675 Ind. Admin. Code 17-1.8-13

Current through August 28, 2024
Section 675 IAC 17-1.8-13 - Section 300.3; conductors

Authority: IC 22-13-2-2; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 13.

Add Section 300.3(D), entitled "Separation from corrugated stainless steel tubing", and add text to read as follows: All wiring methods shall be isolated from corrugated stainless steel tubing by a space separation of at least 2 inches except where the bonding connection is made.

675 IAC 17-1.8-13

Fire Prevention and Building Safety Commission; 675 IAC 17-1.8-13; filed Jul 27, 2009, 10:39 a.m.: 20090826-IR-675090140FRA
Readopted filed 7/17/2015, 3:40 p.m.: 20150812-IR-675140473RFA
Readopted filed 7/8/2021, 3:18 p.m.: 20210804-IR-675210166RFA

Agency cited as 675 IAC 17-1.8-14, which was renumbered by the Publisher as 675 IAC 17-1.8-13.