Cal. Code Regs. tit. 25 § 1176

Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 1176 - Aluminum Conductors
(a) Connections of aluminum conductors shall be made only inside boxes or equipment enclosures which are designed and installed to prevent the entry or accumulation of moisture within the enclosure.
(b) Only connectors which are listed for use with aluminum conductors shall be used to connect aluminum conductors. If more than one conductor is connected to a connector, the connector shall be provided with a terminal fitting for each conductor.
(c) Prior to inserting an aluminum conductor into the connector, the conductor from which the insulation has been removed shall be wire-brushed and sealed with an approved oxide-inhibiting joint compound.

Cal. Code Regs. Tit. 25, § 1176

1. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).

Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18670, Health and Safety Code.

1. Amendment filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).