Exception: Wall-mounted visible alarm notification appliances in Group I-3 occupancies shall be permitted to be a maximum of 120 inches (3048 mm) above the floor or ground, measured to the bottom of the appliance. Such appliances shall otherwise comply with all applicable requirements.
Exception: This section does not apply to parking spaces used exclusively for buses, trucks, other delivery vehicles, law-enforcement vehicles, or vehicular impound and motor pools where lots accessed by the public are provided with an accessible passenger loading zone.
Table 1106.2(1) Accessible Parking Spaces for Groups A, B, E, M, R-1, R-2, and Ia | |
Total Parking Spaces Provided | Required Minimum Number of Accessible Spaces |
1 - 25 | 1 |
26 - 50 | 2 |
51 - 75 | 3 |
76 - 100 | 4 |
101 - 125 | 5 |
126 - 150 | 6 |
151 - 200 | 7 |
201 - 300 | 8 |
301 - 400 | 9 |
401 - 500 | 10 |
501 - 1,000 | 2.33% of total |
1,001 and over | 23, plus one for each 100, or fraction thereof, over 1,000 |
a. Condominium parking in Group R-2 occupancies where parking is part of the unit purchase shall be in accordance with Table 1106.2.2. |
Table 1106.2(2) Accessible Parking Spaces for Groups F, S, H, R-3, R-4, and U | |
Total Parking Spaces Provided | Required Minimum Number of Accessible Spaces |
1 - 25 | 1 |
26 - 50 | 2 |
51 - 75 | 3 |
76 - 100 | 4 |
101 - 150 | 5 |
151 - 200 | 6 |
201 - 300 | 7 |
301 - 400 | 8 |
401 - 500 | 9 |
501 - 1,000 | 2.0% of total |
1,001 and over | 20, plus one for each 100, or fraction thereof, over 1,000 |
13 Va. Admin. Code § 5-63-250
Statutory Authority: § 36-98 of the Code of Virginia.