N.D. Admin. Code 24.1-06-06-25

Current through Supplement No. 394, October, 2024
Section 24.1-06-06-25 - (NEC 625) Electric vehicle charging system

625.41 Overcurrent protection. Overcurrent protection for feeders and branch circuits supplying vehicle charging equipment must be sized for continuous duty and must have a rating of not less than one hundred twenty-five percent of the maximum load of the equipment. For these installations, "maximum load of equipment" means the setting the electrician adjusted the device to. The adjustment may not be readily accessible or cannot easily be adjusted by the consumer. The electrician shall label the device if set to a value less than the maximum nameplate rating. The contractor shall assure the size of the service feeding these devices is adequate.

N.D. Admin Code 24.1-06-06-25

Adopted by Administrative Rules Supplement 2020-377, July 2020, effective 7/1/2020.
Amended by Administrative Rules Supplement 2020-378, October 2020, effective 7/1/2020.

General Authority: NDCC 43-09-05

Law Implemented: NDCC 43-09-21, 43-09-22