Cal. Code Regs. tit. 22 § 64433.3

Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 64433.3 - Monitoring and Compliance-Fluoride Levels
(a) If a water system has a single fluoridation system which treats all the water distributed to consumers, the supplier shall collect a daily sample for fluoride analysis, pursuant to Section 64415(b), either in the distribution system or at the entry point. If a water system does not fluoridate all its water and/or has more than one fluoridation system, the supplier shall collect one sample daily in the distribution system and rotate the sample sites in order to be representative of the water throughout the distribution system according to a monitoring plan the State Board has determined to be representative. For water systems fluoridating as of January 1, 1997, the plan shall be submitted by July 1, 1998. For all others, the plan shall be submitted prior to initiating fluoridation treatment. A water system shall monitor only when it is operating its fluoridation system.
(b) If more than 20 percent of the daily fluoride samples collected in a month by a water system pursuant to subsection (a) fall outside the control range of optimal levels as determined by temperature for that system pursuant to Section 64433.2, the system shall be out of compliance with Section 64433.2.
(c) At least once a month, any water supplier with an operating fluoridation system shall divide one sample and have one portion analyzed for fluoride by water system personnel and the other portion analyzed pursuant to Section 64415(a).
(d) Any water system with an operating fluoridation system shall sample the raw source waters annually and analyze for fluoride pursuant to Section 64415(a); samples collected pursuant to Section 64432(c)(1) may be used toward satisfying this requirement. All raw source water samples collected under this subsection are subject to compliance with the fluoride MCL in Table 64431-A.
(e) If any sample result obtained pursuant to subsection (a) does not fall within the temperature-appropriate fluoride level control range in Table 64433.2-A, the water supplier shall take action as detailed in the water system's approved fluoridation system operations contingency plan as specified in section 64433.8.

Cal. Code Regs. Tit. 22, § 64433.3

1. New section filed 3-23-98; operative 4-22-98 (Register 98, No. 13).
2. Amendment of subsection (d) and amendment of NOTE filed 10-29-2008; operative 11-28-2008 (Register 2008, No. 44).
3. Change without regulatory effect amending subsection (a) and NOTE filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).

Note: Authority cited: Sections 116271, 116385, 116410 and 116415, Health and Safety Code. Reference: Sections 116365, 116410 and 116415, Health and Safety Code.

1. New section filed 3-23-98; operative 4-22-98 (Register 98, No. 13).
2. Amendment of subsection (d) and amendment of Note filed 10-29-2008; operative 11-28-2008 (Register 2008, No. 44).
3. Change without regulatory effect amending subsection (a) and Note filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).