This rule shall apply to temporary conditions where there is danger of employees or material falling through floor, roof or wall openings or from stairways or runways.
Temporary floors shall be provided in all structures for employees working on various floor levels and shall be substantially constructed to support employees and equipment safely.
The planks shall be placed as close together as possible and shall not extend more than one foot beyond supports unless securely fastened to prevent slipping or tipping.
In buildings or structures where the upper floors are constructed before the lower floors, temporary floors of the strength required in paragraph (C)(1) of this rule shall be maintained no more than two floors below the floor being constructed.
The provisions of paragraph (C)(5)(a) of this rule shall not apply to what is generally known as mill buildings where no floors are contemplated, and where the operation of overhead cranes, etc., will not permit compliance.
Reinforced concrete frame constructed buildings shall have floor or concrete forms constructed before the forms of the story above are started.
In sectionally constructed buildings each section constitutes a separate building operation in the application of the temporary floor requirements of this rule.
Floor openings shall be guarded by a standard guard railing and toeboard or a cover with a safety factor of no less than two and so constructed that the cover cannot be accidentally displaced. A safety belt or harness with a lanyard may be provided in lieu of a standard guard railing and toeboard or cover.
Ladder or openings shall be guarded by a standard guard railing and toeboard on all exposed sides except at the entrance to the opening, with the passage through the standard guard railing either provided with a swinging gate or so offset that an employee cannot walk directly into the opening.
Floor holes into which employees can accidentally walk, shall be provided with either a standard guard railing and toeboard on all exposed sides, or a floor hole cover which provides a factor of safety of no less than two and so constructed that the cover cannot be accidentally displaced. While the cover is not in place, the floor hole shall be guarded by a standard guard railing.
A removable standard guard railing and toeboard shall be provided on no more than two sides of the hatchway opening and fixed standard guard railing and toeboard shall be provided on all other exposed sides. The removable portion of the standard guard railings shall be kept in place when the opening is not in use and where practicable should be hinged or otherwise mounted so as to be conveniently replaceable.
Each employee working on, at, above, or near wall openings (including those with chutes attached) shall be protected from falling by the use of a guardrail system, a safety net system, or a personal fall arrest system.
If spreaders are used in window or door frames, such spreaders shall be substantially secured in place.
Wherever there is a danger of an employee falling six feet or more to a lower level through a roof opening, including skylights, a standard guard railing and toeboard shall be provided on all exposed sides, or a cover which provides a factor of safety of no less than two shall be provided. A safety belt or harness or a safety net system may be provided in lieu of the standard guard railing and toeboard or cover.
For wood railings, the uprights shall be of no less than two-inch by four-inch (nominal) stock space not to exceed eight feet; the top rail shall be of no less than two-inch by four-inch (nominal) stock; the intermediate rail shall be of no less than one-inch by six-inch stock (nominal).
Except during stairway construction, foot traffic is prohibited on stairways with pan stairs where the treads and/or landings are to be filled in with concrete or other material at a later date, unless the stairs are temporarily fitted with wood or other solid material at least to the top edge of each pan. Such temporary treads and landings shall be replaced when worn below the level of the top edge of the pan.
Treads for temporary service shall be made of wood or other solid material, and shall be installed the full width and depth of the stair.
Stairways, ramps, runways and platforms shall be lighted to no less than the minimum illumination intensity of five foot-candles.
A stair railing shall be of construction similar to a standard guard railing, except that the vertical height shall be no less than thirty-six inches from the upper surface of the top rail to the surface of the tread in line with the face of the riser at the forward edge of the tread.
Overhead protection shall be provided where employees are working below other employees on floor levels with open floor above.
The height of the standard guard railing on bridge decks may be adjusted to provide clearance for the operation of paving machinery.
Ohio Admin. Code 4123:1-3-04
Five Year Review (FYR) Dates: 10/29/2019 and 01/01/2025
Promulgated Under: 119.03
Statutory Authority: 4121.12, 4121.121, 4121.13, Const. Art. II, Sec. 35
Rule Amplifies: 4121.47
Prior Effective Dates: 04/01/1968, 11/01/1979, 04/01/1999, 01/01/2011