Mich. Admin. Code R. 400.18617

Current through Vol. 24-15, September 1, 2024
Section R. 400.18617 - Fire alarms

Rule 617.

(1) A new or existing congregate facility shall be equipped with an approved electrically operated, closed circuit, self-supervised, local fire alarm system that has suitable signaling devices which will communicate the alarm of fire to the personnel on each floor of the building. A system shall also have approved actuating stations that are suitably located on each floor and in the basement so that it is not necessary to travel more than 100 feet from any room to reach a station on the same floor.
(2) A telephone or other suitable means of communicating an alarm of fire to the fire department shall be provided. A pay station is not an approved means of sending an alarm.
(3) An alarm shall be tested every 6 months and a record maintained of the test.
(4) The electrical circuit that serves a fire alarm device shall be installed on a separate circuit and, in new construction, shall be installed in nonflexible metallic conduit and fused ahead of the main entrance switch.

Mich. Admin. Code R. 400.18617

1994 AACS