TABLE 2306.2.1(1) ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL DIAPHRAGMS WITH FRAMING OF DOUGLAS FIR-LARCH, OR SOUTHERN PINEa FOR WIND OR SEISMIC LOADINGh
PANEL GRADE | COMMON NAIL SIZE OR STAPLEf LENGTH AND GAGE | MINIMUM FASTENER PENETRATION IN FRAMING (inches) | MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM NOMINAL WIDTH OF FRAMING MEMBERS AT ADJOINING PANEL EDGES AND BOUNDARIESg (inches) | BLOCKED DIAPHRAGMS | UNBLOCKED DIAPHRAGMS | ||||
Fastener spacing (inches) at diaphragm boundaries (all cases) at continuous panel edges parallel to load (Cases 3, 4), and at all panel edges (Cases 5, 6)b | Fasteners spaced 6 max. at supported edgesb | |||||||||
6 | 4 | 2 1/2c | 2c | Case 1(No unblocked edges or continuous joints parallel to load) | All other configurations(Cases 2, 3, 4, 5 and 6) | |||||
Fastener spacing (inches) at other panel edges (Cases 1, 2, 3 and 4)b | ||||||||||
6 | 6 | 4 | 3 | |||||||
Structural I grades | 8d (2 1/2" x 0.131") | 1 3/8 | 3/8 | 2 | 270 | 360 | 530 | 600 | 240 | 180 |
3 | 300 | 400 | 600 | 675 | 265 | 200 | ||||
11/2 16 Gage | 1 | 2 | 175 | 235 | 350 | 400 | 155 | 115 | ||
3 | 200 | 265 | 395 | 450 | 175 | 130 | ||||
10dd (3" x 0.148") | 1 1/2 | 15/32 | 2 | 320 | 425 | 640 | 730 | 285 | 215 | |
3 | 360 | 480 | 720 | 820 | 320 | 240 | ||||
11/2 16 Gage | 1 | 2 | 175 | 235 | 350 | 400 | 155 | 120 | ||
3 | 200 | 265 | 395 | 450 | 175 | 130 | ||||
Sheathing, single floor and other grades covered in DOC PS 1 and PS 2 | 6de (2" x 0.113") | 11/4 | 3/8 | 2 | 185 | 250 | 375 | 420 | 165 | 125 |
8d (21/2" x 0.131") | 13/8 | 3 | 210 | 280 | 420 | 475 | 185 | 140 | ||
2 | 240 | 320 | 480 | 545 | 215 | 160 | ||||
3 | 270 | 360 | 540 | 610 | 240 | 180 | ||||
11/2 16 Gage | 1 | 2 | 160 | 210 | 315 | 360 | 140 | 105 | ||
3 | 180 | 235 | 355 | 400 | 160 | 120 | ||||
8d (2 1/2" x 0.131") | 1 3/8 | 7/16 | 2 | 255 | 340 | 505 | 575 | 230 | 170 | |
3 | 285 | 380 | 570 | 645 | 255 | 190 | ||||
11/2 16 Gage | 1 | 2 | 165 | 225 | 335 | 380 | 150 | 110 | ||
3 | 190 | 250 | 375 | 425 | 165 | 125 | ||||
8d (2 1/2" x 0.131") | 1 3/8 | 15/32 | 2 | 270 | 360 | 530 | 600 | 240 | 180 | |
3 | 300 | 400 | 600 | 675 | 265 | 200 | ||||
10dd (3" x 0.148") | 11/2 | 2 | 290 | 385 | 575 | 655 | 255 | 190 | ||
3 | 325 | 430 | 650 | 735 | 290 | 215 | ||||
11/2 16 Gage | 1 | 2 | 160 | 210 | 315 | 360 | 140 | 105 | ||
3 | 180 | 235 | 355 | 405 | 160 | 120 | ||||
10dd (3" x 0.148") | 11/2 | 19/32 | 2 | 320 | 425 | 640 | 730 | 285 | 215 | |
3 | 360 | 480 | 720 | 820 | 320 | 240 | ||||
13/4 16 Gage | 1 | 2 | 175 | 235 | 350 | 400 | 155 | 115 | ||
3 | 200 | 265 | 395 | 450 | 175 | 130 |
TABLE 2306.2.1(1)-continued-ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL DIAPHRAGMS WITH FRAMING OF DOUGLAS FIR-LARCH, OR SOUTHERN PINEa FOR WIND OR SEISMIC LOADINGh
Click to view image |
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. a. For framing of other species: (1) Find specific gravity for species of lumber in AF & PA NDS. (2) For staples find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails find shear value from table above for nail size for actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [1-(0.5 - SG)], where SG = Specific Gravity of the framing lumber. This adjustment factor shall not be greater than 1. b. Space fasteners maximum 12 inches o.c. along intermediate framing members (6 inches o.c. where supports are spaced 48 inches o.c.). c. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where panel edge nailing is specified at 21/2 inches o.c. or less. d. Framing at adjoining panel edges shall be 3 inches nominal or wider, and nails at all panel edges shall be staggered where both of the following conditions are met: (1) 10d nails having penetration into framing of more than 11/2 inches and (2) panel edge nailing is specified at 3 inches o.c. or less. e. 8d is recommended minimum for roofs due to negative pressures of high winds. f. Staples shall have a minimum crown width of 7/16 inch and shall be installed with their crowns parallel to the long dimension of the framing members. g. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches. h. For shear loads of normal or permanent load duration as defined by the AF & PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively. |
TABLE 2306.2.1(2) ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL BLOCKED DIAPHRAGMS UTILIZING MULTIPLE ROWS OF FASTENERS (HIGH LOAD DIAPHRAGMS) WITH FRAMING OF DOUGLAS FIR-LARCH OR SOUTHERN PINEa FOR WIND OR SEISMIC LOADINGb, g, h
PANEL GRADEc | COMMON NAIL SIZE OR STAPLEf GAGE | MINIMUM FASTENER PENETRATION IN FRAMING (inches) | MINIMUM NOMINAL PANEL THICKNESS (inch) | MINIMUM NOMINAL WIDTH OF FRAMING MEMBER AT ADJOINING PANEL EDGES AND BOUNDARIESe | LINES OF FASTENERS | BLOCKED DIAPHRAGMS | |||||||
Cases 1 and 2d | |||||||||||||
Fastener Spacing Per Line at Boundaries(inches) | |||||||||||||
4 | 21/2 | 2 | |||||||||||
Fastener Spacing Per Line at Other Panel Edges (inches) | |||||||||||||
6 | 4 | 4 | 3 | 3 | 2 | ||||||||
Structural I grades | 10d common nails | 11/2 | 15/32 | 3 4 4 | 2 2 3 | 605 700 875 | 815 915 1,220 | 875 1,005 1,285 | 1,150 1,290 1,395 | - - - | - - - | ||
19/32 | 3 4 4 | 2 2 3 | 670 780 965 | 880 990 1,320 | 965 1,110 1,405 | 1,255 1,440 1,790 | - - - | - - - | |||||
23/32 | 3 4 4 | 2 2 3 | 730 855 1,050 | 955 1,070 1,430 | 1,050 1,210 1,525 | 1,365 1,565 1,800 | - - - | - - - | |||||
14 gage staples | 2 | 15/32 | 3 4 | 2 3 | 600 860 | 600 900 | 860 1,160 | 960 1,295 | 1,060 1,295 | 1,200 1,400 | |||
19/32 | 3 4 | 2 3 | 600 875 | 600 900 | 875 1,175 | 960 1,440 | 1,075 1,475 | 1,200 1,795 | |||||
Sheathing single floor and other grades covered in DOC PS 1 and PS 2 | 10d common nails | 11/2 | 15/32 | 3 4 4 | 2 2 3 | 525 605 765 | 725 815 1,085 | 765 875 1,130 | 1,010 1,105 1,195 | - - - | - - - | ||
19/32 | 3 4 4 | 2 2 3 | 650 755 935 | 860 965 1,290 | 935 1,080 1,365 | 1,225 1,370 1,485 | - - - | - - - | |||||
23/32 | 3 4 4 | 2 2 3 | 710 825 1,020 | 935 1,050 1,400 | 1,020 1,175 1,480 | 1,335 1,445 1,565 | - - - | - - - | |||||
14 gage staples | 2 | 15/32 | 3 4 | 2 3 | 540 735 | 540 810 | 735 1,005 | 865 1,105 | 915 1,105 | 1,080 1,195 | |||
19/32 | 3 4 | 2 3 | 600 865 | 600 900 | 865 1,130 | 960 1,430 | 1,065 1,370 | 1,200 1,485 | |||||
23/32 | 4 | 3 | 865 | 900 | 1,130 | 1,490 | 1,430 | 1,545 |
For SI: 1 inch = 25.4 mm, 1 pound per foot = 14.5939 N/m. a. For framing of other species: (1) Find specific gravity for species of framing lumber in AF & PA NDS. (2) For staples, find shear value from table above for Structural I panels (regardless of actual grade) and multiply value by 0.82 for species with specific gravity of 0.42 or greater, or 0.65 for all other species. (3) For nails, find shear value from table above for nail size of actual grade and multiply value by the following adjustment factor: Specific Gravity Adjustment Factor = [ 1- (0.5 - SG)], where SG = Specific gravity of the framing lumber. This adjustment factor shall not be greater than 1. b. Fastening along intermediate framing members: Space fasteners a maximum of 12 inches on center, except 6 inches on center for spans greater than 32 inches. c. Panels conforming to PS 1 or PS 2. d. This table gives shear values for Cases 1 and 2 as shown in Table 2306.2.1(1). The values shown are applicable to Cases 3, 4, 5 and 6 as shown in Table 2306.2.1(1), providing fasteners at all continuous panel edges are spaced in accordance with the boundary fastener spacing. e. The minimum nominal depth of framing members shall be 3 inches nominal. The minimum nominal width of framing members not located at boundaries or adjoining panel edges shall be 2 inches. f. Staples shall have a minimum crown width of 7/16 inch, and shall be installed with their crowns parallel to the long dimension of the framing members. g. High load diaphragms shall be subject to special inspection in accordance with Section 1704.6.1. h. For shear loads of normal or permanent load duration as defined by the AF & PA NDS, the values in the table above shall be multiplied by 0.63 or 0.56, respectively. |
TABLE 2306.2.1(2)-continued-ALLOWABLE SHEAR (POUNDS PER FOOT) FOR WOOD STRUCTURAL PANEL BLOCKED DIAPHRAGMS UTILIZING MULTIPLE ROWS OF FASTENERS (HIGH LOAD DIAPHRAGMS) WITH FRAMING OF DOUGLAS FIR-LARCH OR SOUTHERN PINE FOR WIND OR SEISMIC LOADING
Click to view image |
780 CMR, 2306.2