Wash. Admin. Code § 51-50-0713

Current through Register Vol. 24-16, August 15, 2024
Section 51-50-0713 - Section 713-Shaft enclosures
713.13.7Chute venting and roof termination. The full diameter of waste and linen chutes shall extend a minimum of 3 feet (0.92 m) above the building roof and be gravity vented in accordance with International Mechanical Code Section 515.

EXCEPTIONS:

1. Where mechanically ventilated in accordance with International Mechanical Code Section 515 the full diameter of the chute shall extend through the roof a minimum of 3 feet (0.92 m) and terminate at a blast cap. The mechanical exhaust connection shall tap into the side of the blast cap extension above the roof.

2. Where the trash chute does not extend to the upper floor of the building below the roof the trash chute shall be permitted to gravity vent to a sidewall louver termination. The horizontal extension of the trash chute shall be the full diameter of the chute and shall be enclosed in rated construction equal to the rating of the shaft enclosure. Where the chute is mechanically ventilated in accordance with International Mechanical Code Section 515 the blast cap shall terminate behind the louver and the exhaust fan and duct connection will be enclosed in the rated shaft.

Wash. Admin. Code § 51-50-0713

Adopted by WSR 20-01-090, Filed 12/12/2019, effective 7/1/2020
Amended by WSR 22-13-094, Filed 6/14/2022, effective 7/1/2023