Section 2230 - Required Gas Supply(a) The minimum hourly volume of gas required at each lot outlet, or any section of a park gas piping system shall be calculated as shown in Table 2230-1.(b) Required gas supply for other fuel gas consuming appliances connected to the park gas piping system shall be calculated as provided in the California Plumbing Code, Chapter 12. Table 2230-1 |
Demand Factors for Use in Calculating Gas Piping Systems in Parks |
|
Number of Lots | | BTU Per Hours Per Lot |
1 | | | 125,000 | |
2 | | | 117,000 | |
3 | | | 104,000 | |
4 | | | 96,000 | |
5 | | | 92,000 | |
6 | | | 87,000 | |
7 | | | 83,000 | |
8 | | | 81,000 | |
9 | | | 79,000 | |
10 | | | 77,000 | |
11-20 | | | 62,000 | |
21-30 | | | 62,000 | |
31-40 | | | 58,000 | |
41-60 | | | 55,000 | |
Over 60 | | | 50,000 | |
Cal. Code Regs. Tit. 25, § 2230
1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28). Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.4, Health and Safety Code.