N.M. Code R. § 14.10.4.14

Current through Register Vol. 35, No. 16, August 27, 2024
Section 14.10.4.14 - CHAPTER 4 EQUIPMENT FOR GENERAL USE

Article 422 Appliances. See this article of the NEC and add the following to section 422.19. evaporative cooling units where an evaporative cooler is installed, a listed raceway shall be installed during rough-in from the control point to the evaporative cooler location. The raceway shall contain a wire-type equipment-grounding conductor from the control point outlet box to the junction box at the unit. The equipment grounding conductor shall be sized in accordance with table 250.122

N.M. Code R. § 14.10.4.14

14.10.4.14 NMAC - Rp, 14.10.4.14 NMAC, 6-28-13, Adopted by New Mexico Register, Volume XXXIV, Issue 04, February 28, 2023, eff. 3/28/2023