Where a cable crosses under railroad tracks, the same clearances indicated in 220 CMR 126.32(1)(e) shall apply.
Table 1
CONDUCTORS OR CABLES
Voltage Phase to Ground | Depth of Burial (Inches) |
600 and below | 24 |
601 to 22,000 | 30 |
22,001 to 40,000 | 36 |
40,001 and above | 42 |
Note: This is applicable when cable in non-metallic duct is considered as a direct buried cable installation and random separation is desired.
Exception: Where a buried cable passes through a short section of conduit, such as under a roadway, the contact with earth of the grounded conductor can be omitted, provided the grounded conductor is continuous through the conduit. The bare conductor(s) in contact with the earth shall be of suitable corrosion-resistant material.
220 CMR, § 126.35