Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 6165 - Standpipe and Hose Systems(a) Scope and Application. (1) Scope. This Section applies to all small hose, Class II, and Class III standpipe systems.(b) General. (1) When standpipe and hose systems are provided, they shall be designed and installed in an approved manner. NOTE: For information on standpipe and hose systems design and installation, consult the National Fire Protection Association's Standard for the "Installation of Standpipe and Hose Systems", NFPA 14, 2013 edition and/or your local jurisdiction fire department.
(c) Protection of Standpipes. (1) The employer shall assure that standpipes are located or otherwise protected against mechanical damage. Damaged standpipes shall be repaired promptly.(d) Equipment. (1) Reels and Cabinets. Where reels or cabinets are provided to contain fire hose, the employer shall assure that they are designed to facilitate prompt use of the hose valves, the hose, and other equipment at the time of a fire or other emergency. The employer shall assure that the reels and cabinets are conspicuously identified and used only for fire equipment.(2) Hose Outlets and Connections.(A) The employer shall assure that hose outlets and connections are located high enough above the floor to avoid being obstructed and to be accessible to employees.(B) The employer shall standardize screw threads or provide appropriate adapters throughout the system and assure that the hose connections are compatible with those used on the supporting fire equipment.(3) Hose. (A) The employer shall assure that every 1 1/2" (3.8 cm) or smaller hose outlet used to meet this standard is equipped with hose connected and ready for use. In extremely cold climates where such installation may result in damaged equipment, the hose may be stored in another location provided it is immediately available and can be connected when needed.(B) Standpipe systems installed after July 1, 1981, for use by employees, shall be equipped with lined hose. Unlined hose may remain in use on existing systems. However, after the effective date of this standard, unlined hose which becomes unserviceable shall be replaced with lined hose.(C) Beginning July 1, 1981, the employer shall provide hose of such length that friction loss resulting from water flowing through the hose will not decrease the pressure at the nozzle below 30 psi (210 kPa). The dynamic pressure at the nozzle shall be within the range of 30 psi (210 kPa) to 125 psi (860 kPa).(4) Nozzles. Beginning July 1, 1981, the employer shall assure that all lined standpipe hose is equipped with shut-off type nozzles.(e) Water Supply.(1) The minimum water supply for standpipe and hose systems, which are provided for the use of employees, shall be sufficient to provide 100 gallons per minute (6.3 l/s) for a period of at least thirty minutes.(f) Tests and Maintenance. (1) Acceptance Tests. (A) The employer shall assure that the piping of Class II and Class III systems installed after July 1, 1981, including yard piping, is hydrostatically tested for a period for at least 2 hours at not less than 200 psi (1380 kPa), or at least 50 psi (340 kPa) in excess of normal pressure when such pressure is greater than 150 psi (1030 kPa).(B) The employer shall assure that hose on all standpipe systems installed after July 1, 1981, is hydrostatically tested with couplings in place, at a pressure of not less than 200 psi (1380 kPa), before it is placed in service. This pressure shall be maintained for at least 15 seconds and not more than one minute during which time the hose shall not leak nor shall any jacket thread break during the test.(2) Maintenance. (A) The employer shall assure that water supply tanks are kept filled to the proper level except during repairs. When pressure tanks are used, the employer shall assure that proper pressure is maintained at all times except during repairs.(B) The employer shall assure that valves in the main piping connections to the automatic sources of water supply are kept fully open at all times except during repair.(C) The employer shall assure that hose systems are inspected at least annually and after each use to assure that all of the equipment and hose are in place, available for use, and in serviceable condition.(D) When the system or any portion thereof is found not to be serviceable, the employer shall remove it from service immediately and replace it with equivalent protection such as extinguishers and fire watches.(E) Hemp or linen hose on existing systems shall be inspected for deterioration at least annually. Defective hose shall be replaced in accordance with Section 6165(d)(3)(B).(F) The employer shall designate trained persons to conduct all inspections required under this Section.Cal. Code Regs. Tit. 8, § 6165
1. Repealer of Article 158 (Sections 6165-6167) and new Article 158 (Section 6165) filed 9-8-81; effective thirtieth day thereafter (Register 81, No. 37). For prior history, see Registers 81, No. 4 and 76, No. 29.
2. Change without regulatory effect deleting Title 24 reference (Register 87, No. 49).
3. Amendment of subsection (b)(1) filed 12-2-2014; operative 1-1-2015 (Register 2014, No. 49). Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
1. Repealer of Article 158 (Sections 6165-6167) and new Article 158 (Section 6165) filed 9-8-81; effective thirtieth day thereafter (Register 81, No. 37). For prior history, see Registers 81, No. 4 and 76, No. 29.
2. Change without regulatory effect deleting Title 24 reference (Register 87, No. 49).