 901

GENERAL

*Delete section 901.4.2 in its entirety and substitute in its place the following:

901.4.2 Provisions in excess of the minimum Code requirements shall, as a minimum, be installed to meet the provisions of the currently adopted code(s) and/or standard(s) which may be applicable to the provision at the time of its installation. Any non-required fire protection system which is added onto, or interconnected with, any required fire protection system (of a similar type), shall be designed, installed, and maintained in accordance with the provisions of the currently adopted code(s) and/or standard(s) which may be applicable to the provision at the time of its installation.

Exceptions:

1. Other installations not conforming with the provisions of the currently adopted code(s) and/or standards(s) applicable to the provisions at the time of its installation if such installations are reported and filed with the local responding fire department and the authority having jurisdiction. In addition such systems shall be identified as required by the authority having jurisdiction.

2. Non-required systems designed, reviewed, installed and approved in accordance with local codes and/or ordinances.

(Effective January 1, 2005)

*Add a new paragraph 901.6.3 to read as follows:

901.6.3 Automatic sprinkler systems and other water based fire extinguishing systems, including fire pumps, required or installed shall be maintained in accordance with NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner, provided however, that any area not specifically addressed by NFPA 25, and which is specifically addressed by this Code, the specific provision of this Code shall be the minimum requirement. A certificate of inspection, as specified by NFPA 25, shall be retained on file at the facility and shall be made available to the Fire Code Official upon request for review for a period of at least three years.

(Effective January 1, 2005)

SECTION 903

AUTOMATIC SPRINKLER SYSTEMS

*Delete paragraph 903.2 in its entirety and substitute in its place the following:

903.2 The requirements for the installation, design, testing and maintenance of automatic sprinkler systems shall be as required by the LSC and, as applicable, NFPA 13, Standard for the Installation of Sprinkler Systems, NFPA 13D, Standard for the Installation of Sprinkler Systems in One- and Two-Family Dwellings and Manufactured Homes, or NFPA 13R, Standard for the Installation of Sprinkler Systems in Residential Occupancies up to and Including Four Stories in Height, as adopted and modified by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner. If there are any areas not specifically addressed by the LSC or by NFPA Standards 13, 13D or 13R, and which are addressed by this Code, the specific provisions of this Code shall be the minimum requirements.

(Effective January 1, 2005)

SECTION 904

ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS

*Delete paragraph 904.11 in its entirety and substitute in its place the following:

904.11 Fire protection for cooking operations

904.11.1 The design, installation, protection and maintenance of cooking equipment, shall be as required by the LSC and NFPA 96, Standard for the Ventilation Control and Fire Protection of Commercial Cooking Operations, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner. If there are any areas not specifically addressed by the LSC or by NFPA 96, and which are addressed by this Code, the specific provisions of this Code shall be the minimum requirements.

904.11.2 Fire suppression systems approved for the protection of commercial cooking equipment shall be designed, installed, and maintained in accordance with the applicable standards adopted in Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

SECTION 905

STANDPIPE SYSTEMS

*Delete paragraph 905.1 in its entirety and substitute in its place the following:

905.1 General. The State's minimum requirements for standpipe systems shall be as required by this Code, International Fire Code (IFC). If there are any areas not specifically addressed by this Code IFC and which are addressed by the LSC, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner, the requirements of the LSC shall be the State minimum requirements. Standpipe systems shall be installed and maintained in accordance with NFPA 14, Standard for the Installation of Standpipe, Private Hydrant, and Hose Systems, and NFPA 25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, as adopted by Chapter120-3-3, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

SECTION 906

PORTABLE FIRE EXTINGUISHERS

*Delete paragraph 906.1 in its entirety and substitute in its place the following:

906.1 Portable fire extinguishers - general. Unless specifically prohibited in the LSC, portable fire extinguishers shall be installed in all buildings, structures and facilities falling under the Rules and Regulations of the Safety Fire Commissioner. Any area not specifically addressed in the LSC and which are addressed by this Code or by any of the standards or codes adopted by the various chapters of the Rules and Regulations of the Safety Fire Commissioner, the provisions addressed by the other applicable standard or code shall be the State minimum requirements.

(Effective January 1, 2005)

*Delete paragraph 906.2 in its entirety and substitute in its place the following:

906.2 General requirements. The selection, installation and maintenance of portable fire extinguishers shall comply with NFPA 10, Standard for Portable Fire Extinguishers, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner.

Exception: The maximum travel distance to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies.

(Effective January 1, 2005)

SECTION 907

FIRE ALARM AND DETECTION SYSTEMS

*Delete paragraph 907.1 in its entirety and substitute in its place the following, while retaining existing subsections:

907.1 Fire alarm systems - general. The State's minimum requirements for fire alarm systems shall be as required by the LSC, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner. If there are any areas not specifically addressed by the LSC and which are addressed by the IBC or by this Code, the requirements of the IBC or this Code shall be the State minimum requirements. Fire alarm systems shall be installed and maintained in accordance with NFPA 72, National Fire Alarm Code, as adopted by Chapter 120-3-3,Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

*Delete paragraph 907.2 in its entirety and substitute in its place the following:

907.2 Smoke detectors - general. The State's minimum requirements for smoke detectors or smoke detection systems shall be as required by the LSC, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner, except where they are specifically addressed by the O.C.G.A. Title 25, Chapter 2. If there are any areas not specifically addressed by the LSC or by O.C.G.A. Title 25, Chapter 2, and which are addressed by the IBC or by this Code, the requirements of the IBC or this Code shall be the State minimum requirements. Such detectors installed as required by O.C.G.A. Title 25, Chapter 2, and the applicable provisions of the Rules and Regulations of the Safety Fire Commissioner shall be properly maintained in an operable condition.

(Effective January 1, 2005)

*Delete paragraph 907.3 in its entirety.

SECTION 909

SMOKE CONTROL SYSTEMS

*Add a new paragraph 909.2.1 to read as follows:

909.2.1 Smoke control. For guidance on designing, installing, acceptance testing, periodic testing, and maintaining engineered smoke-control systems, see the following (see LSC A.23.3.1.3 for existing detention and correctional occupancies):

(1) NFPA 92A, Recommended Practice for Smoke-Control Systems

(2) NFPA 92B, Guide for Smoke Management Systems in Malls, Atria, and Large Areas

(3) NFPA SPP-53, Smoke Control in Fire Safety Design

(4) ASHRAE/SFPE, Design of Smoke Management Systems

(5) ASHRAE, Guideline 5: Guideline for Commissioning Smoke Management Systems.

(Effective January 1, 2005)

SECTION 910

SMOKE AND HEAT VENTS

*Add an exception to paragraph 910.1 to read as follows:

Exception 2: ESFR Sprinkler system(s). In areas of buildings protected throughout by an approved automatic ESFR sprinkler system(s), neither smoke or heat venting nor mechanical smoke removal systems are required.

(Effective January 1, 2005)

CHAPTER 10

MEANS OF EGRESS

SECTION 1001

GENERAL

*Delete paragraph 1001.1 in its entirety and substitute in its place the following:

1001.1 The State's means of egress requirements and all components thereof, with the exception of mezzanines, unless otherwise addressed in the Rules and Regulations of the Safety Fire Commissioner, shall be established by the LSC, as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner.

1001.1.1 The State's minimum requirements for means of egress from mezzanines shall be established by the Life Safety as adopted by Chapter 120-3-3, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

*Add the following paragraph 1001.3 to read as follows:

1001.3 Overcrowding prevention. Overcrowding or admittance of any person beyond the approved capacity of a building or a portion thereof shall not be allowed. It is the responsibility of the manager and the person in charge of a building, structure, or portion thereof not to allow an overcrowded condition or any condition which constitutes a life safety hazard to exist, and to take prompt action to remedy an overcrowded condition or life safety hazard when evidence of such a condition is noted, or when advised or ordered by the Fire Code Official or his/her representative.

(Effective January 1, 2005)

CHAPTER 11

AVIATION FACILITIES

SECTION 1103

GENERAL PRECAUTIONS

*Delete paragraph 1103.5 in its entirety and substitute in its place the following:

1103.5 Dispensing of flammable and combustible liquids. No dispensing, transfer or storage of flammable or combustible liquids shall be permitted inside any building or structure.

Exceptions:

1. As provided in Chapter 34 of this Code, provided the provisions are not less protective than the provisions of any applicable codes and standards adopted by the Rules and Regulations of the Safety Fire Commissioner.

2. When the procedures used follow the guidelines and requirements set forth in NFPA 410 - Standard for Aircraft Maintenance.

(Effective January 1, 2005)

SECTION 1107

HELISTOPS AND HELIPORTS

*Delete paragraph 1107.1 in its entirety and substitute in its place the following:

1107.1 General. Helistops and heliports shall be maintained in accordance with Section 1107. Helistops and heliports on buildings or structures shall be constructed in accordance with the IBC and the requirements set forth by NFPA 418 - Standard for Heliports.

(Effective January 1, 2005)

CHAPTER 27

HAZARDOUS MATERIALS-GENERAL PROVISIONS

SECTION 2701

GENERAL

*Delete paragraph 2701.1 in its entirety and substitute in its place the following:

2701.1 Scope. The State's minimum requirements for the storage, handling, use, and transportation of hazardous materials such as but not limited to: aerosols (Chapter 28); compressed gases (Chapter 30); corrosive materials (Chapter 31); cryogenic fluids (Chapter 32); explosives and fireworks (Chapter 33); flammable and combustible liquids (Chapter 34); flammable gases (Chapter 35); flammable solids (Chapter 36); highly toxic and toxic materials (Chapter 37); liquefied petroleum gases (Chapter 38); organic peroxides (Chapter 39); oxidizers (Chapter 40); pyrophoric materials (Chapter 41); pyroxylin (cellulose nitrate) plastics (Chapter 42); unstable (reactive) materials (Chapter 43); water-reactive solids and liquids (Chapter 44); and other materials deemed hazardous by the Fire Code Official shall be in accordance with the applicable Rules and Regulations of the Safety Fire Commissioner. If there are areas not specifically addressed by the Rules and Regulations of the Safety Fire Commissioner, but which are addressed by this Code, the minimum standards established by this Code shall apply.

(Effective January 1, 2005)

SECTION 2703

GENERAL REQUIREMENTS

*In Table 2703.11.1, add superscript "k" to Oxidizers in the Material column and add the following footnote "k" to read as follows:

k. Group M occupancies with Class 2 and Class 3 oxidizers exceeding these quantities shall include fire protection in accordance with NFPA 430, Section 7-4.

(Effective January 1, 2005)

CHAPTER 33

EXPLOSIVES AND FIREWORKS

SECTION 3306

SMALL ARMS AMMUNITION

*Delete paragraph 3306.5.1.3 in its entirety and substitute in its place the following:

3306.5.1.3 Small arms primers or percussion caps - 10,000 on display in a non-sprinklered building; 25,000 on display in a sprinklered building.

(Effective January 1, 2005)

SECTION 3308

FIREWORKS DISPLAY

*Delete paragraph 3308.1 in its entirety and substitute in its place the following:

3308.1 General provisions. In addition to the requirements of this Section for the display of fireworks the provisions of O.C.G.A. Title 25, Chapter 2, and Chapter 120-3-22, Rules and Regulations of the Safety Fire Commissioner, shall apply. Where there may be a conflict between a provision of this Section and a provision of the above referenced law or regulation, the provision of the above referenced law or regulation shall apply. Nothing in this chapter shall be construed to prohibit the use of fireworks by railroads or other transportation agencies for the signal purposes or illumination, or the sale or use of blank cartridges for a show or theater, or for signal or ceremonial purposes in athletics or sports or for the use by military organizations.

(Effective January 1, 2005)

CHAPTER 38

LIQUEFIED PETROLEUM GASES

*Delete Chapter 38 in its entirety and substitute in its place the following:

The provisions relating to the storage and handling of liquefied petroleum gases shall be those in NFPA 58, Liquefied Petroleum Gas Code, as adopted by Chapter 120-3-16, Rules and Regulations of the Safety Fire Commissioner.

(Effective January 1, 2005)

End of Amendments

Click here to view

GEORGIA STATE MINIMUM

STANDARD PLUMBING CODE

(INTERNATIONAL PLUMBING CODE)

The STANDARD PLUMBING CODE (International Plumbing Code), 2000 Edition, published by the Southern Building Code Congress International, Inc. (International Code Council), when used in conjunction with these Georgia Amendments and the Georgia Amendments adopted effective January 1 of 2001, 2002, 2003 and 2004, shall constitute the official Georgia State Minimum Standard Plumbing Code.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Replace all references to the ICC Electrical Code with references to the Georgia State Minimum Standard Electrical Code (National Electrical Code).

(b) Replace all references to the International Energy Conservation Code (IECC) with references to the Georgia State Energy Code for Buildings. The Georgia State Energy Code for Buildings shall be used for efficiency and coefficient of performance ratings of plumbing equipment.

SCOPE:

The provisions of the Georgia State Minimum Standard Plumbing Code (International Plumbing Code)shall apply to the erection, installation, alteration, replacement, repairs, relocation, addition, use or maintenance of plumbing systems within the State of Georgia. The installation of fuel gas distribution piping and equipment, fuel gas-fired water heaters and water heater venting systems shall be regulated by NFPA 54 (National Fuel Gas Code).

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

GEORGIA STATE MINIMUM

REQUIREMENTS FOR BOILERS/WATER HEATERs aND PRESSURE VESSELS

(a) The State's minimum requirements for boilers/water heaters and pressure vessels over 200,000 BTU (58.56 kW), 210 degrees Fahrenheit or 120 gallons capacity shall be established by O.C.G.A. Title 34, Chapter 11 and the Rules and Regulations of the Georgia Department of Labor.

CHAPTER 3

GENERAL REGULATIONS

SECTION 306

TRENCHING, EXCAVATION AND BACKFILL

*Revise Section 306.3 'Backfilling.'

306.3 Backfilling. Loose earth free from rocks, broken concrete, frozen chunks and other rubble, shall be placed in the trench in 6-inch (153 mm) layers and tamped in place until the crown of the pipe is covered by a minimum of 6 inches (153 mm) of tamped earth. The backfill under and beside the pipe shall be compacted for pipe support. Backfill shall be brought up evenly on both sides of the pipe so that the pipe remains aligned. In instances where the manufacturer's installation instructions for materials are more restrictive than those prescribed by the code, the material shall be installed in accordance with the more restrictive requirement.

(Effective January 1, 2005)

CHAPTER 5

WATER HEATERS

SECTION 502

INSTALLATION

*Revise Section 502.2 'Water heaters installed in garages' to add exception.

502.2 Water heaters installed in garages.

Exception:

Elevation of the ignition source is not required for appliances that are listed and labeled as flammable vapor resistant and for installation without elevation.

(Effective January 1, 2005)

SECTION 504

SAFETY DEVICES

*Revise Section 504.6.1 'Discharge' of the Georgia Amendments revised January 1, 2002 and rename 'Relief discharge.'

504.6.1 Relief discharge. The relief valve shall discharge full size, separately to a safe place of disposal such as a concrete floor, outside the building, an indirect waste receptor, or other approved location. The discharge shall terminate in a manner that does not cause injury to occupants in the immediate area or structural damage to the building. The discharge pipe shall not be trapped. When the relief valve discharge piping goes upward a thermal expansion control device shall be installed on the cold water distribution or service pipe in accordance with Section 607.3.2 (GA Amendments). Provisions shall be made at the low point to drain the trapped portion of the discharge pipe.

(Effective January 1, 2005)

*Revise Section 504.7 'Required pan' of the Georgia Amendments revised January 1, 2002 to add exception.

504.7 Required pan.

Exception:

A pan is not required when the water heater is located on a concrete floor or a wood floor covered with vinyl or tile flooring.

(Effective January 1, 2005)

CHAPTER 6

WATER SUPPLY AND DISTRIBUTION

SECTION 602

WATER REQUIRED

*Revise Section 602.2 'Potable water required' to add exception.

602.2 Potable water required.

Exception:

Fixture shutoff valves are not required on tubs and showers.

(Effective January 1, 2005)

CHAPTER 10

TRAPS, INTERCEPTORS AND SEPARATORS

SECTION 1003

INTERCEPTORS AND SEPARATORS

*Revise Section 1003.4 'Oil separators required' to add sentence.

1003.4 Oil separators required. In elevator pits where oil containment complies with the Georgia Department of Labor Elevator Rules and Regulations, no additional oil separator shall be required.

(Effective January 1, 2005)

*Delete Section 1003.5 'Oil separators' of the Georgia Amendments revised January 1, 2001 without substitution. Revert to original Section 1003.5 'Sand interceptors in commercial establishments.'

(Effective January 1, 2005)

GA STATE AMENDMENTS

*Delete Appendix J in the current Georgia State Amendments without substitution.

(Effective January 1, 2005)

End of Amendments

Click here to view

GEORGIA STATE MINIMUM

STANDARD MECHANICAL CODE

(INTERNATIONAL MECHANICAL CODE)

The STANDARD MECHANICAL CODE (International Mechanical Code), 2000 Edition, published by the Southern Building Code Congress International, Inc. (International Code Council), when used in conjunction with these Georgia Amendments and the Georgia Amendments adopted effective January 1 of 2001 and 2004, shall constitute the official Georgia State Minimum Standard Mechanical Code.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Replace all references to the ICC Electrical Code with references to the Georgia State Minimum Standard Electrical Code (National Electrical Code).

(b) Replace all references to the International Energy Conservation Code (IECC) with references to the Georgia State Energy Code for Buildings. The Georgia State Energy Code for Buildings shall be used for efficiency and coefficient of performance ratings of mechanical equipment.

SCOPE:

The provisions of the Georgia State Minimum Standard Mechanical Code (International Mechanical Code) shall regulate the design, installation, maintenance, alteration and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within buildings. This code shall also regulate those mechanical systems, system components, equipment and appliances specifically addressed herein. The installation of fuel gas distribution piping and equipment, fuel gas-fired appliances and fuel gas-fired appliance venting systems shall be regulated by the Georgia State Minimum Standard Gas Code (International Fuel Gas Code).

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

GEORGIA STATE MINIMUM

REQUIREMENTS FOR BOILERS/WATER HEATERS AND PRESSURE VESSELS

(a) The State's minimum requirements for boilers/water heaters and pressure vessels over 200,000 BTU (58.56 kW), 210 degrees Fahrenheit or 120 gallons capacity shall be established by O.C.G.A. Title 34, Chapter 11 and the Rules and Regulations of the Georgia Department of Labor.

CHAPTER 4

VENTILATION

SECTION 403

MECHANICAL VENTILATION

*Revise Section 403.3 'Ventilation rate' to add exception.

403.3 Ventilation rate.

Exception #2:

The minimum outdoor airflow rate may also be determined in accordance with Addendum "n" of ASHRAE 62-2001 as an alternate method.

(Effective January 1, 2005)

CHAPTER 6

DUCT SYSTEMS

SECTION 603

DUCT CONSTRUCTION AND INSTALLATION

*Revise Section 603.1 'General' to add.

603.1 General.

Ducts and duct systems complying with the following applicable standards shall be deemed as meeting the intent of this code:

1. SMACNA Fibrous Glass Duct Construction Standards; or SMACNA HVAC Duct Construction Standards-Metal and Flexible; or NAIMA Fibrous Glass Duct Construction Standards.

2. ASHRAE Handbook

3. UL-181; UL-181A and UL-181B

4. ADC Flexible Duct Performance and Installation Standards

5. ACCA Manual D-Residential Duct Systems; ACCA Manual Q-Commercial Low Pressure, Low Velocity Duct System Design.

(Effective January 1, 2005)

CHAPTER 15

REFERENCED STANDARDS

*Revise Chapter 15 'Referenced Standards' to add.

(Effective January 1, 2005)

ACCA

Air Conditioning Contractors of America 2800 Shirlington Road, Suite 300 Arlington, VA 22206

Standard reference number

Title

Referenced in code section number

Manual D

Residential Duct Systems

603.1

Manual Q

Commercial Low Pressure, Low Velocity

Duct System Design

603.1

ADC

Air Diffusion Council 1000 East Woodfield Road, Suite 102 Schaumburg, IL 60173

Standard reference number

Title

Referenced in code number section

Flexible Duct Performance and Installation Standards

(Third Edition 2003)

603.1

NAIMA

North American Insulation Manufacturers Association 44 Canal Center Plaza, Suite 310 Alexandria, VA 22314

Standard reference number

Title

Referenced in code section number

Fibrous Glass Duct Construction Standards 603.1

UL

Underwriters Laboratories Inc. 333 Pfingsten Road Northbrook, IL 60062-2096

Standard reference number

Title

Referenced in code section number

181A-94

Standard for Closure Systems for Use with Rigid Air Ducts and Air Connectors

603.1

181B-95

Standard for Closure Systems for Use with Flexible Air Ducts and Air Connectors

603.1

End of Amendments

Click here to view

GEORGIA STATE MINIMUM

STANDARD BUILDING CODE

(INTERNATIONAL BUILDING CODE)

The STANDARD BUILDING CODE (International Building Code), 2000 Edition, published by the Southern Building Code Congress International, Inc. (International Code Council), when used in conjunction with these Georgia Amendments and the Georgia Amendments adopted effective January 1 of 2002, 2003 and 2004, shall constitute the official Georgia State Minimum Standard Building Code.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Replace all references to the ICC Electrical Code with references to the Georgia State Minimum Standard Electrical Code (National Electrical Code).

(b) Replace all references to the International Energy Conservation Code (IECC) with references to the Georgia State Energy Code for Buildings. The Georgia State Energy Code for Buildings shall be used for efficiency and coefficient of performance ratings of equipment.

SCOPE:

The provisions of the Georgia State Minimum Standard Building Code (International Building Code) shall apply to the construction, alteration, movement, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of every building or structure or any appurtenances connected or attached to such buildings or structures.

Exception: Detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories high with separate means of egress and their accessory structures shall comply with the Georgia State Minimum Standard One and Two Family Dwelling Code (International Residential Code for One- and Two-Family Dwellings).

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

CHAPTER 2

DEFINITIONS

SECTION 202

DEFINITIONS

*Revise Section 202 'Definitions' to add definition of 'Elevator Door Opening Protective Device.'

ELEVATOR DOOR OPENING PROTECTIVE DEVICE. Any device that either independently or in conjunction with the (elevator) door assembly allows the device(s) to meet the requirements of Section 714.2.3.

(Effective January 1, 2005)

CHAPTER 4

SPECIAL DETAILED REQUIREMENTS BASED ON

USE AND OCCUPANCY

SECTION 403

HIGH-RISE BUILDINGS

*Delete Section 403.9 'Elevators,' rename 'Elevators and elevator lobbies' and substitute.

403.9 Elevators and elevator lobbies.

403.9.1 All elevators on all floors shall open into elevator lobbies which are separated from the remainder of the building by non-rated smoke partitions with automatic or self-closing doors in accordance with Section 714.

Exceptions:

1. Elevator lobbies within an atrium.

2. Elevators which are located on the exterior of the building and served by exterior walkways.

3. The main entrance level of the building except as required by Section 403.9.5.

4. Elevator shafts which connect three contiguous stories or less within the building.

5. Elevators which serve open air parking decks and not more than one floor in accordance with Section 406.3 beneath other occupancies.

6. Hoistways which are provided with a mechanical smoke control system designed to resist the migration of smoke to other floors through the hoistway in accordance with Section 513 of the International Mechanical Code.

7. In buildings protected with an approved automatic sprinkler system in accordance with Section 903, lobbies are not required where a listed elevator door opening protective device, in compliance with Section 1001.1 (GA Amendments), is provided at the hoistway opening other than at the designated primary and alternate floors of elevator return, subject to approval by the authority having jurisdiction.

403.9.2 Each elevator lobby shall have at least one means of egress, shall contain at least thirty square feet (2.79 m2) for each elevator cab discharging into the lobby, but no area less than the largest cab discharging into the lobby, and shall have no lobby dimension less than five feet (1.53 m). Openings in the elevator lobby shall be limited to those required for access to theelevators and for egress from the building. Approved smoke dampers shall be installed where mechanical ducts penetrate the lobby enclosure.

403.9.3 Each elevator lobby shall be provided with an approved smoke detector located on the lobby ceiling. When the detector is activated, elevator doors shall not open and all cars serving that lobby are to return to the main floor and be under manual control only. If the main floor detector or a transfer floor detector is activated, all cars serving the main floor or transfer floor shall return to a location approved by the fire department and building official and be under manual control only. The detector may serve to close the lobby doors.

403.9.4 Elevator operation and installation shall be in accordance with Chapter 30.

403.9.5 Designated floors for elevator return. New elevators, escalators, dumbwaiters, and moving walks shall be installed in accordance with the requirements of ANSI/ASME A17.1, Safety Code for Elevators and Escalators. The elevator lobby of the designated floor and the alternate floor specified by Rule 2.27.3 shall be separated from the remainder of the building by 1 hour fire-rated construction. In buildings equipped with automatic sprinkler protection, smoke partitions in accordance with Section 8.2.4 (NFPA 101, 2000 Edition) may be used in lieu of 1 hour fire-rated construction. Except health care occupancies, openings in the elevator lobby shall be limited to those required for access to the elevators from exit access corridors only. Elevator lobbies may be used as part of the means of egress from the building.

Exceptions:

1. Elevator lobbies are not required within an atrium.

2. Elevator lobbies are not required where elevators are installed on open exterior walls.

3. Elevator lobbies are not required where elevators are installed in open air parking structures.

4. Elevator lobbies are not required in buildings three stories or less with vertical openings protected in accordance with the applicable occupancy chapter.

5. Elevator lobbies are not required in mercantile occupancies that have properly protected openings for escalators or stairs.

6. Existing installations acceptable to the authority having jurisdiction.

(Effective January 1, 2005)

CHAPTER 7

FIRE-RESISTANCE-RATED CONSTRUCTION

SECTION 707

SHAFT AND VERTICAL EXIT ENCLOSURES

*Delete Section 707.14.1 'Elevator lobby' of the Georgia Amendments revised January 1, 2002. Delete Section 707.14 'Elevator and dumbwaiter shafts' and substitute.

707.14 Elevator and dumbwaiter shafts. Elevator hoistway and dumbwaiter enclosures shall be constructed in accordance with this section, Sections 403.9 and 707.4 and Chapter 30.

707.14.1 Elevator lobby. Elevator lobbies opening onto floors required to be provided with fire-rated exit access corridors and elevator lobbies in high-rise buildings shall be provided with an elevator lobby at each floor. The elevator lobby shall be separated from exit access corridors by 1 hour fire barriers with all duct penetrations protected with approved automatic smoke dampers. Each elevator lobby shall have at least one means of egress, shall contain atleast thirty square feet (2.79 m2) for each elevator cab discharging in the lobby, but no area less than the largest cab discharging into the lobby, and shall have no lobby dimension less than five feet (1.53 m). Openings into the elevator lobby shall be limited to those required for access to the elevators and for egress from the building.

Exceptions:

1. In office buildings, elevator lobbies are not required from a street floor lobby provided the entire street floor is equipped with an automatic sprinkler system in accordance with Section 903.3.1.1, except as provided in Section 707.14.2.

2. Elevators not required to be located in a shaft in accordance with Section 707.2.

3. Where additional doors are provided in accordance with Section 3002.6.

4. In other than Groups I-2 and I-3, and buildings which are not classified as high-rise buildings, lobby separation is not required where the building is protected by an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1 or 903.3.1.2.

5. Elevator lobbies are not required within an atrium.

6. Elevators which are located on the exterior of the building and served by exterior walkways.

7. Elevators which serve open air parking decks in accordance with Section 406.3 beneath other occupancies.

8. Hoistways which are provided with mechanical systems designed to resist the passage of smoke to other floors through the hoistway.

9. Lobbies are not required where a listed elevator door opening protective device, in compliance with Section 1001.1 (GA Amendments), is provided at the hoistway opening other than at the designated primary and alternate floors of elevator return, subject to approval by the authority having jurisdiction.

10. Elevator shafts which connect three contiguous stories or less within the building.

707.14.2 Designated floors for elevator return. New elevators, escalators, dumbwaiters, and moving walks shall be installed in accordance with the requirements of ANSI/ASME A17.1, Safety Code for Elevators and Escalators. The elevator lobby of the designated floor and the alternate floor specified by Rule 2.27.3 shall be separated from the remainder of the building by 1 hour fire-rated construction. In buildings equipped with automatic sprinkler protection, smoke partitions in accordance with Section 8.2.4 (NFPA 101, 2000 Edition) may be used in lieu of 1 hour fire-rated construction. Except health care occupancies, openings in the elevator lobby shall be limited to those required for access to the elevators from exit access corridors only. Elevator lobbies may be used as part of the means of egress from the building.

Exceptions:

1. Elevator lobbies are not required within an atrium.

2. Elevator lobbies are not required where elevators are installed on open exterior walls.

3. Elevator lobbies are not required where elevators are installed in open air parking structures.

4. Elevator lobbies are not required in buildings three stories or less with vertical openings protected in accordance with the applicable occupancy chapter.

5. Elevator lobbies are not required in mercantile occupancies that have properly protected openings for escalators or stairs.

6. Existing installations acceptable to the authority having jurisdiction.

(Effective January 1, 2005)

CHAPTER 16

STRUCTURAL DESIGN

SECTION 1615

EARTHQUAKE LOADS-SITE GROUND MOTION

*Revise Section 1615.1 'General procedure for determining maximum considered earthquake and design spectral response accelerations' to add exception and two new figures.

1615.1 General procedure for determining maximum considered earthquake and design spectral response accelerations.

Exception #2:

As an alternate Figures 1615(11) and 1615(12) shall be permitted to be used in Georgia.

(Effective January 1, 2005)

Click here to view

FIGURE 1615(11)

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR GEORGIA OF 0.2 SEC SPECTRAL RESPONSE ACCELERATION (5 PERCENT OF CRITICAL DAMPING), SITE CLASS B

Click here to view

FIGURE 1615(12)

MAXIMUM CONSIDERED EARTHQUAKE GROUND MOTION FOR GEORGIA OF 1.0 SEC SPECTRAL RESPONSE ACCELERATION (5 PERCENT OF CRITICAL DAMPING), SITE CLASS B

SECTION 1616

EARTHQUAKE LOADS-CRITERIA SELECTION

*Revise Section 1616.3 'Determination of seismic design category' to add exception.

1616.3 Determination of seismic design category.

Exception:

The seismic design category is permitted to be determined from Table 1616.3(1) alone when all of the following apply:

1. The approximate fundamental period of the structure, Ta, in each of the two orthogonal directions determined in accordance with 1617.4.2.1 is less than 0.8 Ts, determined in accordance with 1615.1.4;

2. Equation 16-35 is used to determine the seismic response factor, Cs; and

3. The diaphragms are rigid as defined in Section 1602.

(Effective January 1, 2005)

CHAPTER 23

WOOD

SECTION 2304

GENERAL CONSTRUCTION REQUIREMENTS

*Revise Section 2304.9.5 'Fasteners in preservative-treated and fire-retardant-treated wood' and rename 'Fasteners in naturally durable, preservative-treated and fire-retardant-treated wood.'

2304.9.5 Fasteners in naturally durable, preservative-treated and fire-retardant-treated wood. Fasteners for naturally durable wood shall be resistant to corrosion or be protected to resist corrosion. Where sacrificial coatings are applied to fasteners, a minimum coating thickness capable of protecting the fastener for the expected service life of the structure shall be provided. Fasteners for preservative-treated and fire-retardant-treated wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. Fastenings for wood foundations shall be as required in AF&PA Technical Report No. 7. The coating weights for zinc-coated fasteners shall be in accordance with ASTM A 153M or ASTM A 641, Supplementary Requirements.

(Effective January 1, 2005)

End of Amendments

Click here to view

GEORGIA STATE

ENERGY CODE FOR BUILDINGS

(INTERNATIONAL ENERGY CONSERVATION CODE)

The GEORGIA STATE ENERGY CODE FOR BUILDINGS (International Energy Conservation Code), 2000 Edition, published by the International Code Council, when used in conjunction with these Georgia Supplements and Amendments and the Georgia Supplements and Amendments adopted effective January 1 of 2003, shall constitute this official Georgia State Minimum Standard Code.

GEORGIA STATE AMENDMENTS

SCOPE:

Each chapter of these Georgia Supplements and Amendments corresponds with a chapter of the International Energy Conservation Code (IECC).

Chapter 1: Administration and Enforcement.

Chapter 2: Definitions.

Chapter 3: Design Conditions. 'The criteria of this chapter establish the design conditions for use with Chapters 4, 5, 6 and 8.'

Chapter 4: Residential Building Design by Systems Analysis and Design of Buildings Utilizing Renewable Energy Sources. 'This chapter establishes design criteria in terms of total energy use by a residential building, including all of its systems.' (One method by which to achieve compliance for low-rise residential construction.)

Chapter 5: Residential Building Design by Component1 Performance Approach. 'Residential buildings or portions thereof that enclose conditioned space shall be constructed to meet the requirements of this chapter.' (One method by which to achieve compliance for low-rise residential construction.)This chapter offers the use of 'trade-offs,' whereby values between building components may be substituted or traded-off for compliance. A properly completed Georgia Trade-Off Worksheet2 or the use of appropriate computer software (REScheck3) may be used to validate any trade-off.

Chapter 6: Simplified Prescriptive Requirements for Residential Buildings, Type A-1 and A-2. 'This chapter sets forth energy-efficiency-related requirements for the design and construction of Type A-1 and A-2 residential buildings.' (One method by which to achieve compliance for low-rise residential construction.)

Chapter 7: Building Design for All Commercial Buildings. Commercial buildings [except those that comply with Chapter 8, Design by Acceptable Practice for Commercial Buildings; the Single Step Compliance for Simple Commercial Buildings; or appropriate computer software (COMcheck3)] shall meet the requirements of ANSI/ASHRAE/IESNA Standard 90.1-2001. (One method by which to achieve compliance for commercial and high-rise residential construction.)

Chapter 8: Design by Acceptable Practice for Commercial Buildings. 'The requirements contained in this chapter are applicable to commercial buildings, or portions of commercial buildings.' (One method by which to achieve compliance for commercial and high-rise residential construction.)

Chapter 9: Referenced Standards.

Appendix A.

Appendix B. Provides additional prescriptive methods by which to achieve compliance, simple methods and forms to assist in compliance calculations, and illustrations to assist in the understanding of compliance requirements.

Individual structures should follow a single compliance method and not a combination of compliance methods. The 'basic requirements' of the International Energy Conservation Code (IECC) apply to all compliance methods.

Where these Georgia Supplements and Amendments conflict with either the International Energy Conservation Code (IECC)or ANSI/ASHRAE/IESNA Standard 90.1-2001, these Georgia Supplements and Amendments shall take precedence.

Air infiltration accounts for substantial heat loss, heat gain and moisture migration in a building. Proper sealing around all doors, windows and other envelope penetrations through the walls, ceiling and foundation is as important to code compliance as are proper insulation R-values and component U-values.

It is not the intention of this code to abridge safety or health. Where the International Energy Conservation Code (IECC) and these Georgia Supplements and Amendments conflict with other mandatory State Minimum Standard Codes, the International Energy Conservation Code (IECC) and these Georgia Supplements and Amendments shall be enforced as written provided safety, health or environmental requirements of other mandatory State Minimum Standard Codes are not abridged.

CODE REFERENCE:

(a) Replace all references to ASHRAE/IESNA 90.1-1999 with references to ANSI/ASHRAE/IESNA 90.1-2001.

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

________________

1. 'Component' refers to a particular element of a building, such as a ceiling, an exterior wall, a floor, etc.

2. For the 'Georgia Trade-Off Worksheet,' see Appendix B.

3. REScheck and COMcheck are computer programs developed by Pacific Northwest National Laboratories for the U.S. Department of Energy to assist in demonstration of compliance with the International Energy Conservation Code (IECC). They can be obtained from the D.O.E. by calling (800) 270-CODE (2633) or free of charge online at www.energycodes.gov.

CHAPTER 3

DESIGN CONDITIONS

SECTION 302

THERMAL DESIGN PARAMETERS

*Revise Figure 302.1(11) 'Georgiaa' to change Cherokee County and Forsyth County from Climate Zone 8 to Climate Zone 7A.

(Effective January 1, 2005)

CHAPTER 5

RESIDENTIAL BUILDING DESIGN BY COMPONENT

PERFORMANCE APPROACH

SECTION 502

BUILDING ENVELOPE REQUIREMENTS

*Revise Note #2 of Section 502.2.1.2 'Roof/ceiling.'

502.2.1.2 Roof/ceiling.

Note #2:

Weather-stripped access doors (minimum U-0.35), weather-stripped hatches/scuttle hole covers (minimum R-19 insulation or U-0.05), or weather-stripped disappearing/pull-down stairs (minimum U-0.35) shall be calculated as a sub-element with a U-factor of U-0.05 or insulation R-value of R-19. Weather-stripping, factory applied or approved by the local Building Official, shall be deemed to meet Table 502.2a Footnote a, Sections 502.1.4 Air leakage and 502.1.4.2 Caulking and sealants and Table 502.2.1 in Appendix B.

(Effective January 1, 2005)

*Revise Section 502.2.1.6 'Basement walls,' add superscript '1' to title and add exceptions and notes.

502.2.1.6 Basement walls1. The exterior walls of conditioned basements2 shall have a thermal transmittance value not exceeding the valve given in Table 502.2 from the top of the basement wall to a depth of 10 feet (3048 mm) below grade, or to the level of the basement floor, whichever is less.

Exceptions:

1. For conditioned basements in Climate Zones 4B, 5A, 6B and 7A, insulate the Mass Wall with minimum R-5 insulation and the cavity in Stud Walls, Cripple Walls and Bands with minimum R-11 insulation.

2. For conditioned basements in Climate Zone 8, insulate the Mass Wall with minimum R-6 insulation and the cavity in Stud Walls, Cripple Walls and Bands with minimum R-11 insulation.

When using Exceptions 1 or 2, the basement is "Deemed to Comply" with the Georgia State Energy Code; if the rest of the dwelling complies by any method in Chapters 5 or 6 or by another approved compliance method, the whole dwelling is "Deemed to Comply."

Note 1: IECC defines a 'basement wall' as 'the opaque portion of a wall which encloses one side of a basement and having an average below-grade area greater than or equal to 50 percent of its total wall area, including openings.'

Note 2: 'Basement' is defined in the Georgia Amendments to the CABO One and Two Family Dwelling Code (International Residential Code), revised January 1, 2002.

(Effective January 1, 2005)

*Revise Section 502.2.3.6 'Basement walls,' add superscript '1' to title and add exceptions and notes.

502.2.3.6 Basement walls1. The exterior walls of conditioned basements2 shall have a thermal transmittance value not exceeding the valve given in Table 502.2 from the top of the basement wall to a depth of 10 feet (3048 mm) below grade, or to the level of the basement floor, whichever is less. The U-factor of the wall shall be determined by selecting the U-factor for the wall section from Appendix A Table 502.2.3.6 or Appendix B Tables 502.2.3.1(1a) or 502.2.3.1(1b).

Exceptions:

1. For conditioned basements in Climate Zones 4B, 5A, 6B and 7A, insulate the Mass Wall with minimum R-5 insulation and the cavity in Stud Walls, Cripple Walls and Bands with minimum R-11 insulation. When using this Exception, include all openings and exclude any opaque area of the walls in the basement when calculating Percent of Openings.

2. For conditioned basements in Climate Zone 8, insulate the Mass Wall with minimum R-6 insulation and the cavity in Stud Walls, Cripple Walls and Bands with minimum R-11 insulation. When using this Exception, include all openings and exclude any opaque area of the walls in the basement when calculating Percent of Openings.

When using Exceptions 1 or 2, the basement is "Deemed to Comply" with the Georgia State Energy Code; if the rest of the dwelling complies by any method in Chapters 5 or 6 or by another approved compliance method, the whole dwelling is "Deemed to Comply."

Note 1: IECC defines a 'basement wall' as 'the opaque portion of a wall which encloses one side of a basement and having an average below-grade area greater than or equal to 50 percent of its total wall area, including openings.'

Note 2: 'Basement' is defined in the Georgia Amendments to the CABO One and Two Family Dwelling Code (International Residential Code), revised January 1, 2002.

(Effective January 1, 2005)

*Add new Table 502.2.3.6 'Conditioned Walls in Basements.'

See page 7.

(Effective January 1, 2005)

*Revise Section 502.2.4 'Compliance by prescriptive specification on an individual component basis.'

Section 502.2.4 Compliance by prescriptive specification on an individual component basis. For buildings with a window area less than or equal to 15 percent, 18 percent, 25 percent, or 30 percent (Type A-1 residential buildings) or 22 percent or 25 percent (Type A-2 residential buildings) of the gross exterior wall area, the thermal resistance of insulation applied to the opaque building envelope components shall be greater than or equal to the minimum R-values, and the thermal transmittance of all fenestration assemblies shall be less than or equal to the maximum U-factors shown in Tables 502.2.4(1), 502.2.4(2), 502.2.4(3), 502.2.4(4), 502.2.4(5), 502.2.4(6), or 502.2(7), as applicable. Sections 502.2.4.1 through 502.2.4.12 and 502.2.4.15 through 502.2.4.17 shall apply to the use of these tables.

Note: Percent refers to the Percent of Opening to be determined by dividing the total openings (including conditioned basement openings) by the Gross Wall Area. For these tables the Gross Wall Area is the normal projection of all exterior walls above grade enclosing conditioned space, including all windows and doors therein. When using these tables, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings. Percent of Openings = 100 x (Openings in Floors Above Grade + Openings in Basement) / (Gross Wall Area Above Grade + Openings in Basement).

(Effective January 1, 2005)

CHAPTER 9

REFERENCED STANDARDS

*Revise Chapter 9 'Reference Standards' to update NFRC Standard Reference Numbers.

(Effective January 1, 2005)

NFRC

National Fenestration Rating Council, Inc. Suite 120 1300 Spring Street Park

Silver Spring, MD 20910

Standard reference number

Title

Referenced in code section number

100-97, -01

Procedure for Determining Fenestration Product U-Factors

102.5.2, 601.3.2, 601.3.2.1

200-97, -01

Procedure for Determining Fenestration Product Solar Heat Gain Coefficients and Visible Transmittance at Normal Incidence

102.5.2, 601.3.2, 601.3.2.1

GA STATE SUPPLEMENTS AND AMENDMENTS

*Revise Table 502.2.1 of Appendix B of the Georgia Supplements and Amendments revised January 1, 2003 to add Note 1 and renumber notes.

See page 7.

(Effective January 1, 2005)

*Revise Table 502.2.3.1(1a) 'Wall R-values* 2 x 4 Wood Studs 16" OC (Insulation plus sheathing)' of Appendix B of the Georgia Supplements and Amendments revised January 1, 2003.

See page 8.

(Effective January 1, 2005)

*Delete Tables 502.2.4(1-9) and Tables 502.2.4(1-5) and 602.1 of the Georgia Supplements and Amendments revised January 1, 2003 and substitute with new Tables 502.2.4(1-7) and 602.1.

See pages 9-12.

(Effective January 1, 2005)

*Revise Table 701 'Minimum Thermal Component Requirements' of the Georgia Supplements and Amendments revised January 1, 2003.

See page 13.

(Effective January 1, 2005)

*Delete Single Step Residential Energy Code Compliance Tables of Appendix B of the Georgia Supplements and Amendments revised January 1, 2003 and substitute.

See pages 14-28.

(Effective January 1, 2005)

End of Amendments

TABLE 502.2.1

SUMMARY OF MINIMUM INSULATION VALUES

MAXIMUM U-FACTOR FOR ENVELOPE COMPONENTS

ELEMENT1

MODE

TYPE A-1 & A-2 RESIDENTIAL BUILDINGS

R-value

Walls Stud

Heating or cooling

R-11

Walls Masonry/CMU2

Heating or cooling

R-5

Attic Knee Walls3

Heating or cooling

R-19

Roof/ceiling

Heating or cooling

R-19

Floor over unheated spaces

Heating or cooling

R-11

Windows4

Heating or cooling

U-0.65 with max. SHGC 0.40

Note 1: Weather-stripped access doors (minimum U-0.35), weather-stripped hatches/scuttle hole covers (minimum R-19 insulation or U-0.05), or weather-stripped disappearing/pull-down stairs (minimum U-0.35) shall be deemed to meet the minimum insulation R-values of any Element.

Note 2: Any Mass wall above or below grade.

Note 3: Attic Knee wall for purpose of Georgia Energy Code is defined as any vertical or near vertical wall in the building envelope that has conditioned space on one side and attic space on the other side.

Exception: When the attic space formed by the Attic Knee Wall, the ceiling of the floor below and the sloped roof is not vented and the sloped roof is insulated (the insulated roof is the building envelope).

Note 4: Maximum window U-factor shall be 0.65 and maximum SHGC shall be 0.40. These window requirements were implemented on January 1, 2004.

TABLE 502.2.3.6

CONDITIONED WALLS IN BASEMENTS

REQUIRED INSULATION R-VALUE FOR COMBINATION BASEMENT MASS WALLS AND STUD WALLS

CLIMATE ZONE FROM FIGURE 302.1(11)

Mass Wall

Stud Wall

Bands

4B

R-5

R-11

R-11

5A

R-5

R-11

R-11

6B

R-5

R-11

R-11

7A

R-5

R-11

R-11

8

R-6

R-11

R-11

Note: Include all openings and exclude any opaque area of the walls in the basement when calculating Percent of Openings when using this Table.

TABLE 502.2.3.1(1A)

WALL R-VALUES 2 X 4 WOOD STUDS 16'' OC (INSULATION PLUS SHEATHING)

R-11

R-12

R-13

R-14

R-15

R-16

R-17

R-18

Attic Knee Wall

R-19

R-20

R-11 Batts & Plywood/OSB (R-10.91)

(U-0.0916)

R-11 Batts & Fiberboard

(R-11.68)

(U-0.0859)

R-11 Batts & R-2 Foam

(R-12.42)

(U-0.0805)

R-11 Batts & R-3 Foam

(R-13.50)

(U-0.0741)

R-11 Batts & R-4 Foam

(R-14.56)

(U-0.0686)

R-11 Batts & R-5 Foam

(R-15.62)

(U-0.0640)

R-11 Batts & R-6 Foam

(R-16.66)

(U-0.060)

R-11 Batts & R-7 Foam

(R-17.70)

(U-0.0565)

2x6 wall

R-19 Batts

(R-15.42)

(U-0.0648)

R-11 Batts & R-8 Foam

(R-18.73)

(U-0.0534)

R-11 Batts & R-9 Foam

(R-19.77)

(U-0.0506)

R-11 Batts & Gypsum 2 sides (Garage)

(R-10.61)

(U-0.0942)

R-11 Batts & Plywood/OSB Fiberboard

(R-12.36)

(U-0.0809)

R-13 Batts & Gypsum on Two Sides

(Garages)

(R-11.52)

(U-0.0868)

R-13 Batts & Fiberboard

(R-12.64)

(U-0.0791)

R-13 Batts & R-2 Foam

(R-13.42)

(U-0.0745)

R-13 Batts & R-3 Foam

(R-14.53)

(U-0.0688)

R-13 Batts & R-4 Foam

(R-15.63)

(U-0.0640)

R-13 Batts & R-5 Foam

(R-16.71)

(U-0.0598)

2x4 wall

R-19 Batts

(R-13.08)

(U-0.0764)

R-13 Batts & R-6 Foam

(R-17.79)

(U-0.0562)

R-13 Batts & R-7 Foam

(R-18.85) (U-0.0530)

R-11 Batts & Plywood/OSB Unfinished Basement wall

(R-10.41)

(U-0.0960)

R-13 Batts & Plywood/OSB

(R-11.83)

(U-0.0846)

R-13 Plywood/OSB Fiberboard (R-13.35)

(U-0.0749)

R-15 Batts & Plywood/OSB (R-12.66)

(U-0.0790)

R-15 Batts & Fiberboard

(R-13.51)

(U-0.0740)

R-15 Batts & R-2 Foam

(R-14.32)

(U-0.0698)

R-15 Batts & R-3 Foam

(R-15.48)

(U-0.0646)

2x4 wall

R-13 Batts & R-6 Foam

(R-17.68)

(U-0.0565)

R-15 Batts & R-4 Foam

(R-16.62)

(U-0.0602)

R-15 Batts & R-5 Foam

(R-17.73) (U-0.0564)

R-13 Batts & Plywood/OSB Unfinished Basement wall

(R-11.3)

(U-0.0884)

R-15 Batts & Gypsum on Two Sides

(Garages)

(R-12.32)

(U-0.0811)

R-13 Batts R-0.62 OSB

R-3 Foam

(R-15.22)

(U-0.0657)

R-13 Batts

R-0.62 OSB

R-4 Foam

(R-16.3)

(U-0.0613)

R-13

R-0.62 OSB

R-5 Foam

(R-17.38)

(U-0.0575)

2x4 wall

R-15 Batts & R-4 Foam

(R-16.50)

(U-0.0606)

R-19 Batts & Plywood/OSB

(R-15.84)

(U-0.0631)

R-19 Batts & Fiberboard

(R-16.65)

(U-0.0601)

2x6 wall

R-15 Batts & R-4 Foam

(R-17.94)

(U-0.0557)

R-19 Batts & OSB Unfinished Basement wall

(R-15.75)

(U-0.0635)

R-19 Batts & Gypsum on Two Sides

(Garages)

(R-15.53)

(U-0.0644)

Wall R-values shown in this chart are for the insulated (opaque) wall areas based on 25% framing factor (bands uninsulated); does not include any openings (windows and doors). Per FTC Regulation 16 CFR 460, the R-value of the insulation shall not be more than 10% below the R-value shown in a label, fact sheet, ad, or other promotional material for that insulation. R-values shown in labels, fact sheets, ads, or other promotional materials shall be rounded to the nearest tenth. However, R-values of 10 or more may be rounded to the nearest whole number. Therefore, an R-2 Foam shall be an aged/stabilized R-1.8 or higher, an R-3 Foam shall be an aged/stabilized R-2.7 or higher, an R-4 Foam shall be an aged/stabilized R-3.6 or higher and etc. For full details on LABELING AND ADVERTISING OF HOME INSULATION see: http://www.access.gpo.gov/nara/cfr/waisidx_03/16cfr460_03.html.

TABLE 502.2.4(1)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-1 RESIDENTIAL BUILDINGS

WINDOW AREA 15 PERCENT OF GROSS EXTERIOR WALL AREA

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value 2,3

Exterior Wall

R-value4

Floor

R-value

Basement Wall

R-value5

Slab perimeter

R-value6

Crawl space wall R-value

4B

0.65

0.4

R-30

R-11

R-11

R-5

R-0

R-5

5A

0.65

0.4

R-30

R-13

R-11

R-5

R-0

R-6

6B

0.65

0.4

R-30

R-13

R-19

R-5

R-0

R-7

7A-1

0.65

0.4

R-38

R-16

R-19

R-5

R-0

R-8

7A-2

0.60

0.4

R-38

R-13

R-19

R-5

R-0

R-8

8

0.60

0.4

R-38

R-16

R-19

R-6

R-0

R-10

8

0.55

0.4

R-38

R-13

R-19

R-6

R-0

R-10

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: Where ceiling is R-38 and up to 25% R-19 insulation, may use R-30 on 100% of ceiling area.

Note 4: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 6: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 502.2.4(2)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-1 RESIDENTIAL BUILDINGS

WINDOW AREA 18 PERCENT OF GROSS EXTERIOR WALL AREA

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value 2,3

Exterior Wall

R-value4

Floor

R-value

Basement Wall

R-value5

Slab perimeter

R-value6

Crawl space wall R-value

4B-1

0.60

0.4

R-30

R-11

R-11

R-5

R-0

R-5

4B-2

0.65

0.4

R-30

R-13

R-11

R-5

R-0

R-5

5A-1

0.60

0.4

R-30

R-13

R-13

R-5

R-0

R-6

5A-2

0.55

0.4

R-30

R-13

R-11

R-5

R-0

R-6

6B-1

0.60

0.4

R-30

R-15

R-19

R-5

R-0

R-7

6B-2

0.55

0.4

R-30

R-13

R-19

R-5

R-0

R-7

7A-1

0.55

0.4

R-38

R-16

R-19

R-5

R-0

R-8

7A-2

0.51

0.4

R-30

R-16

R-19

R-5

R-0

R-8

7A-3

0.50

0.4

R-38

R-13

R-19

R-5

R-0

R-8

8-1

0.50

0.4

R-38

R-16

R-19

R-6

R-0

R-10

8-2

0.47

0.4

R-30

R-16

R-19

R-6

R-0

R-10

8-3

0.45

0.4

R-38

R-13

R-19

R-6

R-0

R-10

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: Where ceiling is R-38 and up to 25% R-19 insulation, may use R-30 on 100% of ceiling area.

Note 4: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 6: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 502.2.4(3)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-1 RESIDENTIAL BUILDINGS

WINDOW AREA 18 PERCENT OF GROSS EXTERIOR WALL AREA

R-13 WALL WITH PLYWOOD/OSB SHEATHING AND R-30 CEILING

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value 2

Exterior Wall

R-value3

Floor

R-value

Basement Wall

R-value4

Slab perimeter

R-value5

Crawl space wall R-value

4B-13 Wall

0.65

0.4

R-30

R-13

R-11

R-5

R-0

R-5

5A-13 Wall

0.62

0.4

R-30

R-13

R-13

R-5

R-0

R-6

6B-13 Wall

0.58

0.4

R-30

R-13

R-19

R-5

R-0

R-7

7A-13 Wall

0.48

0.4

R-30

R-13

R-19

R-5

R-0

R-8

8-13 Wall

0.43

0.4

R-30

R-13

R-19

R-6

R-0

R-10

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 4: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 5: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 502.2.4(4)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-1 RESIDENTIAL BUILDINGS

WINDOW AREA 25 PERCENT OF GROSS EXTERIOR WALL AREA

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value 2,3

Exterior Wall

R-value4

Floor

R-value

Basement Wall

R-value5

Slab perimeter

R-value6

Crawl space wall R-value

4B-1

0.55

0.4

R-30

R-16

R-13

R-5

R-0

R-5

4B-2

0.50

0.4

R-30

R-13

R-13

R-5

R-0

R-5

4B-3

0.45

0.4

R-30

R-11

R-11

R-5

R-0

R-5

5A-1

0.49

0.4

R-30

R-16

R-13

R-5

R-0

R-6

5A-2

0.45

0.4

R-30

R-13

R-13

R-5

R-0

R-6

5A-3

0.40

0.4

R-30

R-11

R-11

R-5

R-0

R-7

6B-1

0.45

0.4

R-30

R-15

R-19

R-5

R-0

R-7

6B-2

0.43

0.4

R-30

R-13

R-19

R-5

R-0

R-7

6B-3

0.40

0.4

R-30

R-11

R-19

R-5

R-0

R-7

7A-1

0.39

0.4

R-30

R-16

R-19

R-5

R-0

R-8

7A-2

0.37

0.4

R-30

R-13

R-19

R-5

R-0

R-8

8-1

0.35

0.4

R-38

R-13

R-19

R-6

R-0

R-10

8-2

0.36

0.4

R-30

R-16

R-19

R-6

R-0

R-10

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: Where ceiling is R-38 and up to 25% R-19 insulation, may use R-30 on 100% of ceiling area.

Note 4: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 6: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 502.2.4(5)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-1 RESIDENTIAL BUILDINGS

WINDOW AREA 30 PERCENT OF GROSS EXTERIOR WALL AREA

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value 2,3

Exterior Wall

R-value4

Floor

R-value

Basement Wall

R-value5

Slab perimeter

R-value6

Crawl space wall R-value

4B-1

0.50

0.4

R-30

R-19

R-13

R-5

R-0

R-5

4B-2

0.45

0.4

R-30

R-13

R-13

R-5

R-0

R-5

5A-1

0.45

0.4

R-30

R-19

R-13

R-5

R-0

R-6

5A-2

0.40

0.4

R-30

R-13

R-13

R-5

R-0

R-6

6B-1

0.43

0.4

R-30

R-19

R-19

R-5

R-0

R-7

6B-2

0.40

0.4

R-38

R-16

R-19

R-5

R-0

R-7

6B-3

0.04

0.4

R-30

R-13

R-19

R-5

R-0

R-7

7A

0.35

0.4

R-38

R-16

R-19

R-5

R-0

R-8

8

0.34

0.4

R-387

R-16

R-19

R-6

R-0

R-10

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: Where ceiling is R-38 and up to 25% R-19 insulation, may use R-30 on 100% of ceiling area.

Note 4: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 6: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

Note 7: 100% of the ceiling shall be minimum R-38.

TABLE 502.2.4(6)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-2 RESIDENTIAL BUILDINGS

WINDOW AREA 22 PERCENT OF GROSS EXTERIOR WALL AREA

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value

Exterior Wall

R-value3

Floor

R-value

Basement Wall

R-value4

Slab perimeter

R-value5

Crawl space wall R-value

4B-5A

0.65

0.4

R-19

R-11

R-11

R-5

R-0

R-5

6B-8

0.65

0.4

R-302

R-13

R-19

R-5

R-0

R-7

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 4: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 5: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 502.2.4(7)

PRESCRIPTIVE BUILDING ENVELOPE REQUIREMENTS, TYPE A-2 RESIDENTIAL BUILDINGS

WINDOW AREA 25 PERCENT OF GROSS EXTERIOR WALL AREA

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value2

Exterior Wall

R-value3

Floor

R-value

Basement Wall

R-value4

Slab perimeter

R-value5

Crawl space wall R-value

4B

0.65

0.4

R-19

R-11

R-11

R-5

R-0

R-5

5A

0.65

0.4

R-19

R-13

R-11

R-5

R-0

R-6

6B

0.60

0.4

R-30

R-13

R-19

R-5

R-0

R-7

7A

0.58

0.4

R-30

R-13

R-19

R-5

R-0

R-8

8

0.58

0.4

R-30

R-13

R-19

R-5

R-0

R-10

Note 1: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 2: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 3: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 4: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 5: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 602.1

SIMPLIFIED PRESCRIPTIVE BUILDING ENVELOPE THERMAL COMPONENT CRITERIA

MINIMUM REQUIRED THERMAL PERFORMANCE (U-FACTOR AND R-VALUE)1

Maximum

Minimum

CLIMATE ZONE

[FIGURE 302.1(11)]

Glazing U-factor1

SHGC1

Ceiling

R-value3,4

Exterior Wall

R-value5

Floor

R-value

Basement Wall

R-value6

Slab perimeter

R-value7

Crawl space wall R-value

4B

0.65

0.4

R-30

R-13

R-11

R-5

R-0

R-5

5A

0.60

0.4

R-30

R-13

R-13

R-5

R-0

R-6

6B

0.55

0.4

R-30

R-13

R-19

R-5

R-0

R-7

7A-1

0.55

0.4

R-38

R-16

R-19

R-5

R-0

R-8

7A-2

0.50

0.4

R-38

R-13

R-19

R-5

R-0

R-8

8-1

0.50

0.4

R-38

R-16

R-19

R-6

R-0

R-10

8-1

0.45

0.4

R-38

R-13

R-19

R-6

R-0

R-10

Note 1: Maximum 18% fenestration area.

Note 2: Up to 5% of the fenestration may be exempt from meeting the window/door U-factor and Solar Heat Gain Coefficient (SHGC) requirements to allow for decorative glazing.

Note 3: Up to 25% of ceiling area may be R-19 for sloped ceilings & under HVAC.

Note 4: Where ceiling is R-38 and up to 25% R-19 insulation, may use R-30 on 100% of ceiling area.

Note 5: When the Exterior Wall R-value is cavity insulation and continuous insulated sheathing, 40% of the gross wall area may be plywood/OSB (for corner bracing/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 6: Insulate the Mass wall with listed R-value and Stud wall and Bands with Min R-11. When using this table, include openings in the basement and exclude the opaque wall area in the basement when calculating Percent of Openings.

Note 7: Foam plastic shall not be installed on the exterior of below grade foundation walls or below grade on slab foundations. See Paragraph 502.2.1.4.

TABLE 701

MINIMUM THERMAL COMPONENT REQUIREMENTS

Element

Type Nonresidential & Residential Conditioned

Minimum R-value of Insulation

Maximum U-factor SHGC

Roof

Metal Buildings1

R-19 with Thermal Block

0.065

Insulation Entirely above Deck except Metal Buildings

R-15

0.063

Attic and Other2

R-30

0.034

Walls above Grade

Metal Building

R-13

0.113

Cavity Walls3

R-13

N/A

Mass Walls4

Per ASHRAE 90.1

Glazed Fenestration

Any

N/A

U-0.65 / SHGC 0.60

Note 1: Metal buildings with purlins 5' on center and 1" x 3" thermal block.

Note 2: See appropriate ANSI/ASHRAE/IESN 90.1-2001 Tables B-5, B-6, B-8, B-9 or B-11 and Tables A-1, A-2, A-3 or A-4 for Attic and other Building Roof Minimum Thermal Requirements.

Note 3: Steel Framed or Wood Framed and Other Walls. See ANSI/ASHRAE/IESN 90.1-2001 Tables B-5, B-6, B-8, B-9 or B-11.

Note 4: Masonry, concrete, CMU, or other solid walls with a minimum weight of 30 pounds per square foot. See ANSI/ASHRAE/IESN 90.1-2001, Page 13, Definitions, Mass Wall.

"Single-Step" Residential Energy Code Compliance

Climate Zone 4B - South Georgia - Option 4B-2-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

1. Your building shall be a one or two family detached dwelling built using wood framing.

2. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

3. Your building site shall be located in Climate Zone 4B, as shown in the IECC 2000 Figure 302.1(11).

4. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

5. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

6. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

7. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.65

-Windows2

0.65

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-11

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors)/(opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 4B - South Georgia - Option 4B-3-2005-25%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

8. Your building shall be a one or two family detached dwelling built using wood framing.

9. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

10. Your building site shall be located in Climate Zone 4B, as shown in the IECC 2000 Figure 302.1(11).

11. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

12. Your window and door openings shall not exceed 25.0 percent of the gross wall area.

13. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

14. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

25.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.50

-Windows2

0.50

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-13

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 5A - South Central Georgia - Option 5A-2-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

15. Your building shall be a one or two family detached dwelling built using wood framing.

16. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

17. Your building site shall be located in Climate Zone 5A or 4B, as shown in the IECC 2000 Figure 302.1(11).

18. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

19. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

20. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

21. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.62

-Windows2

0.62

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-13

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 5A - South Central Georgia - Option 5A-3-2005-25%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

22. Your building shall be a one or two family detached dwelling built using wood framing.

23. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

24. Your building site shall be located in Climate Zone 5A or 4B, as shown in the IECC 2000 Figure 302.1(11).

25. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

26. Your window and door openings shall not exceed 25.0 percent of the gross wall area.

27. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

28. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

25.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.45

-Windows2

0.45

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insula tion3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-13

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 6B - Central Georgia - Option 6B-3-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

29. Your building shall be a one or two family detached dwelling built using wood framing.

30. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

31. Your building site shall be located in Climate Zone 6B, 5A or 4B, as shown in the IECC 2000 Figure 302.1(11).

32. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

33. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

34. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

35. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.55

-Windows2

0.55

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 6B - Central Georgia - Option 6B-4-2005-25%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

36. Your building shall be a one or two family detached dwelling built using wood framing.

37. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

38. Your building site shall be located in Climate Zone 4B, 5A or 4B, as shown in the IECC 2000 Figure 302.1(11).

39. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

40. Your window and door openings shall not exceed 25.0 percent of the gross wall area.

41. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

42. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

25.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.43

-Windows2Max. U-factor

0.43

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 7A - Greater Atlanta Area - Option 7A-4-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

43. Your building shall be a one or two family detached dwelling built using wood framing.

44 Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

45. Your building site shall be located in Climate Zone 7A, 6B, 5A or 4B as shown in the IECC 2000 Figure 302.1(11).

46. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

47. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

48. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

49. Equipment minimum efficiencies shall be observed: Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ____________

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.50

-Windows2

0.55

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-38

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

R-3

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area. Also complies if 100% of ceiling is R-30.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-16 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 7A - Greater Atlanta Area - Option 7A-7-2005-25%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

50. Your building shall be a one or two family detached dwelling built using wood framing.

51. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

52. Your building site shall be located in Climate Zone 7A, 6B, 5A, or 4B as shown in the IECC 2000 Figure 302.1(11).

53. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

54. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

55. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

56. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.50

-Windows2

0.51

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

R-3

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-16 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 7A - Greater Atlanta Area - Option 7A-8-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

57. Your building shall be a one or two family detached dwelling built using wood framing.

58. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

59. Your building site shall be located in Climate Zone 7A, 6B, 5A, or 4B as shown in the IECC 2000 Figure 302.1(11).

60. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

61. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

62. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

63. Equipment minimum efficiencies shall be observed: Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.50

-Windows2

0.50

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-38

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing4

OSB/Plywood/FibBd

-Floor Insulation (over unconditioned space

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 7A - Greater Atlanta Area - Option 7A-7-2005-25%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

64. Your building shall be a one or two family detached dwelling built using wood framing.

65. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

66. Your building site shall be located in Climate Zone 7A, 6B, 5A, or 4B as shown in the IECC 2000 Figure 302.1(11).

67. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

68. Your window and door openings shall not exceed 25.0 percent of the gross wall area.

69. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

70. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) _____________

-% Openings in gross area of exterior wall1

25.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.40

-Windows2

0.37 Max.

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Attic Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood/FibBd

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area. May also insulate 100% with R-30.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. Up to 40% of the gross wall area can be gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 7A - Greater Atlanta Area - Option 7A-OSB-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

71. Your building shall be a one or two family detached dwelling built using wood framing.

72. Your building is three stories or less in height and above grade conditioned floor area is not larger than 5,000 sq. ft.

73. Your building site shall be located in Climate Zone 7A, 6B, 5A, or 4B as shown in the IECC 2000 Figure 302.1(11).

74. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

75. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

76. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

77. Equipment minimum efficiencies shall be observed:

78. Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.55

-Windows2

0.55

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-38

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

R-3

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulatio n5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-16 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 7A - Metro Atlanta - Option 7A-OSB-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

79. Your building shall be a one or two family detached dwelling built using wood framing.

80. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

81. Your building site shall be located in Climate Zone 7A, 6B,5A or 4B as shown in the IECC 2000 Figure 302.1(11).

82. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

83. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

84. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

85. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.48

-Windows2

0.48

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-5

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 8 - North Georgia - Option 8-3-2005-25%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

86. Your building shall be a one or two family detached dwelling built using wood framing.

87. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

88. Your building site may be located in any Climate Zone, as shown in the IECC 2000 Figure 302.1(11).

89. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

90. Your window and door openings shall not exceed 25.0 percent of the gross wall area.

91. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

92. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

25.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.35

-Windows2

0.35

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-38

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-6

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area. Also complies if 100% of ceiling is R-30.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 8 - North Georgia - Option 8-4-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

93. Your building shall be a one or two family detached dwelling built using wood framing.

94. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

95. Your building site may be located in any Climate Zone, as shown in the IECC 2000 Figure 302.1(11).

96. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

97. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

98. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

99. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.47

-Windows2

0.47

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

R- 3

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-6

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-16 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

"Single-Step" Residential Energy Code Compliance

Climate Zone 8 - North Georgia - Option 8-OSB-2005-18%

You are "deemed to comply" with the Georgia State Energy Code for Buildings if your residential structure meets the following conditions:

100. Your building shall be a one or two family detached dwelling built using wood framing.

101. Your building is three stories or less in height and the above grade conditioned floor area is not larger than 5,000 sq. ft.

102. Your building site may be located in any Climate Zone, as shown in the IECC 2000 Figure 302.1(11).

103. You shall not make any substitutions of any kind for R-values/U-factors listed below in conditioned space.

104. Your window and door openings shall not exceed 18.0 percent of the gross wall area.

105. You shall comply with code requirements for envelope air sealing including all air tight, I. C. rated light fixtures in ceilings with attics and seal all ductwork with mastic.

106. Equipment minimum efficiencies shall be observed:

Gas furnace: AFUE min 78%; A/C or Heat pump: SEER 10.0; Heat pump: HSPF 6.8; other (explain) ______

-% Openings in gross area of exterior wall1

18.0% Max.

-Solid Doors Max. U-factor2

0.35

-Glazed Doors Max. U-factor2

0.43

-Windows2

0.43

-Solar Heat Gain Coefficient (SHGC)

0.40 Max.

-Ceiling insulation3

R-30

-Wall cavity insulation4

R-13

-Knee Wall cavity insulation

R-19

-Wall Sheathing 4

OSB/Plywood

-Floor Insulation (over unconditioned space)

R-19

-Basement Mass Wall insulation Min.

R-6

-Basement Stud Wall & Bands cavity insulation5

R-11

-Slab Perimeter Insulation 6

R-0

All R-values shall be printed on the actual insulation and be stabilized (aged) R-values.

All Windows shall have labels listing U-factor, SHGC, and Key Features.

Foam Plastics shall not be installed below grade on exterior side of foundation walls or below grade on slab foundations. These R-values may result in some degree of "over-design". However, this method will apply to a majority of one and two family residences built in Georgia. If you must change one or more of the R-values/U-factors listed to a lower R-value or higher U-factor, then do not use this method. No substitutions are allowed here.

Instead, you may use one of the other methods to show compliance, such as The Trade-off Worksheet or the free REScheck software (available at www.energycodes.gov). You may also use one of the Chapter 4, 5, or 6 approaches of the 2000 IECC with Georgia modifications.

At the time a permit is requested, you shall show how you plan to meet the Georgia Energy Code. When using the "Single-Step" Residential Energy Code Compliance method, you may not be required to turn in additional paperwork to obtain a building permit, except calculation on Percent of Openings (Take-off Worksheet may be used to calculate % Openings).

________________________________________________________________________

Note 1: "% Openings" is defined by the total area of the openings of windows and doors divided by the total gross area of the exterior wall. % Openings = 100 x (windows + doors) / (opaque walls + windows + doors - basement opaque walls).

Note 2: One Door or up to 5% of the opening area (whichever is greater area) may be exempt from meeting the window/door U-factor and SHGC requirements to allow for decorative glazing.

Note 3: Sloped ceilings, such as cathedral & tray ceilings, which require batt insulation, and space under HVAC equipment may be insulated with R-19 batts, provided the R-19 portion does not exceed 25% of the total ceiling area.

Note 4: Any combination of Cavity Insulation + Sheathing R-value that = R-13 or greater is permitted. 40% of the gross wall area and all basement walls, may be Plywood/OSB (for corner/structural requirements) or gypsum fastened direct to the garage wall studs.

Note 5: Unfinished conditioned basements require unfaced insulation, Class 1 facer (0-25 Flame Spread) or other approved insulation.

Note 6: Unheated slabs.

Click here to view

GEORGIA STATE MINIMUM

STANDARD GAS CODE

(INTERNATIONAL FUEL GAS CODE)

The STANDARD GAS CODE (International Fuel Gas Code), 2000 Edition, published by the Southern Building Code Congress International, Inc. (International Code Council), when used in conjunction with these Georgia Amendments and the Georgia Amendments adopted effective January 1 of 2001, 2002 and 2003, shall constitute the official Georgia State Minimum Standard Gas Code.

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Replace all references to the ICC Electrical Code with references to the Georgia State Minimum Standard Electrical Code (National Electrical Code).

(b) Replace all references to the International Energy Conservation Code (IECC) with references to the Georgia State Energy Code for Buildings. The Georgia State Energy Code for Buildings shall be used for efficiency and coefficient of performance ratings of equipment.

SCOPE:

The provisions of the Georgia State Minimum Standard Gas Code (International Fuel Gas Code) shall apply to the installation of fuel gas piping systems, fuel gas utilization equipment and related accessories as follows:

1. Coverage of piping systems shall extend from the point of delivery to the connections with gas utilization equipment (See definition of 'Point of Delivery').

2. a. Systems with an operating pressure of 125 psig (862 kPa gauge) or less.

b. Piping systems for gas-air mixtures within the flammable range with an operating pressure of 10 psig (69 kPa gauge).

c. LP-Gas piping systems with an operating pressure of 20 psig (140 kPa gauge) or less.

3. Piping systems requirements shall include design, materials, components, fabrication, assembly, installation, testing, inspection, operation and maintenance.

4. Requirements for gas utilization equipment and related accessories shall include installation, combustion, ventilation air and venting.

The provisions of the Georgia State Minimum Standard Gas Code (International Fuel Gas Code) shall not apply to the following:

1. Portable LP-Gas equipment of all types that are not connected to a fixed fuel piping system.

2. Installation of farm equipment such as brooders, dehydrators, dryers and irrigation equipment.

3. Raw material (feedstock) applications except for piping to special atmosphere generators.

4. Oxygen-fuel gas cutting and welding systems.

5. Industrial gas applications using gases such as acetylene and acetylene compounds, hydrogen, ammonia, carbon monoxide, oxygen and nitrogen.

6. Petroleum refineries, pipeline compressor or pumping stations, loading terminals, compounding plants, refinery tank farms and natural gas processing plants.

7. Integrated chemical plants or portions of such plants where flammable or combustible liquids or gases are produced by chemical reactions or used in chemical reactions.

8. LP-Gas installations at utility gas plants.

9. Liquefied Natural Gas (LNG) installations.

10. Fuel gas piping in power and atomic energy plants.

11. Proprietary items of equipment, apparatus or instruments such as gas generating sets, compressors and calorimeters.

12. LP-Gas equipment for vaporization, gas mixing and gas manufacturing.

13. Temporary LP-Gas piping for buildings under construction or renovation that is not to become part of the permanent piping system.

14. Installation of LP-Gas systems for railroad switch heating.

15. Installation of LP-Gas and Compressed Natural Gas (CNG) systems on vehicles.

16. Except as provided in Section 401.1.1, gas piping meters, gas pressure regulators and other appurtenances used by the serving gas supplier in the distribution of gas, other than undiluted LP-gas.

17. Building design and construction, except as specified herein.

The requirements for the design, installation, maintenance, alteration and inspection of mechanical systems operating with fuels other than fuel gas shall be regulated by the Georgia State Minimum Standard Mechanical Code (International Mechanical Code).

The State's minimum requirements for natural gas systems shall be established by NFPA 54 (National Fuel Gas Code). For areas not specifically addressed by NFPA 54 (National Fuel Gas Code)which are addressed by the Georgia State Minimum Standard Gas Code (International Fuel Gas Code), the Georgia State Minimum Standard Gas Code (International Fuel Gas Code) shall be used as a supplement.

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

GEORGIA STATE MINIMUM

REQUIREMENTS FOR BOILERS/WATER HEATERs aND PRESSURE VESSELS

(a) The State's minimum requirements for boilers/water heaters and pressure vessels over 200,000 BTU (58.56 kW), 210 degrees Fahrenheit or 120 gallons capacity shall be established by O.C.G.A. Title 34, Chapter 11 and the Rules and Regulations of the Georgia Department of Labor.

CHAPTER 3

GENERAL REGULATIONS

SECTION 305 (IFGC)

INSTALLATION

*Delete existing Exception #1 of Section 305.2 'Elevation of ignition source' of the Georgia Amendments revised January 1, 2001 and substitute.

305.2 Elevation of ignition source.

Exception #1:

Elevation of the ignition source is not required for appliances that are listed and labeled as flammable vapor resistant and for installation without elevation.

(Effective January 1, 2005)

*Add new Section 310 'Bonding' with Sub-Section 310.1 'Gas pipe bonding.'

SECTION 310

BONDING

310.1 Gas pipe bonding.

Each above-ground portion of a gas piping system that is likely to become energized shall be electrically continuous and bonded to an effective ground-fault current path. Gas piping shall be considered to be bonded where it is connected to gas utilization equipment that is connected to the equipment grounding conductor or the circuit supplying that equipment.

(Effective January 1, 2005)

End of Amendments

Click here to view

GEORGIA STATE MINIMUM

STANDARD ONE AND TWO FAMILY DWELLING CODE

(INTERNATIONAL RESIDENTIAL CODE For ONE- AND TWO- FAMILY DWELLINGS)

The CABO ONE AND TWO FAMILY DWELLING CODE (International Residential Code for One- and Two-Family Dwellings), 2000 Edition, published by the Southern Building Code Congress International, Inc. (International Code Council), when used in conjunction with these Georgia Amendments and the Georgia Amendments adopted effective January 1 of 2002, 2003 and 2004, shall constitute the official Georgia State Minimum Standard One and Two Family Dwelling Code.

Plumbing (Chapters 25 through 32) is deleted from the CABO ONE AND TWO FAMILY DWELLING CODE (International Residential Code for One- and Two-Family Dwellings) according to Title 8, Chapter 2, Article 1, Part 2 of the Official Code of Georgia, Annotated (O.C.G.A.). Substitute for plumbing requirements the Georgia State Minimum Standard Plumbing Code (International Plumbing Code).

Electrical (Chapters 33 through 42) is deleted from the CABO ONE AND TWO FAMILY DWELLING CODE (International Residential Code for One- and Two-Family Dwellings). Substitute for electrical requirements the Georgia State Minimum Standard Electrical Code (National Electrical Code).

GEORGIA STATE AMENDMENTS

CODE REFERENCE:

(a) Replace all references to the ICC Electrical Code with references to the Georgia State Minimum Standard Electrical Code (National Electrical Code).

(b) Replace all references to the International Energy Conservation Code (IECC) with references to the Georgia State Energy Code for Buildings. The Georgia State Energy Code for Buildings shall be used for heating and air conditioning equipment.

SCOPE:

The provisions of the GeorgiaState Minimum Standard One and Two Family Dwelling Code(International Residential Code for One- and Two-Family Dwellings) shall apply to the construction, alteration, movement, enlargement, replacement, repair, equipment, use and occupancy, location, maintenance, removal and demolition of detached one- and two-family dwellings and multiple single-family dwellings (townhouses) not more than three stories in height with separate means of egress and their accessory structures.

APPENDICES:

Appendices are not enforceable unless they are specifically referenced in the body of the code or adopted by the Department of Community Affairs or the authority having jurisdiction.

GEORGIA STATE MINIMUM

REQUIREMENTS FOR BOILERS/WATER HEATERS AND PRESSURE VESSELS

(a) The State's minimum requirements for boilers/water heaters and pressure vessels over 200,000 BTU (58.56 kW), 210 degrees Fahrenheit or 120 gallons capacity shall be established by O.C.G.A. Title 34, Chapter 11 and the Rules and Regulations of the Georgia Department of Labor.

CHAPTER 3

BUILDING PLANNING

SECTION R309

GARAGES AND CARPORTS

*Revise Section R309.2 'Separation required' to add exception.

R309.2 Separation required.

Exception #2:

A disappearing/pull-down stairway with minimum 3/8-inch (9.53 mm) (nominal) fire-retardant-treated structural panel is deemed to meet the 20-minute thermal barrier test based on ASTM E 119, Standard Test Method for Fire Tests of Building Construction and Materials, or deemed to have the fire resistance of or equivalent to 1/2-inch (12.7 mm) gypsum wall board.

(Effective January 1, 2005)

SECTION R323

PROTECTION AGAINST DECAY

*Revise Section R323.3 'Fasteners.'

R323.3 Fasteners. Fasteners for naturally durable and preservative-treated wood shall be resistant to corrosion or be protected to resist corrosion. Where sacrificial coatings are applied to fasteners, a minimum coating thickness capable of protecting the fastener for the expected service life of the structure shall be provided. Fasteners for pressure preservative and fire-retardant-treated wood shall be of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper. The coating weights for zinc-coated fasteners shall be in accordance with ASTM A 153M or ASTM A 641M, Supplemental Requirements. Fastenings for permanent wood foundations shall be as required in AF&PA Technical Report No. 7.

(Effective January 1, 2005)

CHAPTER 4

FOUNDATIONS

SECTION R404

FOUNDATION WALLS

*Revise Section R404.2.6 'Fastening.'

R404.2.6 Fastening. Wood structural panel foundation wall sheathing shall be attached to framing in accordance with Table R602.3(1) and Sections R402.1.1 and R323.3.

(Effective January 1, 2005)

*Revise Section R404.3 'Wood sill plates.'

R404.3 Wood sill plates. Wood sill plates shall be a minimum of 2-inch by 4-inch (51 mm by 102 mm) nominal lumber. Sill plate anchorage shall be in accordance with Sections R403.1.6, R602.11 and R323.3.

(Effective January 1, 2005)

CHAPTER 6

WALL CONSTRUCTION

SECTION R602

WOOD WALL FRAMING

*Revise Footnote a of Table R602.3(1) 'Fastener Schedule For Structural Members.'

R602.3(1) Fastener Schedule For Structural Members.

Footnote a:

All nails are smooth-common, box or deformed shanks except where otherwise stated or as required to be hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze or copper in accordance with Section R323.3. Nails used for framing and sheathing connections shall have minimum average bending yield strengths as shown: 80 ksi (551 MPa) for shank diameter of 0.192 inch (20d common nail), 90 ksi (620 MPa) for shank diameters larger than 0.142 inch but not larger than 0.177 inch, and 100 ksi (689 MPa) for shank diameters of 0.142 inch or less.

(Effective January 1, 2005)

*Revise Section R602.10.5 'Continuous structural panel sheathing' to add exception.

R602.10.5 Continuous structural panel sheathing.

Exception:

Vertical wall segments, in the first story of one- or two-story buildings, next to garage openings shall be permitted to have a 6:1 height-to-width ratio (with height being measured from top of header to sill plate) when constructed in accordance with the following provisions. Each panel shall have a length of not less than 15 inches (381 mm) and a height of not more than 10 feet (3048 mm). Each panel shall be sheathed on one face with a single layer of 3/8-inch (9.53 mm) minimum thickness wood structural panel sheathing nailed with 8d common or galvanized box nails in accordance with Figure R602.10.5. The wood structural panel sheathing shall extend up over the solid sawn or glued laminated header and shall be nailed in accordance with Figure R602.10.5. The header shall extend between the inside faces of the first full-length outer studs of each panel. The clear span of the header between the inner studs of each panel shall be not less than six feet (1829 mm) and not more than 18 feet (5486 mm) in length. A strap with an uplift capacity of not less than 1000 pounds (454 kg) shall fasten the header to the side of the inner studs opposite the sheathing. Two anchor bolts shall be installed in accordance with Section R403.1.6, and plate washers shall be a minimum of 2 inches by 2 inches by 3/16 inches (51 mm by 51 mm by 4.77 mm) thick and shall be used on each bolt. This exception is only permitted in Seismic Design Categories A-C.

(Effective January 1, 2005)

End of Amendments

Ga. Comp. R. & Regs. R. 110-11-1-.14

O.C.G.A. Sec. 8-2-20et seq.

Original Rule entitled "Adoption of the 2003 International Fire Code With Georgia Amendments, Georgia Amendments to the 2000 CABO One and Two Family Dwelling Code, 2000 Standard Building Code, 2000 Standard Plumbing Code, 2000 Standard Mechanical Code, 2000 Standard Gas Code, and the 2000 International Energy Conservation Code, effective Jan. 1, 2005" adopted. F. Nov. 23, 2004; eff. January 1, 2005, as specified by the Agency.