30 C.F.R. § 75.1101-8

Current through November 30, 2024
Section 75.1101-8 - Water sprinkler systems; arrangement of sprinklers
(a) At least one sprinkler shall be installed above each belt drive, belt take-up, electrical control, and gear-reducing unit, and individual sprinklers shall be installed at intervals of no more than 8 feet along all conveyor branch lines.
(b) Two or more branch lines, at least one of which shall be above the top belt and one between the top and bottom belt, shall be installed in each sprinkler system to provide a uniform discharge of water to the belt surface.
(c) The water discharge rate from the sprinkler system shall not be less than 0.25 gallon per minute per square foot of the top surface of the top belt and the discharge shall be directed at both the upper and bottom surfaces of the top belt and to the upper surface of the bottom belt. The supply of water shall be adequate to provide a constant flow of water for 10 minutes with all sprinklers functioning.
(d) Each individual sprinkler shall be activated at a temperature of not less than 150 °F. and not more than 300 °F.
(e) Water systems shall include strainers with a flush-out connection and a manual shut-off valve.

30 C.F.R. § 75.1101-8