Wash. Admin. Code § 296-811-40015

Current through Register Vol. 24-16, August 15, 2024
Section 296-811-40015 - Self-contained breathing apparatus' (SCBAs)
(1) Provide SCBAs, other than escape self-contained breathing apparatus' (ESCBAs), and make sure they are used by each fire brigade member who does interior structural firefighting.
(2) Make sure SCBAs do the following:
(a) Meet the requirements found in chapter 296-842 WAC, Respirators.
(b) Are positive-pressure or pressure-demand type.
(c) Use only compressed-air cylinders that meet department of transportation (DOT) and the National Institute for Occupational Safety and Health (NIOSH) requirements.
(d) Have a service life of at least thirty minutes, as required by 42 C.F.R., Part 84.
(e) Have an automatic alarm that can be heard when seventy-five to eighty percent of its service life has been used up.

Note:

An SCBA can have a quick-disconnect valve or "buddy breathing" accessory only if the valve or accessory does not do any of the following:

1. Damage the SCBA.

2. Restrict the SCBA's air flow.

3. Interfere with the SCBA's normal operation.

4. The "buddy breathing" accessory or quick-disconnect valve need not be certified by NIOSH.

Wash. Admin. Code § 296-811-40015

Amended by WSR 17-18-075, Filed 9/5/2017, effective 10/6/2017

Statutory Authority: RCW 49.17.010, 49.17.040, 49.17.050, 49.17.060. 09-15-145, § 296-811-40015, filed 7/21/09, effective 9/1/09; 06-01-073, § 296-811-40015, filed 12/20/05, effective 3/1/06.