CAS No. | Contaminant | MCL (mg/l) | |
(a) | 15972-60-8 | Alachlor | 0.002 |
(b) | Reserved | ||
(c) | Reserved | ||
(d) | Reserved | ||
(e) | 1912-24-9 | Atrazine | 0.003 |
(f) | 1563-66-2 | Carbofuran | 0.04 |
(g) | 57-74-9 | Chlordane | 0.002 |
(h) | 96-12-8 | Dibromochloropropane | 0.0002 |
(i) | 94-75-7 | 2,4-D | 0.07 |
(j) | 72-20-80 | Endrin | 0.002 |
(k) | 106-93-4 | Ethylene dibromide | 0.00002 |
(l) | 76-44-8 | Heptachlor | 0.0004 |
(m) | 1024-57-3 | Heptachlor epoxide | 0.0002 |
(n) | 58-89-9 | Lindane | 0.0002 |
(o) | 72-43-5 | Methoxychlor | 0.04 |
(p) | 1336-36-3 | Polychlorinated biphenyls | 0.0005 |
(q) | 87-86-5 | Pentachlorophenol | 0.001 |
(r) | 8001-35-2 | Toxaphene | 0.003 |
(s) | 93-72-1 | 2,4,5-TP | 0.05 |
(t) | 50-32-8 | Benzo(a)pyrene | 0.0002 |
(u) | 75-99-0 | Dalapon | 0.2 |
(v) | 103-23-1 | Di(2-ethylhexyl) adipate | 0.4 |
(w) | 117-81-7 | Di(2-ethylhexyl) phthalate | 0.006 |
(x) | 88-85-7 | Dinoseb | 0.007 |
(y) | 85-00-7 | Diquat | 0.02 |
(z) | 145-73-3 | Endothall | 0.1 |
(aa) | 1071-53-6 | Glyphosate | 0.7 |
(bb) | 118-74-1 | Hexachlorobenzene | 0.001 |
(cc) | 77-47-4 | Hexachlorocyclopentadiene | 0.05 |
(dd) | 23135-22-0 | Oxamyl (Vydate) | 0.2 |
(ee) | 1918-02-1 | Picloram | 0.5 |
(ff) | 122-34-9 | Simazine | 0.004 |
(gg) | 1746-01-6 | 2,3,7,8-TCDD(Dioxin) | 3x10-8 |
Basis of an SOC Sampling Waiver. The Department may grant a waiver after evaluating the following factor(s): Knowledge of previous use (including transport, storage, or disposal) of the contaminant within the watershed or zone of influence of the system. If a determination by the Department reveals no previous use of the contaminant within the watershed or Zone II or IWPA, a waiver may be granted. If previous use of the contaminant is unknown or it has been used previously, then the following factors shall be used to determine whether a waiver is granted.
Contaminant | EPA Method | SM | ASTM | Other |
2,3,7,8-TCDD(dioxin) | 1613 | |||
2,4-D3 (as acid, salts and esters) | 515.2, 555, 515.1, 515.3, 515.4 | D5317-93,98 (Reapproved 2003). | ||
2,4,5-TP3 (Silvex) | 515.2, 555, 515.1, 515.3, 515.4 | D5317-93, 98 (Reapproved 2003). | ||
Alachor1 | 505, 507, 525.2, 508.1, 551.1 | |||
Atrazine1 | 505, 507, 525.2, 508.1, 551.1 | Syngenta AG-6254 | ||
Benzo(a)pyrene | 525.2, 550, 550.1 | |||
Carbofuran | 531.1, 531.2 | 6610 | ||
Chlordane | 505, 508, 525.2, 508.1 | |||
Dalapon | 552.1, 515.1, 515.3, 552.2, 515.4 | |||
Di(2-ethylhexyl)adipate | 506, 525.2 | |||
Di(2-ethylhexyl)phthalate | 506, 525.2 | |||
Dibromochloropropane (DBCP) | 504.1, 551.1 | |||
Dinoseb3 | 515.2, 555, 515.1, 515.3, 515.4 | |||
Diquat | 549.2 | |||
Endothall | 548.1 | |||
Endrin | 505, 508, 525.2, 508.1, 551.1 | |||
Ethylene dibromide (EDB) | 504.1, 551.1 | 6651 | ||
Glyphosate | 547 | |||
Heptachlor | 505, 508, 525.2, 508.1, 551.1 | |||
Heptachlor Epoxide | 505, 508, 525.2, 508.1, 551.1 | |||
Hexachlorobenzene | 505, 508, 525.2, 508.1, 551.1 | |||
Hexachloro-cyclopentadiene | 505, 508, 525.2, 508.1, 551.1 | |||
Lindane | 505, 508, 525.2, 508.1, 551.1 | |||
Methoxychlor | 505, 508, 525.2, 508.1, 551.1 | |||
Oxamyl | 531.1, 531, 2 | 6610 | ||
PCBs(as decachlorobiphenyl)2 | 508A | |||
PCBs (as Aroclors)2 | 505, 508, 508.1, 525.2 | |||
Pentachlorophenol | 515.2, 525.2, 555, 515.1, 515.3, 515.4 | D5317-93, 98 (Reapproved 2003). | ||
Picloram3 | 515.2, 555, 515.1, 515.3, 515.4 | D5317-93, 98 (Reapproved 2003). | ||
Simazine1 | 505, 507, 525.2, 508.1, 551.1 | |||
Toxaphene | 505, 508, 508.1, 525.2 |
Footnotes
1 Substitution of the detector specified in Methods 505, 507, 508, or 508.1 for the purpose of achieving lower detection limits is allowed as follows. Either an electron capture or nitrogen phosphorus detector may be used provided all regulatory requirements and quality control criteria are met.
2 PCBs are qualitatively identified as Arolcolrs and measured for compliance purposes as decachlorobiphenyl. Users of Method 505 may have more difficulty in achieving the required detection limits than users of Methods 508.1, 525.2, or 508.
3 Accurate determination of the chlorinated esters requires hydrolysis of the sample as described in EPA Methods 515.1, 515.2, 515.3, 515.4 and 555 and ASTM Methods D5317-93,98 (Reapproved 2003).
4 This method may not be used for the analysis of atrazine in any system where chlorine dioxide is used for drinking water treatment. In samples from all other systems, any result for atrazine generated by Method AG-625 that is greater than 1/2 the maximum contaminant level (MCL) (in other words, greater than 0.0015mg/L or 1.5 ug/L) must be confirmed using another approved method for this contaminant and should use additional volume of the original sample collected for compliance monitoring. In instances where a result from Method AG-625 triggers such confirmatory testing, the confirmatory result is to be used to determine compliance.
SOC DETECTION LIMITS | |
Contaminant | Detection Limit mg/l |
Alachlor | 0.0002 |
Aldicarb | 0.0005 |
Aldicarb sulfoxide | 0.0005 |
Aldicarb sulfone | 0.0008 |
Atrazine | 0.0001 |
Benzo(a)pyrene | 0.00002 |
Carbofuran | 0.0009 |
Chlordane | 0.0002 |
Dalapon | 0.001 |
Dibromochloropropane (DBCP) | 0.00002 |
Di (2-ethythexyl) adipate | 0.0006 |
Di (2-ethylhexyl) phthalate | 0.0006 |
Dinoseb | 0.0002 |
Diquat | 0.0004 |
2,4-D | 0.0001 |
Endothall | 0.009 |
Endrin | 0.00001 |
Ethylene dibromide (EDB) | 0.00001 |
Glyphosate | 0.006 |
Heptachlor | 0.00004 |
Heptachlor epoxide | 0.00002 |
Hexachlorobenzene | 0.0001 |
Hexachlorocyclopentadiene | 0.0001 |
Lindane | 0.00002 |
Methoxychlor | 0.0001 |
Oxamyl | 0.002 |
Picloram | 0.0001 |
Polychlorinated biphenyls (PCBs) (as decachlorobiphenyl) | 0.0001 |
Pentachlorophenol | 0.00004 |
Simazine | 0.00007 |
Toxaphene | 0.001 |
2,3,7,8-TCDD (Dioxin) | 0.000000005 |
2,4,5-TP (Silvex) | 0.0002 |
BAT FOR ORGANIC CONTAMINANTS LISTED IN 310 CMR 22.07A(1)
CAS # | Chemical | GAC | PTA | OX |
15972-60-8 | Alachlor | X | ||
116-06-3 | Aldicarb | X | ||
1646-88-4 | Aldicarb sulfone | X | ||
1646-87-3 | Aldicarb sulfoxide | X | ||
1912-24-9 | Atrazine | X | ||
50-32-8 | Benzo[a)pyrene | X | ||
1563-66-2 | Carbofuran | X | ||
57-74-9 | Chlordane | X | ||
75-99-0 | Dalapon | X | ||
96-12-8 | Dibromochloropropane (DBCP) | X | X | |
75-09-2 | Dichloreomethane | X | ||
103-23-1 | Di (2-ethylhexyl) adipate | X | X | |
117-81-7 | Di (2-ethylhexyl) phthalate | X | ||
88-85-7 | Dinoseb | X | ||
85-00-7 | Diquat | X | ||
94-75-7 | 2,4-D | X | ||
72-20-8 | Endrin | X | ||
145-73-3 | Endothall | X | ||
106-93-4 | Ethylene Dibromide (EDB) | X | X | |
1071-583-6 | Glyphosate | X | ||
76-44-8 | Heptachlor | X | ||
1024-57-3 | Heptachlor epoxide | X | ||
118-74-1 | Hexachlorobenzene | X | ||
77-47-3 | Hexachlorocyclopentadiene | X | X | |
58-89-9 | Lindane | X | ||
72-43-5 | Methoxychlor | X | ||
1336-36-3 | Polychlorinated biphenyls(PCB) | X | ||
23135-22-0 | Oxamyl (Vydate) | X | ||
87-86-5 | Pentachlorophenol | X | ||
1918-02-1 | Picloram | X | ||
93-72-1 | 2,4,5-TP (Silvex) | X | ||
122-34-9 | Simazine | X | ||
120-82-1 | 1,2,4-Trichlorobenzene | X | X | |
79-00-5 | 1,1,2-Trichloroethane | X | X | |
1746-01-6 | 2,3,7,8-TCDD(Dioxin) | X | ||
8001-35-2 | Toxaphene | X | X |
310 CMR, § 22.07A