Nev. Admin. Code § 444.188

Current through September 16, 2024
Section 444.188 - Equipment rooms
1. Pumps, chlorinators and other electrical equipment must be installed in a protective enclosure.
2. If any part of the equipment room is below grade, access by stairway and suitable drainage, by sump pump if necessary, must be provided. If an open stairwell is used, ventilation through a fully louvered door and a permanently open louvered vent on at least one other side of the room is required. Enclosed stairways require louvered vents on three sides of the room or an exhaust fan. The access opening must be at least 3 feet x 6 feet (0.9 x 1.8 meters).
3. Equipment must be installed so that there is adequate clearance to allow for its normal operation and maintenance. An equipment room must have space to store chemicals and auxiliary equipment.

Nev. Admin. Code § 444.188

Bd. of Health, Public Bathing Places Reg. Art. 25, eff. 5-21-74-NAC A 9-17-82; 11-1-88

NRS 439.200, 444.070