Kan. Admin. Regs. § 26-40-305

Current through Register Vol. 43, No. 24, August 22, 2024
Section 26-40-305 - Nursing facility physical environment; mechanical, electrical, and plumbing systems
(a) Applicability. This regulation shall apply to all nursing facilities.
(b) Codes and standards. Each nursing facility shall meet the requirements of the building codes, standards, and regulations enforced by city, county, or state jurisdictions. The requirements specified in this regulation shall be considered as a minimum.
(1) Each nursing facility shall meet the requirements of the national fire protection association's NFPA 101 "life safety code" (LSC), as adopted by reference in K.A.R. 26-39-105 .
(2) Each applicant for a nursing facility license and each addition to a nursing facility licensed on or after the effective date of this regulation shall meet the requirements of the "international building code" (IBC), as adopted by reference in K.A.R. 26-39-105 .
(3) Each nursing facility and each portion of each nursing facility that was approved under a previous regulation shall, at a minimum, remain in compliance with the regulation or building code in effect at the date of licen-sure, unless otherwise indicated.
(4) Each nursing facility shall have a complete set of manufacturer's operating, maintenance, and preventive maintenance instructions for each piece of building, mechanical, dietary, and laundry equipment.
(c) Heating, ventilation, and air conditioning systems. Each nursing facility's heating, ventilation, and air conditioning systems shall be initially tested, balanced, and operated to ensure that system performance conforms to the requirements of the plans and specifications.
(1) Each nursing facility shall have a test and balance report from a certified member of the national environmental balancing bureau or the associated air balance council and shall maintain a copy of the report for inspection by department personnel.
(2) Each nursing facility shall meet the minimum ventilation rate requirements in table 1a. If the building was licensed as a nursing facility on the effective date of this regulation, the minimum ventilation rate requirements shall be the levels specified in table 1b.
(3) Each nursing facility shall have a heating, ventilation, and air conditioning system designed to maintain a year-round indoor temperature range of 70°F to 85°F in resident care areas.
(d) Insulation. Each nursing facility shall have insulation surrounding the mechanical, electrical, and plumbing equipment to conserve energy, protect residents and personnel, prevent vapor condensation, and reduce noise. Insulation shall be required for the following fixtures within the nursing facility:
(1) All ducts or piping operating at a temperature greater than 100F; and
(2) all ducts or pipes operating at a temperature below ambient at which condensation could occur.
(e) Plumbing and piping systems. The water supply systems of each nursing facility shall meet the following requirements:
(1) Water service mains, branch mains, risers, and branches to groups of fixtures shall be valved. A stop valve shall be provided at each fixture.
(2) Backflow prevention devices or vacuum breakers shall be installed on hose bibs, janitors' sinks, bedpan flushing attachments, and fixtures to which hoses or tubing can be attached.
(3) Water distribution systems shall supply water during maximum demand periods at sufficient pressure to operate all fixtures and equipment.
(4) Water distribution systems shall provide hot water at hot water outlets at all times. A maximum variation of 98°F to 120°F shall be acceptable at bathing facilities, at sinks in resident-use areas, and in clinical areas. At least one sink in each dietary services area not designated as a hand-washing sink shall have a maximum water temperature of 120°F.
(5) Water-heating equipment shall have sufficient capacity to supply hot water at temperatures of at least 120°F in dietary and laundry areas. Water temperature shall be measured at the hot water point of use or at the inlet to processing equipment.
(f) Electrical requirements. Each nursing facility shall have an electrical system that ensures the safety, comfort, and convenience of each resident.
(1) Panelboards serving lighting and appliance circuits shall be located on the same floor as the circuits the panelboards serve. This requirement shall not apply to emergency system circuits.
(2) The minimum lighting intensity levels shall be the levels specified in table 2a. Portable lamps shall not be an acceptable light source to meet minimum requirements, unless specified in table 2a. If the building was licensed as a nursing facility on the effective date of this regulation, the minimum lighting intensity levels shall be the levels specified in table 2b.
(3) Each electrical circuit to fixed or portable equipment in hydrotherapy units shall have a ground-fault circuit interrupter.
(4) Each resident bedroom shall have at least one duplex-grounded receptacle on each side of the head of each bed and another duplex-grounded receptacle on another wall. A television convenience outlet shall be located on at least one wall. If the building was constructed before February 15, 1977 and licensed as a nursing facility on the effective date of this regulation, each resident bedroom shall have at least one duplex-grounded receptacle.
(5) Duplex-grounded receptacles for general use shall be installed a maximum of 50 feet apart in all corridors and a maximum of 25 feet from the ends of corridors.
(g) Emergency power. Each nursing facility shall have an emergency electrical power system that can supply adequate power to operate all of the following:
(1) Lighting of all emergency entrances and exits, exit signs, and exit directional lights;
(2) equipment to maintain the fire detection, alarm, and extinguishing systems;
(3) exterior electronic door monitors;
(4) the call system;
(5) a fire pump, if installed;
(6) general illumination and selected receptacles in the vicinity of the generator set;
(7) the paging or speaker system if the system is intended for communication during an emergency; and
(8) if life-support systems are used, an emergency generator. The emergency generator shall be located on the premises and shall meet the requirements of the LSC, as adopted by reference in K.A.R. 26-39-105 .
(h) Reserve heating. Each nursing facility's heating system shall remain operational under loss of normal electrical power. Each nursing facility shall have heat sources adequate in number and arrangement to accommodate the nursing facility's needs if one or more heat sources become inoperable due to breakdown or routine maintenance.
(i) Preventive maintenance program. Each nursing facility shall have a preventive maintenance program to ensure that all of the following conditions are met:
(1) All electrical and mechanical equipment is maintained in good operating condition.
(2) The interior and exterior of the building are safe, clean, and orderly.
(3) Resident care equipment is maintained in a safe, operating, and sanitary condition.
(j) Tables.

Table 1a
Pressure Relationships and Ventilation of Certain Areas
Minimum Air Changes ofMinimum
PressureOutdoor AirTotal AirAll Air
RelationshipPer HourChanges PerExhaustedRecirculated
to AdjacentSupplied toHour SuppliedDirectly toWithin Room
Room Name or Area DesignationAreasRoomto RoomOutdoorsUnits
Resident's room:
General * 2 4 Optional Optional
Bed * 2 4 Optional Optional
Toilet room Negative Optional 10 Yes No
Medication room Positive 2 4 Optional Optional
Consultation room * 2 6 Optional Optional
Clean workroom Positive 2 4 Optional Optional
Soiled workroom Negative 2 10 Yes No
Housekeeping Negative Optional 10 Yes No
Public restroom Negative Optional 10 Yes No
Living, dining, and recreation room * 2 4 Optional Optional
Nourishment area * 2 4 Optional Optional
Kitchen and other food
preparation and serving areas * 2 10 Yes Yes
Warewashing room Negative Optional 10 Yes Yes
Food storage (nonrefrigerated) * Optional 2 Yes No
Den * 2 4 Optional Optional
Central bath and showers Negative Optional 10 Yes No
Soiled Linen Sorting and Storage Negative Optional 10 Yes No
Laundry, Processing * 2 10 Yes No
Clean Linen Storage Positive Optional 2 Yes No
Multipurpose room * 2 4 Optional Optional
Rehabilitation room Negative 2 6 Optional Optional
Beauty and barber shop Negative 2 10 Yes No
Corridors * Optional 2 Optional Optional
Designated smoking area Negative Optional 20 Yes No
* Continuous directional control not required

Resident's Room Equal 2 2 Optional Optional
Resident Area Corridor Equal Optional 2 Optional Optional
Examination and Treatment Room Equal 2 6 Optional Optional
Physical Therapy Negative 2 6 Optional Optional
Activities Room Negative 2 6 Optional Optional
Soiled Workroom Negative 2 10 Yes No
Medicine Preparation and
Clean Workroom Positive 2 4 Optional Optional
Toilet Room Negative Optional 10 Yes No
Bathroom Negative Optional 10 Yes No
Janitors' Closets Negative Optional 10 Yes No
Linen and Trash Chute Rooms Negative Optional 10 Yes No
Food Preparation Center Equal 2 10 Yes No
Warewashing Room Negative Optional 10 Yes No
Dietary Dry Storage Equal Optional 2 Yes No
Laundry, Processing Room Equal 2 10 Yes No
Soiled Linen Sorting and Storage Negative Optional 10 Yes No
Clean Linen Storage Positive Optional 2 Optional Optional
Personal Care Room Negative 2 6 Yes No
Designated Smoking Area Negative Optional 20 Yes No

Table 2a
Artificial Light Requirements
Light Measured
Placein Foot-CandlesWhere Measured
Resident's room:
General 30 Three feet above floor
Bed 30 Mattress top level, at bed wall to three feet out from bed wall
Toilet room 30 Three feet above floor
Medication preparation 30 Counter level
Nurses' work area and office:
General 30 Three feet above floor
Desk and charts 50 Desk level
Medication room 100 Counter level
Consultation room 30 Three feet above floor
Clean and soiled workrooms 30 Counter level
Storage room 30 Three feet above floor
Housekeeping 30 Three feet above floor
Public restroom 30 Floor level
Living, recreation rooms 30 Three feet above floor
Dining room 50 Table level
Nourishment area 50 Counter level
Kitchen in a resident unit 50 Counter level
Central kitchen (includes food preparation and serving areas) 70 Counter level
Food storage (nonrefrigerated) 30 Three feet above floor
Den 30 Chair or table level
Reading and other specialized areas (may be portable lamp) 70 Chair or table level
Central bath and showers 30 Three feet above floor
Laundry 30 Three feet above floor
Multipurpose room 30 Three feet above floor
Rehabilitation room 30 Three feet above floor
Beauty and barber shop 50 Counter level
Corridors:
Resident waking hours 30 Floor level
Resident sleeping hours 10 Floor level
Stairways 20 Step level

Exits:
Resident waking hours 30 Floor level
Resident sleeping hours 10 Floor level
Maintenance service and equipment area 30 Floor level
Heating plant space 30 Floor level

Table 2b
Artificial Light Requirements
Light Measured
Placein Foot-CandlesWhere Measured
Kitchen in a resident unit 50 Counter level
Central kitchen (includes food preparation and serving areas) 70 Counter level
Dining Room 25 Table level
Living room or recreation room
General 15 Three feet above floor
Reading and other specialized areas (may be portable lamp) 50 Chair or table level
Nurses' station and office:
General 20 Three feet above floor
Desk and charts 50 Desk level
Clean workroom 30 Counter level
Medication room 100 Counter level
Central bath and showers 30 Three feet above floor
Resident's room:
General 10 Three feet above floor
Bed 30 Mattress top level, at bed wall
to three feet out from bed wall
Laundry 30 Three feet above floor
Janitor's closet 15 Three feet above floor
Storage room:
General 5 Three feet above floor
Disinfectant or cleaning agent storage area 15 Three feet above floor
Corridors 10 Floor level
Stairways 20 Step level
Exits 5 Floor level
Heating plant space 5 Floor level

Kan. Admin. Regs. § 26-40-305

Authorized by and implementing K.S.A. 39-932; effective Jan. 7, 2011.