Section 61-16.1909 - Temperature and Humidity
A. Minimum design temperature of 75 degrees F. (23.9 degrees C.) at winter design conditions and 81 degrees F. maximum summer design conditions shall be provided for all occupied areas not listed below. The systems shall be designed to provide the following temperatures and humidities in the areas noted:

Area

Temperature

Relative Humidity

Designation

F

C

Minimum

Maximum

Operating Room

68-75

20.0-24.0

20

60

Recovery Rooms

75

23.9

30

60

Intensive Care Units

75-80

23.9-26.7

30

60

B. Perinatal design temperature and humidity shall follow the current edition of Guidelines for Perinatal Care.

S.C. Code Regs. 61-16.1909

Replaced and amended by State Register Volume 38, Issue No. 6, eff 6/27/2014.