229 Neb. Admin. Code, ch. 20, § 006

Current through September 17, 2024
Section 229-20-006

The safety valve capacity of each power boiler shall be such that the safety valve or valves will discharge all the steam that can be generated by the power boiler, without allowing the pressure to rise more than six percent above the highest pressure to which any valve is set, and in no case, to more than six percent above maximum allowable working pressure.

229 Neb. Admin. Code, ch. 20, § 006

Adopted effective 8/7/2016.