Wash. Admin. Code § 51-11C-40354

Current through Register Vol. 24-16, August 15, 2024
Section 51-11C-40354 - Section C403.5.4-Waterside economizers
C403.5.4Waterside economizers. Waterside economizers shall comply with Sections C403.5.4.1 and C403.5.4.2.
C403.5.4.1Design capacity. Water economizer systems shall be configured to cool supply air by indirect evaporation and providing up to 100 percent of the expected system cooling load at outdoor air temperatures of 50°F dry-bulb (10°C dry-bulb)/45°F wet-bulb (7.2°C wet-bulb) and below.

EXCEPTION

:

Systems where dehumidification requirements cannot be met using outdoor air temperatures of 50°F dry-bulb (10°C dry-bulb)/45°F wet-bulb (7. 2°C wet-bulb) and where 100 percent of the expected system cooling load at 45°F dry-bulb (7. 2°C dry-bulb)/40°F wet-bulb (4. 5°C wet-bulb) is met with evaporative water economizers.

C403.5.4.2Maximum pressure drop. Precooling coils and water-to-water heat exchangers used as part of a water economizer system shall either have a waterside pressure drop of less than 15 feet (4572 mm) of water or a secondary loop shall be created so that the coil or heat exchanger pressure drop is not seen by the circulating pumps when the system is in the normal cooling (noneconomizer) mode.

Wash. Admin. Code § 51-11C-40354

Adopted by WSR 19-24-040, Filed 11/26/2019, effective 7/1/2020
Amended by WSR 20-21-080, Filed 10/19/2020, effective 2/1/2021