TABLE 1
Bore Pit Locations | |
Bore Pit Set Back | Outside Clear Zone |
At least ten feet from the edge of pavement, five feet beyond toe of slope under fill sections and at least five feet from the face of curb | At least 30 feet from the edge of the nearest through traffic lane and at least 20 feet from the edge of pavement on ramps. |
TABLE 2
MINIMUM DEPTH OF BURY (Cover) For Underground Utility Facilities*
Location | Under Pavement | Under Sidewal | Under kitch | Utility Location Less Than 20 ft. From Edge of Pavement | Utility Location Greater Than 20 ft. From Edge of Pavement |
Minimum Depth | 4 ft. | 3 ft. | 3 ft. | 5 ft. | 3 ft.** |
Measured From | Top of Pavement | Top of Sidewalk | Low point of Ditch | Ground Surface | Ground Surface |
Measured | Measured Top of Utility Facility or Utility Buffer Zone (if required To by Utility Company) * Applies to longitudinal and crossing installations, cased and uncased. ** Specific types of facilities such as high - pressure gas lines may require additional cover. |
Any installation of overhead facilities shall be made at a location and in a manner that will not detract from the scenic quality of the area being traversed. The installation shall utilize a suitable design and use materials aesthetically compatible to the scenic area, as approved by UDOT.
Utah Admin. Code R930-7-8