Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 1230 - Required Gas Supply(a) The minimum hourly volume of gas required at each lot outlet, or any section of a park gas piping system shall be calculated as shown in Table 1230-1.(b) Required gas supply for other fuel gas consuming appliances connected to the park gas piping system shall be calculated as provided in the California Plumbing Code, Chapter 12. Table 1230-1 Demand Factors for Use in Calculating Gas Piping Systems in Parks |
Number of Lots | BTU Per Hours Per Lot |
| 1 | 125,000 | |
| 2 | 117,000 | |
| 3 | 104,000 | |
| 4 | 96,000 | |
| 5 | 92,000 | |
| 6 | 87,000 | |
| 7 | 83,000 | |
| 8 | 81,000 | |
| 9 | 79,000 | |
| 10 | 77,000 | |
| 11-20 | 66,000 | |
| 21-30 | 62,000 | |
| 31-40 | 58,000 | |
| 41-60 | 55,000 | |
| Over 60 | 50,000 | |
Cal. Code Regs. Tit. 25, § 1230
1. Amendment of subsection (b) filed 8-22-85; effective upon filing pursuant to Government Code Section 11346.2(d) (Register 85, No. 36).
2. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28). Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18690, Health and Safety Code.
1. Amendment of subsection (b) filed 8-22-85; effective upon filing pursuant to Government Code Section 11346.2(d) (Register 85, No. 36).
2. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).