S.C. Code Regs. § § 61-58.9.I

Current through Register Vol. 48, No. 9, September 27, 2024
Section 61-58.9.I - Variances and Exemptions from the Maximum Contaminant Levels for Radionuclides
(1) The following are identified as the best available technology, treatment techniques, or other means available for achieving compliance with the maximum contaminant levels for radionuclides listed in R.61-58.5.H(2), (3), (4), and (5), for the purposes of issuing variances and exemptions, as shown in Table A to this paragraph.

TABLE A: BAT FOR RADIONUCLIDES LISTED IN R.61-58.5.H

Contaminant

BAT

Combined radium-226 and radium-228

Ion exchange, reverse osmosis, lime softening.

Uranium

Ion exchange, reverse osmosis, lime softening, coagulation/filtration.

Gross alpha particle activity (excluding radon and uranium)

Reverse osmosis.

Beta particle and photon radioactivity

Ion exchange, reverse osmosis.

(2) In addition, the following are identified as the best available technology, treatment techniques, or other means available for achieving compliance with the maximum contaminant levels for the radionuclides listed in R.61-58.5.H(2), (3), (4), and (5), for the purposes of issuing variances and exemptions to small drinking water systems, defined here as those serving 10,000 persons or fewer, as shown in Table C to this paragraph.

TABLE B: LIST OF SMALL SYSTEMS COMPLIANCE TECHNOLOGIES FOR RADIONUCLIDES AND LIMITATIONS TO USE

Unit technologies

Limitations (see footnotes)

Operator skill level required [FN1]

Raw water quality range & considerations [FN1]

1. Ion exchange (IE)

( [FNa])

Intermediate

All ground waters.

2. Point of use (POU [FN2]) IE

( [FNb])

Basic

All ground waters.

3. Reverse osmosis (RO)

( [FNc])

Advanced

Surface waters usually require pre-filtration.

4. POU [FN2] RO

( [FNb])

Basic

Surface waters usually require pre-filtration.

5. Lime softening

( [FNd])

Advanced

All waters.

6. Green sand filtration

( [FNe])

Basic

7. Co-precipitation with barium sulfate

( [FNf])

Intermediate to Advanced

Ground waters with suitable water quality.

8.

Electrodialysis/electrodialysis reversal

Basic to Intermediate

All ground waters.

9. Pre-formed hydrous manganese oxide filtration

( [FNg])

Intermediate

All ground waters.

10. Activated alumina

( [FNa]), ( [FNh])

Advanced

All ground waters; competing anion concentrations may affect regeneration frequency

11. Enhanced coagulation/filtration

( [FNi])

Advanced.

Can treat a wide range of water qualities.

[FN1] National Research Council (NRC). Safe Water from Every Tap: Improving Water Service to Small Communities. National Academy Press. Washington, D.C. 1997.

[FN2] A POU, or "point-of-use" technology is a treatment device installed at a single tap used for the purpose of reducing contaminants in drinking water at that one tap. POU devices are typically installed at the kitchen tap. See the April 21, 2000 NODA for more details. Limitations Footnotes: Technologies for Radionuclides:

[FNa] The regeneration solution contains high concentrations of the contaminant ions. Disposal options should be carefully considered before choosing this technology.

[FNb] When POU devices are used for compliance, programs for long-term operation, maintenance, and monitoring must be provided by water utility to ensure proper performance.

[FNc] Reject water disposal options should be carefully considered before choosing this technology. See other RO limitations described in the SWTR compliance technologies table.

[FNd] The combination of variable source water quality and the complexity of the water chemistry involved may make this technology too complex for small surface water systems.

[FNe] Removal efficiencies can vary depending on water quality.

[FNf] This technology may be very limited in application to small systems. Since the process requires static mixing, detention basins, and filtration, it is most applicable to systems with sufficiently high sulfate levels that already have a suitable filtration treatment train in place.

[FNg] This technology is most applicable to small systems that already have filtration in place.

[FNh] Handling of chemicals required during regeneration and pH adjustment may be too difficult for small systems without an adequately trained operator.

[FNi] Assumes modification to a coagulation/filtration process already in place.

TABLE C: BAT FOR SMALL COMMUNITY WATER SYSTEMS FOR THE RADIONUCLIDES LISTED IN R.61-58.5.H

Contaminant

Compliance technologies [FN1] for system size categories (population served)

25-500

501-3,300

3,300-10,000

Combined radium-226 and radium-228

1, 2, 3, 4, 5, 6, 7, 8, 9

1, 2, 3, 4, 5, 6, 7, 8, 9

1, 2, 3, 4, 5, 6, 7, 8, 9

Gross alpha particle activity

3, 4

3, 4

3, 4

Beta particle activity and photon activity

1, 2, 3, 4

1, 2, 3, 4

1, 2, 3, 4

Uranium

1, 2, 4, 10, 11

1, 2, 3, 4, 5, 10, 11

1, 2, 3, 4, 5, 10, 11

[FN1] Note: Numbers correspond to those technologies found listed in the Table B to this paragraph.

(3) The Department shall require community water systems to install and/or use any treatment technology identified in Table A to this section, or in the case of small water systems (those serving 10,000 persons or fewer), Table B and Table C of this section, as a condition for granting a variance except as provided in paragraph (4) of this section. If, after the system's installation of the treatment technology, the system cannot meet the MCL, that system shall be eligible for a variance under the provisions of this section.
(4) If a community water system can demonstrate through comprehensive engineering assessments, which may include pilot plant studies, that the treatment technologies identified in this section would only achieve a de minimus reduction in the contaminant level, the Department may issue a schedule of compliance that requires the system being granted the variance to examine other treatment technologies as a condition of obtaining the variance.
(5) If the Department determines that a treatment technology identified under paragraph (4) of this section is technically feasible, the Administrator or the Department may require the system to install and/or use that treatment technology in connection with a compliance schedule issued under the provisions of this section. The Department's determination shall be based upon studies by the system and other relevant information.
(6) The Department may require a community water system to use bottled water, point-of-use devices, point-of-entry devices or other means as a condition of granting a variance or an exemption from the requirements of R.61-58.5.H of this regulation, to avoid an unreasonable risk to health.
(7) Community water systems that use bottled water as a condition for receiving a variance or an exemption from the requirements of R.61-58.5.H of this regulation must meet the requirements specified in Section F(7)(a) through (c) above.
(8) Community water systems that use point-of-use or point-of-entry devices as a condition for obtaining a variance or an exemption from the radionuclides SPDWRs must meet the conditions in Section F(8) above.

S.C. Code Regs. § 61-58.9.I