Section 51-11C-404091 - Section C404.10-Drain water heat recovery units

C404.10 Drain water heat recovery units. Drain water heat recovery units shall comply with CSA B55.2. Potable water side pressure loss shall be less than 10 psi (69 kPa) at maximum design flow. For Group R occupancies, the efficiency of drain water heat recovery unit efficiency shall be in accordance with CSA B55.1.